Inspection visit
Fire Safety inspection
Citations
12 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0041GeneralS&S Fpotential for harm
Implement emergency and standby power systems.
- 0222GeneralS&S Fpotential for harm
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
- 0291GeneralS&S Fpotential for harm
Install emergency lighting that can last at least 1 1/2 hours.
- 0353GeneralS&S Fpotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0362GeneralS&S Epotential for harm
Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.
- 0363GeneralS&S Epotential for harm
Install corridor and hallway doors that block smoke.
- 0521GeneralS&S Fpotential for harm
Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
- 0918GeneralS&S Fpotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0920GeneralS&S Epotential for harm
Ensure proper usage of power strips and extension cords.
- 0372GeneralS&S Epotential for harm
Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
- 0374GeneralS&S Epotential for harm
Install smoke barrier doors that can resist smoke for at least 20 minutes.
- 0511GeneralS&S Fpotential for harm
Have properly installed electrical wiring and gas equipment.
FAQ · About this visit
Common questions about this visit
What happened during the December 2, 2022 survey of SEYMOUR CROSSING?
This was a inspection survey of SEYMOUR CROSSING on December 2, 2022. The surveyor cited 12 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at SEYMOUR CROSSING on December 2, 2022?
Yes, 12 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Implement emergency and standby power systems."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.
SourceView on CMS Care Compare
Next steps
Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.
Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.
Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.