Inspection visit
Fire Safety inspection
Citations
14 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0211GeneralS&S Epotential for harm
Keep aisles, corridors, and exits free of obstruction in case of emergency.
- 0223GeneralS&S Epotential for harm
Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
- 0321GeneralS&S Epotential for harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
- 0324GeneralS&S Epotential for harm
Provide properly protected cooking facilities.
- 0351GeneralS&S Fpotential for harm
Install an approved automatic sprinkler system.
- 0353GeneralS&S Fpotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0363GeneralS&S Epotential for harm
Install corridor and hallway doors that block smoke.
- 0531GeneralS&S Epotential for harm
Have elevators that firefighters can control in the event of a fire.
- 0712GeneralS&S Fpotential for harm
Have simulated fire drills held at unexpected times.
- 0761GeneralS&S Fpotential for harm
To conduct inspection, testing and maintenance of fire doors by qualified individuals.
- 0914GeneralS&S Epotential for harm
Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
- 0918GeneralS&S Fpotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0926GeneralS&S Fpotential for harm
Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.
- 0039GeneralS&S Fpotential for harm
Conduct testing and exercise requirements.
FAQ · About this visit
Common questions about this visit
What happened during the July 26, 2024 survey of SOUTH SHORE REHABILITATION?
This was a inspection survey of SOUTH SHORE REHABILITATION on July 26, 2024. The surveyor cited 14 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at SOUTH SHORE REHABILITATION on July 26, 2024?
Yes, 14 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Keep aisles, corridors, and exits free of obstruction in case of emergency."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.
SourceView on CMS Care Compare