GLEN TERRA ASSISTED LIVINGLicense 1976090051 citation on this visit
1 citation recorded

Inspector’s narrative

What the inspector wrote

On today's date, Licensing Program Analyst (LPA) Christine Wong conducted an initial complaint investigation at the facility and during the complaint investigation and LPA toured of the facility including some residents' rooms including Rm#111, #120 and #214 and LPA measured the hot water temperature at three of the residents' rooms and they tested between 122.6 and 124.7 which is out of the range of Title 22 regulations. According to the California Code of Regulations (Title 22, Division 6, Chapter 8), LPA observed the following deficiency and issued a citation. An exit interview was conducted and a copy of the Facility Evaluation Report and Appeal Rights were provided to Administrator Carlos Lara

Citations

1 citation recorded*CCLD

What does Type A vs Type B mean?

Type A. Serious citation. Imminent or substantial risk to children. The regulator requires corrective action immediately and may impose a civil penalty.

Type B. Lower-severity citation. Corrective action required, no imminent risk. The regulator monitors compliance on the next visit.

  • 87303(e)(2)Type A

    87303 Maintenance and Operation (e)Water supplies and plumbing fixtures shall be maintained as follows: (2)(2) Faucets used by residents for personal care such as shaving and grooming shall deliver hot water. Hot water temperature controls shall be maintained to automatically regulate the temperature of hot water used by residents to attain a temperature of not less than 105 degree F (41 degree C) and not more than 120 degree F (49 degree C). The requirement was not met as evidenced by LPA observation, LPA inspected RM#111, #120 and #214 and hot water was measured between 122.6 to 124.7 which posed an immediate risk to the residents in care

FAQ · About this visit

Common questions about this visit

What happened during the March 29, 2022 inspection of GLEN TERRA ASSISTED LIVING?

This was a other inspection of GLEN TERRA ASSISTED LIVING on March 29, 2022. 1 citation were issued: 1 Type A (serious).

Were any citations issued to GLEN TERRA ASSISTED LIVING on March 29, 2022?

Yes, 1 citation was issued (1 Type A, 0 Type B). The first citation was for: "87303 Maintenance and Operation (e)Water supplies and plumbing fixtures shall be maintained as follows: (2)(2) Faucets u..."

What type of inspection was this?

This was a other inspection. other inspections are conducted by CCLD as part of their licensing oversight.

SourceView on CCLDView original report