F 0684
Provide appropriate treatment and care according to orders, resident’s preferences and goals.
Level of Harm - Minimal harm
or potential for actual harm
**NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** Based on
observation, interview, and record review, the facility failed to document ventilator alarm checks every 4
hours, on the ventilator flow sheets, as specified in the facility ' s policy and procedure, Mechanical
Ventilation, for 3 out of 3 residents.
Residents Affected - Some
This failure could have resulted in facility staff to be unaware of a ventilated resident ' s respiratory decline
or faulty ventilator
setting.
Findings:
On [DATE], at 12:00 p.m., an unannounced visit was made to the facility for a Quality-of-Care issue.
1) A review of Resident 1 ' s SBAR (Situation, Backround, Assessment, Recommendations), dated, [DATE],
at 11:34, by RN 1, stated, . LN (Licensed Nurse) reported to RN (Registered Nurse) that (Resident 1) is
unresponsive. Upon assessment, (Resident 1) was unresponsive, blue color, no pulse. Code blue called
and CPR (Cardio-Pulmonary Resuscitation, life saving measures) was initiated and called 911 .
Review of Resident1 ' s face sheet, indicated, resident was admitted to the facility on [DATE], with a
diagnosis of Acute and chronic respiratory failure with hypoxia (Impairment of oxygen exchange between
the lungs and blood, causing a decreased amount of oxygen in the blood); Tracheostomy (An opening
made in the wind pipe to help air and oxygen reach the lungs); Dependance on respirator [Ventilator] (A
machine that can be connected to a tracheostomy to move air in and out of the lungs). Further review of
Resident1 ' s medical records indicated, resident could not breath independently, and required the constant
assistance of a ventilator machine, connected to his tracheostomy, to breath.
On [DATE], at 1:36 p.m., an interview was conducted with RN 1. RN 1 stated, She was giving report to the
oncoming nurse at nursing station; rounds were being done by additional staff, and a staff called from
(Resident 1 ' s) room that the resident was unreponsive. RN1 was in the nursing station just across from
(Resident 1 ' s) room, and she did not remember a ventilator alarm going off at the time of being notified
resident was unresponsive. RN1 further stated, the ventilator alarms are Really loud, and they alarm at the
nurse ' s station, light up above the resident ' s room, and shows what room the ventilator is alarming down
the hall on the screen.
On [DATE], at 5:12 p.m., an interview was conducted with RN2, who stated, she was Just coming on to
(continued on next page)
Any deficiency statement ending with an asterisk (*) denotes a deficiency which the institution may be excused from correcting providing it is determined that other
safeguards provide sufficient protection to the patients. (See instructions.) Except for nursing homes, the findings stated above are disclosable 90 days following the
date of survey whether or not a plan of correction is provided. For nursing homes, the above findings and plans of correction are disclosable 14 days following the date
these documents are made available to the facility. If deficiencies are cited, an approved plan of correction is requisite to continued program participation.
LABORATORY DIRECTOR'S OR PROVIDER/SUPPLIER
REPRESENTATIVE'S SIGNATURE
TITLE
(X6) DATE
FORM CMS-2567 (02/99)
Previous Versions Obsolete
Facility ID:
If continuation sheet
Page 1 of 3
Event ID:
056229
Printed: 05/15/2026
Form Approved OMB
No. 0938-0391
Department of Health & Human Services
Centers for Medicare & Medicaid Services
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION
(X1) PROVIDER/SUPPLIER/CLIA
IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
056229
B. Wing
A. Building
(X3) DATE SURVEY
COMPLETED
11/08/2023
NAME OF PROVIDER OR SUPPLIER
STREET ADDRESS, CITY, STATE, ZIP CODE
Palm Springs Healthcare & Rehabilitation Center
277 S Sunrise Way
Palm Springs, CA 92262
For information on the nursing home's plan to correct this deficiency, please contact the nursing home or the state survey agency.
(X4) ID PREFIX TAG
SUMMARY STATEMENT OF DEFICIENCIES
(Each deficiency must be preceded by full regulatory or LSC identifying information)
F 0684
Level of Harm - Minimal harm
or potential for actual harm
Residents Affected - Some
shift, during report, she heard RN1. RN1 stated (Resident1) was unresponsive and called for help, RN2
Called the code blue, (A medical emergency, where a resident requires immediate medical attention, most
often the results of a respiratory or heart heart failure) went into (Resident1 ' s) room, she observed RT1
(Respiratory Therapist) Started CPR. RN2 further stated, she was across the hall from Resident1 ' s room,
when the Code Blue was called, and Didn ' t hear the ventilator alarm go off, stating, No ventillator Alarms
were going off.
On [DATE], at 3:10 p.m., an interview was conducted with Respiratory Therapist (RT1), who stated,
Resident1 was on full ventilator support (Requires the ventilator to breath). Nursing staff found (Resident1)
unresponsive and called a code blue, and RT responded to the code. I was down the hall. The ventilator
was not alarming on the monitor or in the room. RT1 Helped with CPR by doing compressions, until (First
responders) showed up. RT1 further stated, At the beginning of the RT ' s shifts they do a vent check which
includes checking the setting on the alarms, this check is done every 6 hours, and documented in the
resident ' s progress notes (Medical records).
On [DATE], at 12:55 p.m., an interview was conducted with the facilities Lead RT (LRT). The LRT stated,
The (ventilator) alarm link is attatched to the side of the ventilator. I do a check (on ventilator alarms) every
Monday for corporate, making sure everthing is plugged in, working properly, etc. Every RT comes on shift
and checks their (Resident ' s ventilator) alarms by (visually) checking the parameters of the alarm, then
(RT) begins their tracheostomy care, and when the resident is suctioned, the alarm will go off. The alarms
are very loud. Ventilator alarm checks are done at the beginnning of shift and every 4 hours. (Alarm check
documentation) is on Matrix under progress notes, and pop-ups (Flow sheets).
