Inspection visit
Fire Safety inspection
Citations
16 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0345GeneralS&S Dpotential for harm
Have approved installation, maintenance and testing program for fire alarm systems.
- 0037GeneralS&S Dpotential for harm
Establish staff and initial training requirements.
- 0211GeneralS&S Dpotential for harm
Keep aisles, corridors, and exits free of obstruction in case of emergency.
- 0222GeneralS&S Dpotential for harm
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
- 0223GeneralS&S Dpotential for harm
Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
- 0347GeneralS&S Dpotential for harm
Properly provide smoke detection systems in areas open to corridors.
- 0351GeneralS&S Dpotential for harm
Install an approved automatic sprinkler system.
- 0353GeneralS&S Dpotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0372GeneralS&S Dpotential for harm
Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
- 0521GeneralS&S Dpotential for harm
Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
- 0700GeneralS&S Dpotential for harm
Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors.
- 0711GeneralS&S Dpotential for harm
Provide a written emergency evacuation plan.
- 0712GeneralS&S Dpotential for harm
Have simulated fire drills held at unexpected times.
- 0761GeneralS&S Dpotential for harm
To conduct inspection, testing and maintenance of fire doors by qualified individuals.
- 0918GeneralS&S Dpotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0324GeneralS&S Dpotential for harm
Provide properly protected cooking facilities.
FAQ · About this visit
Common questions about this visit
What happened during the September 29, 2023 survey of APPLE REHAB COCCOMO?
This was a inspection survey of APPLE REHAB COCCOMO on September 29, 2023. The surveyor cited 16 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at APPLE REHAB COCCOMO on September 29, 2023?
Yes, 16 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Have approved installation, maintenance and testing program for fire alarm systems."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.
SourceView on CMS Care Compare
Next steps
Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.
Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.
Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.