Skip to main content

Inspection visit

Follow-up on corrections

PASADENA VILLA SENIOR LIVINGLicense 1986032861 citation on this visit
1 citation recorded

Inspector’s narrative

What the inspector wrote

Licensing Program Analyst (LPA) Bennette Pena conducted an unannounced Case Management Deficiencies in conjunction with a complaint visit (Complaint Control # 28-AS-20240520102446 ). The purpose of this visit is to issue deficiency that was observed by LPA that is not part of the complaint allegations. During the visit on 5/21/2024, LPA conducted a tour of the facility, and tested the water temperature in the community shower rooms. LPA observed that there was no hot water in any of the stalls in the community shower rooms. Water readings measured by LPA were: 90.8 deg F in stall #1, 98.6 deg F in stall #2 and 89.2 deg F in stall #3, all stalls were in the large community shower room. Interview with S1 confirmed tha t there has been no hot water due to a plumbing issue in the community shower rooms and that the water pressure was very low or water only dripped in some stalls. S1 indicated that a plumber already came in April 2024 and provided them the estimate. Some residents interviewed stated that only cold water was available and there was no hot water in the shower rooms. Deficiency is noted on LIC 809D. Exit interview, a copy of this report and Appeals Rights were provided to Alexander Solorio, Assistant Administrator.

Citations

1 citation recorded*CCLD

What does Type A vs Type B mean?

Type A. Serious citation. Imminent or substantial risk to children. The regulator requires corrective action immediately and may impose a civil penalty.

Type B. Lower-severity citation. Corrective action required, no imminent risk. The regulator monitors compliance on the next visit.

  • 87303(e)(2)Type A

    87303 Maintenance and Operation (e) Water supplies and plumbing fixtures shall be maintained as follows:(2) Faucets used by residents for personal care.... shall deliver hot water. Hot water temperature controls shall be maintained... to attain a temperature of not less than 105 degree F (41 degree C) and not more than 120 degree F (49 degree C).This requirement is not met as evidenced by: Based on interviews and observation, the hot water temperature readings during the visit on 5/21/2024 were 90.8 deg F in stall #1, 98.6 deg F in stall #2 and 89.2 deg F in stall #3, all stalls were in the large community shower room which poses an immediate health and safety risk to residents in care.

FAQ · About this visit

Common questions about this visit

What happened during the July 26, 2024 inspection of PASADENA VILLA SENIOR LIVING?

This was a other inspection of PASADENA VILLA SENIOR LIVING on July 26, 2024. 1 citation were issued: 1 Type A (serious).

Were any citations issued to PASADENA VILLA SENIOR LIVING on July 26, 2024?

Yes, 1 citation was issued (1 Type A, 0 Type B). The first citation was for: "87303 Maintenance and Operation (e) Water supplies and plumbing fixtures shall be maintained as follows:(2) Faucets used..."

What type of inspection was this?

This was a other inspection. other inspections are conducted by CCLD as part of their licensing oversight.

SourceView on CCLDView original report

Share this reportEmail

Next steps

If this is your facility,claim this pageand correct anything the record gets wrong. Free.

Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.

Data from CCLD public records. Last updated . If you believe any information is inaccurate, report it here.