Skip to main content

Inspection visit

Follow-up on corrections

VALLEY VIEW RETIREMENT CENTERLicense 1976004301 citation on this visit
1 citation recorded

Inspector’s narrative

What the inspector wrote

Licensing Program Analyst (LPA) Emily Peraldi conducted an unannounced Case Management-Deficiencies inspection visit at the facility today due to a deficiency observed during the investigation of a complaint visit conducted on 06/21/2022. Between 1:00 p.m. and 3:20 p.m., the LPA along with the Administrator, conducted a physical plant tour. Between 3:15 p.m. and 3:40 p.m., the LPA observed hot water to be measured between 126.0 and 138.1-degree Fahrenheit. At 3:40 p.m., the Administrator observed the hot water temperature and requested maintenance and plumbing services to set the hot water no more than 120-degree Fahrenheit. At 4:15 p.m., staff adjusted the water temperature and the LPA observed the hot water temperature to be measured at 110.4-degree Fahrenheit. Pursuant to Title 22 of the CA Code of Regulations, the following deficiency was cited (refer to LIC 809-D). Civil Penalties issued in the amount of $250.00. Exit interview conducted with Administrator. A copy of the report, civil penalties and appeals rights were reviewed and emailed to the Administrator.

Citations

1 citation recorded*CCLD

What does Type A vs Type B mean?

Type A. Serious citation. Imminent or substantial risk to children. The regulator requires corrective action immediately and may impose a civil penalty.

Type B. Lower-severity citation. Corrective action required, no imminent risk. The regulator monitors compliance on the next visit.

  • 87303(e)(2)Type A

    87303(e)(2) Maintenance and Operation Hot water temperature controls shall be maintained to ...of hot water used by residents to attain a temperature of not less than 105 degree F (41 degrees C) and not more than 120 degree F (49 degrees C). This requirement is not met as evidenced by: Based on observation, the licensee did not comply with the section cited above in as the water temperature in resident bathrooms measured between 126.0 and 138.1 degrees F which poses an immediate health, and safety risk to persons in care.

FAQ · About this visit

Common questions about this visit

What happened during the June 21, 2022 inspection of VALLEY VIEW RETIREMENT CENTER?

This was a other inspection of VALLEY VIEW RETIREMENT CENTER on June 21, 2022. 1 citation were issued: 1 Type A (serious).

Were any citations issued to VALLEY VIEW RETIREMENT CENTER on June 21, 2022?

Yes, 1 citation was issued (1 Type A, 0 Type B). The first citation was for: "87303(e)(2) Maintenance and Operation Hot water temperature controls shall be maintained to ...of hot water used by ..."

What type of inspection was this?

This was a other inspection. other inspections are conducted by CCLD as part of their licensing oversight.

SourceView on CCLDView original report