Skip to main content

Inspection visit

Follow-up

SAKURA GARDENS AT LOS ANGELESLicense 1986021921 citation on this visit
1 citation recorded

Inspector’s narrative

What the inspector wrote

Licensing Program Analyst (LPA) Christian Gutierrez generated this Case Management - Deficiencies report in conjunction with complaint control 28-AS-20241204135046 pertaining to observations made during the physical plant inspection. The purpose of the report was explained to Business Office manager Alfonso Lozoya. At 10:55 AM, during the tour of physical plant inspection LPA Gutierrez checked water temperature in rooms and observed room #137 water temperature at 133.4F, room# 212 water temperature at 134F and room# 206 water temperature at 132.3F not in between the required range of 105-120 degrees F. Based on observation, a citation is being issued. See LIC 809D. An exit interview was conducted, and a copy of the report and appeal rights were issued.

Citations

1 citation recorded*CCLD

What does Type A vs Type B mean?

Type A. Serious citation. Imminent or substantial risk to children. The regulator requires corrective action immediately and may impose a civil penalty.

Type B. Lower-severity citation. Corrective action required, no imminent risk. The regulator monitors compliance on the next visit.

  • Provide resident hot water for personal care

    87303 Maintenance and Operation(e) Water supplies and plumbing fixtures shall be maintained as follows:(2) Faucets used by residents for personal care such as shaving and grooming shall deliver hot water. Hot water temperature controls shall be maintained to automatically regulate the temperature of hot water used by residents to attain a temperature of not less than 105 degree F (41 degree C) and not more than 120 degree F (49 degree C). Based on Observations three (3) out of four (4) bathrooms hot water did not measure between the required range of 105-120 degree.

FAQ · About this visit

Common questions about this visit

What happened during the December 9, 2024 inspection of SAKURA GARDENS AT LOS ANGELES?

This was an other inspection of SAKURA GARDENS AT LOS ANGELES on December 9, 2024. 1 citation were issued: 1 Type A (serious).

Were any citations issued to SAKURA GARDENS AT LOS ANGELES on December 9, 2024?

Yes, 1 citation was issued (1 Type A, 0 Type B). The first citation was for: "87303 Maintenance and Operation(e) Water supplies and plumbing fixtures shall be maintained as follows:(2) Faucets used ..."

What type of inspection was this?

This was an other inspection. other inspections are conducted by CCLD as part of their licensing oversight.