Inspection visit

Follow-up on corrections

ELEONOR'S PLACE 4License 3060059271 citation on this visit
1 citation recorded

Inspector’s narrative

What the inspector wrote

On June 13, 2025, Licensing Program Analyst (LPA) Kevin Saborit-Guasch conducted a case management visit for in order to issue a citation for a deficiency observed during the investigation of complaint 22-AS-20250609144753 and unrelated to the allegations listed on the complaint. During the tour of the physical plant, LPA measured the temperature of the water dispensed by two faucets used for personal grooming in a shared bathroom along with the temperature of the water dispensed by the wall-mounted shower in the same bathroom. Water was measured to be delivered at 130F at all three outlets. A type A deficiency is issued during the visit. Facility staff was able to adjust the water heater during the visit. A second measurement was made in two separate bathrooms and showed the adjusted water temperature to be approximately 112F in both locations. Deficiency cleared during the visit. Based on the observation made during today's visit, one type A deficiency is being cited. An exit interview was conducted and a copy of this report along with appeal rights were provided to a facility representative.

Citations

2 citations recorded*CCLD

What does Type A vs Type B mean?

Type A. Serious citation. Imminent or substantial risk to children. The regulator requires corrective action immediately and may impose a civil penalty.

Type B. Lower-severity citation. Corrective action required, no imminent risk. The regulator monitors compliance on the next visit.

  • 87303(e)(2)Type A

    Per CCR 87303(2): "Hot water temperature controls shall be maintained to automatically regulate the temperature of hot water used by residents to attain a temperature of not less than 105 degree F and not more than 120 degree F". This requirement is not met as evidenced by: Based on observation conducted during the visit, water temperature was measured in three separate locations to be provided at a temperature in excess of 130F which constitutes an immediate risk to the health, safety and personal rights of individuals in care.

  • 87303(a)Type A

    Per CCR Section 87303(a) Maintenance and Operation: "(a) The facility shall be clean, safe, sanitary and in good repair at all times". This requirement is not met as evidenced by: Based on observation, two thermostatic faucets in one of the shared bathrooms were found to be loose and difficult to adjust. This constitutes an immediate risk to the health, safety and personal rights of individuals in care.

FAQ · About this visit

Common questions about this visit

What happened during the June 13, 2025 inspection of ELEONOR'S PLACE 4?

This was a other inspection of ELEONOR'S PLACE 4 on June 13, 2025. 1 citation were issued: 1 Type A (serious).

Were any citations issued to ELEONOR'S PLACE 4 on June 13, 2025?

Yes, 1 citation was issued (1 Type A, 0 Type B). The first citation was for: "Per CCR 87303(2): "Hot water temperature controls shall be maintained to automatically regulate the temperature of hot w..."

What type of inspection was this?

This was a other inspection. other inspections are conducted by CCLD as part of their licensing oversight.

SourceView on CCLDView original report