Inspection visit

Fire Safety inspection

ROCKY POINT CARE CENTERCMS #05549917 citations on this visit
17 citations recorded

Citations

17 citations recorded*CMS

This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.

What do CMS severity letters mean?

Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.

General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.

Each letter combines severity with scope: how many residents the deficiency affected.

  • 0347GeneralS&S Epotential for harm

    Properly provide smoke detection systems in areas open to corridors.

  • 0013GeneralS&S Epotential for harm

    Develop Emergency Preparedness policies and procedures.

  • 0029GeneralS&S Epotential for harm

    Develop a communication plan.

  • 0031GeneralS&S Epotential for harm

    Provide emergency officials' contact information.

  • 0039GeneralS&S Epotential for harm

    Conduct testing and exercise requirements.

  • 0321GeneralS&S Dpotential for harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

  • 0345GeneralS&S Epotential for harm

    Have approved installation, maintenance and testing program for fire alarm systems.

  • 0352GeneralS&S Fpotential for harm

    Properly install and monitor supervisory attachments on automatic sprinkler systems.

  • 0004GeneralS&S Epotential for harm

    Develop and maintain an Emergency Preparedness Program (EP).

  • 0036GeneralS&S Epotential for harm

    Establish emergency prep training and testing.

  • 0353GeneralS&S Epotential for harm

    Inspect, test, and maintain automatic sprinkler systems.

  • 0355GeneralS&S Dpotential for harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

  • 0363GeneralS&S Epotential for harm

    Install corridor and hallway doors that block smoke.

  • 0372GeneralS&S Epotential for harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

  • 0712GeneralS&S Epotential for harm

    Have simulated fire drills held at unexpected times.

  • 0920GeneralS&S Epotential for harm

    Ensure proper usage of power strips and extension cords.

  • 0926GeneralS&S Epotential for harm

    Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.

FAQ · About this visit

Common questions about this visit

What happened during the June 21, 2024 survey of ROCKY POINT CARE CENTER?

This was a inspection survey of ROCKY POINT CARE CENTER on June 21, 2024. The surveyor cited 17 deficiencies, recorded on the federal Form 2567 statement of deficiencies.

Were any deficiencies cited at ROCKY POINT CARE CENTER on June 21, 2024?

Yes, 17 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Properly provide smoke detection systems in areas open to corridors."

What type of survey was this?

This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.

Share this reportEmail

Next steps

Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.

Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.

Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.