Skip to main content

Inspection visit

Complaint

FAIRWINDS - WOODWARD PARKLicense 1072011561 citation on this visit
1 citation recorded

Inspector’s narrative

What the inspector wrote

LPA interviewed various residents through out the facility. It was stated to LPA facility took from 7 days to 3 weeks to fix AC units. As LPA toured the facility and went to all three floors, LPA observed thermostats to not be in working order. Example one thermostat in the hallway of the third floor East Wing was set to 80 degrees F and the temperature read 86 degrees F. In another hallway first floor East Wing was set to 74 degrees F and read 81 degrees F. LPA observed the stairwell door from the third floor open with the window open. Current outside temperature is showing at 91 degrees F 1. The Department investigated the allegation: Staff did not ensure HVAC was working properly. LPA toured the facility and observed facility to not be at a comfortable temperature. LPA observed thermostats at the facility to read at 79 degrees or above when thermostats were set to a lower temperature. Based on LPAs observations and interviews which were conducted and record review(s), the preponderance of evidence standard has been met, therefore the above allegation(s) is found to be SUBSTANTIATED. California Code of Regulations, (Title 22, Division 6 & Chapter number 8), are being cited on the attached LIC 9099D. Exit interviewed conducted with AD, copies of LIC9099, LIC9099C, and LIC9099D were provided.

Citations

1 citation recorded*CCLD

What does Type A vs Type B mean?

Type A. Serious citation. Imminent or substantial risk to children. The regulator requires corrective action immediately and may impose a civil penalty.

Type B. Lower-severity citation. Corrective action required, no imminent risk. The regulator monitors compliance on the next visit.

  • Cool occupied rooms to regulated temperature range

    87303(b)(2) Maintenance and Operation(b) A comfortable temperature for residents shall be maintained at all times.(2) The facility shall cool rooms to a comfortable range, between 78 degrees F (26 degrees C) and 85 degrees F (30 degrees C), or in areas of extreme heat to 30 degrees F less than the outside temperature.This requirement is not met as evidenced by: Based on LPAs observations, interview, and record reviews, the licensee did not comply with the section cited above which poses an immediate health, safety or personal rights risk to persons in care. LPA observed various thermostats which did not show AC to be working properly. LPA conducted various interviews which stated facility took 7 days or longer to repair AC units in apartments.

FAQ · About this visit

Common questions about this visit

What happened during the May 18, 2023 inspection of FAIRWINDS - WOODWARD PARK?

This was a complaint inspection of FAIRWINDS - WOODWARD PARK on May 18, 2023. 1 citation were issued: 1 Type A (serious).

Were any citations issued to FAIRWINDS - WOODWARD PARK on May 18, 2023?

Yes, 1 citation was issued (1 Type A, 0 Type B). The first citation was for: "87303(b)(2) Maintenance and Operation(b) A comfortable temperature for residents shall be maintained at all times.(2) Th..."

What type of inspection was this?

This was a complaint inspection. Complaint inspections are triggered when someone reports a concern about the facility to CCLD.

Share this reportEmail

Next steps

If this is your facility,claim this pageand correct anything the record gets wrong. Free.

Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.

Data from CCLD public records. Last updated . If you believe any information is inaccurate, report it here.