Skip to main content

Inspection visit

Follow-up on corrections

COURTYARD PLAZALicense 1976035601 citation on this visit
1 citation recorded

Inspector’s narrative

What the inspector wrote

Licensing Program Analysts (LPAs) Salia Walker and Sandra Urena conducted an unannounced Case Management-Deficiencies visit at the facility today, due to deficiencies observed during the investigation of complaint control #29-AS-20220708115334. The LPAs met with Administrator Evelina Papazyan at 9:10 a.m. Entrance interview conducted. From 9:16 a.m. until 10:40 a.m.; and from 2:00 p.m. until 3:00 p.m., LPAs Walker, Urena, and Administrator Evelina Papazyan conducted a physical plant tour. During the physical plant tour, a random selection of ten (10) resident rooms were inspected. At 9:46 a.m., LPA Walker was advised by Resident #1 (R1) that the facility hot water temperatures were elevated. Five (5) out of ten (10) resident rooms hot water temperatures measure between 121.7 and 129.5 degrees Fahrenheit. The LPAs advised the Administrator faucets used by residents for personal care shall maintain hot water temperatures of not less than 105 degree F (41 degree C) and not more than 120 degree F (49 degree C). The Administrator acknowledged. Pursuant to Title 22 of the CA Code of Regulations, the following deficiency was cited (refer to LIC 809-D). Exit interview conducted. A copy of the report, and appeal rights were provided.

Citations

1 citation recorded*CCLD

What does Type A vs Type B mean?

Type A. Serious citation. Imminent or substantial risk to children. The regulator requires corrective action immediately and may impose a civil penalty.

Type B. Lower-severity citation. Corrective action required, no imminent risk. The regulator monitors compliance on the next visit.

  • 87303(e)(2)Type A

    87303(e)(2) Water supplies and plumbing fixtures shall be maintained as follows: (2) Faucets.. shall deliver.. hot water.. not less than 105 degree F (41 degree C) and not more than 120 degree F (49 degree C).This requirement is not met as evidenced by: Based on LPAs observation, the licensee failed to ensure hot water temperature measured within 105 to 120 degrees F in resident rooms which poses an immediate health, and safety risk to residents in care.

FAQ · About this visit

Common questions about this visit

What happened during the July 13, 2022 inspection of COURTYARD PLAZA?

This was a other inspection of COURTYARD PLAZA on July 13, 2022. 1 citation were issued: 1 Type A (serious).

Were any citations issued to COURTYARD PLAZA on July 13, 2022?

Yes, 1 citation was issued (1 Type A, 0 Type B). The first citation was for: "87303(e)(2) Water supplies and plumbing fixtures shall be maintained as follows: (2) Faucets.. shall deliver.. hot water..."

What type of inspection was this?

This was a other inspection. other inspections are conducted by CCLD as part of their licensing oversight.

SourceView on CCLDView original report