Inspection visit
Fire Safety inspection
Citations
15 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0037GeneralS&S Cno actual harm
Establish staff and initial training requirements.
- 0041GeneralS&S Fpotential for harm
Implement emergency and standby power systems.
- 0232GeneralS&S Fpotential for harm
Have corridors or aisles that are unobstructed and are at least 8 feet in width.
- 0321GeneralS&S Epotential for harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
- 0324GeneralS&S Epotential for harm
Provide properly protected cooking facilities.
- 0341GeneralS&S Fpotential for harm
Install a fire alarm system that can be heard throughout the facility.
- 0346GeneralS&S Fpotential for harm
Follow proper procedures when the fire alarm was out of service for more than 4 hours.
- 0354GeneralS&S Cno actual harm
Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.
- 0355GeneralS&S Epotential for harm
Properly select, install, inspect, or maintain portable fire extinguishes.
- 0741GeneralS&S Epotential for harm
Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
- 0753GeneralS&S Epotential for harm
Have restrictions on the use of highly flammable decorations.
- 0918GeneralS&S Fpotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0920GeneralS&S Epotential for harm
Ensure proper usage of power strips and extension cords.
- 0921GeneralS&S Fpotential for harm
Ensure that testing and maintenance of electrical equipment is performed.
- 0927GeneralS&S Epotential for harm
Have proper fire barriers, ventilation and signs for the transfilling of oxygen.
FAQ · About this visit
Common questions about this visit
What happened during the June 27, 2025 survey of WATERS OF RUSHVILLE SKILLED NURSING FACILITY, THE?
This was a inspection survey of WATERS OF RUSHVILLE SKILLED NURSING FACILITY, THE on June 27, 2025. The surveyor cited 15 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at WATERS OF RUSHVILLE SKILLED NURSING FACILITY, THE on June 27, 2025?
Yes, 15 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Establish staff and initial training requirements."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.
SourceView on CMS Care Compare