A review of the facility ' s Policy & Procedure, titled, Mechanical Ventilation, undated, reference, RC2
0528.00, indicated, .Producedure . 3. The ventilator flowsheet will be maintained every four hours . 10.
Check the ventilator alarms to be sure they are poroperly set before leaving the room and with every vent
(ventilator) check (every four hours) . Documentation: On Ventilator Flow Sheet: Record ventilator checks,
minimally every four hours .
Review of Resident1 ' s RT progress notes, dated [DATE], (The date of the code blue) at 3:51 a.m.,
indicated, . Received patient . (Ventilator) alarms connected and audible .
Review of Resident 1 ' s, Ventilator Flow Sheet, titled, Respiratory Therapy Minutes, dated [DATE], at 2:41
p.m., indicated, no documented ventilation alarm checks, every 4 hours.
2) On [DATE], at 1:45 p.m., an observation of Sub-Acute Unit, and ventilator alarms was conducted with
SAC. Observed nursing staff monitoring ventilated residents from their bedside, visually checking their
ventilator settings, and assisting residents with tracheostomy care. A ventillator was observed alarming in
Resident 2s room. The Alarm was loud, a light lite up above resident ' s doorway, and Resident 2 ' s room
number (3) was observed on a screen down in the hallway. SAC responded to the alarm immediately by
suctioning resident (Clearing the airway of secretions or mucus), ventilator alarm continued to alert during
suctioning, and reset by SAC, after care was performed.
A review of Resident 2 ' s clinical records, face sheet was conducted, and indicated, Resident 2 was
admitted to the facility on [DATE], with a diagnosis of Acute and chronic respiratory failure; Tracheostomy;
On a Ventilator.
Review of Resident 2 ' s RT progress notes, dated [DATE], indicated, . Patient received . Vent
(continued on next page)
FORM CMS-2567 (02/99)
Previous Versions Obsolete
Event ID:
Facility ID:
056229
If continuation sheet
Page 2 of 3
Printed: 05/15/2026
Form Approved OMB
No. 0938-0391
Department of Health & Human Services
Centers for Medicare & Medicaid Services
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION
(X1) PROVIDER/SUPPLIER/CLIA
IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
056229
B. Wing
A. Building
(X3) DATE SURVEY
COMPLETED
11/08/2023
NAME OF PROVIDER OR SUPPLIER
STREET ADDRESS, CITY, STATE, ZIP CODE
Palm Springs Healthcare & Rehabilitation Center
277 S Sunrise Way
Palm Springs, CA 92262
For information on the nursing home's plan to correct this deficiency, please contact the nursing home or the state survey agency.
(X4) ID PREFIX TAG
SUMMARY STATEMENT OF DEFICIENCIES
(Each deficiency must be preceded by full regulatory or LSC identifying information)
F 0684
alarms are connected and audible .
Level of Harm - Minimal harm
or potential for actual harm
A review of Resident 2 ' s, ventilator flow sheet, titled, Respiratory Therapy Minutes, dated, [DATE], at 2:52,
indicated, no documented ventilator alarm checks, every 4 hours, on the ventilator flow sheet.
Residents Affected - Some
A review of the facility ' s Policy & Procedure, titled, Mechanical Ventilation, undated, reference, RC2
0528.00, indicated, .Producedure . 3. The ventilator flowsheet will be maintained every four hours . 10.
Check the ventilator alarms to be sure they are poroperly set before leaving the room and with every vent
(ventilator) check (every four hours) . Documentation: On Ventilator Flow Sheet: Record ventilator checks,
minimally every four hours .
3) On [DATE], at 2:25 p.m., an observation of Resident 3 conducted, which indicated, resident sleeping in
bed, with a ventilator connected to his tracheostomy, resident ' s chest observed rising and falling with
ventilator assistance.
A review of Resident 3 ' s clinical records, face sheet was conduceted, and indicated, Resident 3 was
admitted to the facility on [DATE], with a diagnosis of Acute respiratory failure; Dependance on ventilator.
Review of Resident 3 ' s RT progress notes, dated, [DATE], at 2:31 a.m., indicated, Patient received .
(Plus)5 alarms on and audible .
A review of Resident 3 ' s, ventilator flow sheet, titled, Respiratory Therapy Minutes, dated [DATE], at 2:42
p.m., indicated, no documented ventilator alarm checks, every 4 hours.
On [DATE], at 10:43 a.m., an interview was conducted with the facility ' s Administrator (Admin). Admin
stated, she verified with the Sub-Acute Coordinator (SAC) that visual ventilator alarm checks are being
performed by RT ' s every 4 hours, for every resident on a ventilator. Admin further verified, she had
Reviewed the (RTs) progress notes, and ventilator alarm checks have been documented at the start of RTs
shift, when they receive the residents care, but the alarm ventilator Checks are not being documented
consistently (Every 4 hours), per facility policy and procedure (Mechanical Ventilation).
A review of the facility ' s Policy & Procedure, titled, Mechanical Ventilation, undated, reference, RC2
0528.00, indicated, .Producedure . 3. The ventilator flowsheet will be maintained every four hours . 10.
Check the ventilator alarms to be sure they are poroperly set before leaving the room and with every vent
(ventilator) check (every four hours) . Documentation: On Ventilator Flow Sheet: Record ventilator checks,
minimally every four hours .
FORM CMS-2567 (02/99)
Previous Versions Obsolete
Event ID:
Facility ID:
056229
If continuation sheet
Page 3 of 3