Inspection visit

Fire Safety inspection

SOUTH PLATTE REHABILITATION AND NURSING LLCCMS #06517014 citations on this visit
14 citations recorded

Citations

14 citations recorded*CMS

This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.

What do CMS severity letters mean?

Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.

General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.

Each letter combines severity with scope: how many residents the deficiency affected.

  • 0222GeneralS&S Fpotential for harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

  • 0271GeneralS&S Fpotential for harm

    Have exits that are accessible at all times.

  • 0281GeneralS&S Fpotential for harm

    Install proper backup exit lighting.

  • 0291GeneralS&S Fpotential for harm

    Install emergency lighting that can last at least 1 1/2 hours.

  • 0324GeneralS&S Epotential for harm

    Provide properly protected cooking facilities.

  • 0345GeneralS&S Fpotential for harm

    Have approved installation, maintenance and testing program for fire alarm systems.

  • 0353GeneralS&S Fpotential for harm

    Inspect, test, and maintain automatic sprinkler systems.

  • 0355GeneralS&S Epotential for harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

  • 0363GeneralS&S Epotential for harm

    Install corridor and hallway doors that block smoke.

  • 0372GeneralS&S Fpotential for harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

  • 0511GeneralS&S Fpotential for harm

    Have properly installed electrical wiring and gas equipment.

  • 0521GeneralS&S Epotential for harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

  • 0712GeneralS&S Fpotential for harm

    Have simulated fire drills held at unexpected times.

  • 0923GeneralS&S Epotential for harm

    Have proper medical gas storage and administration areas.

FAQ · About this visit

Common questions about this visit

What happened during the May 18, 2023 survey of SOUTH PLATTE REHABILITATION AND NURSING LLC?

This was a inspection survey of SOUTH PLATTE REHABILITATION AND NURSING LLC on May 18, 2023. The surveyor cited 14 deficiencies, recorded on the federal Form 2567 statement of deficiencies.

Were any deficiencies cited at SOUTH PLATTE REHABILITATION AND NURSING LLC on May 18, 2023?

Yes, 14 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arra..."

What type of survey was this?

This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.