CROSSVIEW CARE CENTERCMS #11554113 citations on this visit
13 citations recorded

Citations

13 citations recorded*CMS

This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.

What do CMS severity letters mean?

Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.

General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.

Each letter combines severity with scope: how many residents the deficiency affected.

  • 0511GeneralS&S Epotential for harm

    Have properly installed electrical wiring and gas equipment.

  • 0211GeneralS&S Epotential for harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

  • 0223GeneralS&S Epotential for harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

  • 0227GeneralS&S Epotential for harm

    Have ramps, exits, fire escape ladders, steps, and areas of refuge that meet safety requirements.

  • 0311GeneralS&S Fpotential for harm

    Have an enclosure around a vertical opening shaft.

  • 0321GeneralS&S Epotential for harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

  • 0324GeneralS&S Epotential for harm

    Provide properly protected cooking facilities.

  • 0353GeneralS&S Dpotential for harm

    Inspect, test, and maintain automatic sprinkler systems.

  • 0355GeneralS&S Dpotential for harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

  • 0372GeneralS&S Epotential for harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

  • 0741GeneralS&S Dpotential for harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

  • 0923GeneralS&S Dpotential for harm

    Have proper medical gas storage and administration areas.

  • 0004GeneralS&S Dpotential for harm

    Develop and maintain an Emergency Preparedness Program (EP).

FAQ · About this visit

Common questions about this visit

What happened during the July 21, 2022 survey of CROSSVIEW CARE CENTER?

This was a inspection survey of CROSSVIEW CARE CENTER on July 21, 2022. The surveyor cited 13 deficiencies, recorded on the federal Form 2567 statement of deficiencies.

Were any deficiencies cited at CROSSVIEW CARE CENTER on July 21, 2022?

Yes, 13 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Have properly installed electrical wiring and gas equipment."

What type of survey was this?

This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.