Inspection visit
Fire Safety inspection
Citations
16 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0291GeneralS&S Fpotential for harm
Install emergency lighting that can last at least 1 1/2 hours.
- 0293GeneralS&S Fpotential for harm
Have properly located and lighted "Exit" signs.
- 0300GeneralS&S Fpotential for harm
Meet other general requirements that are deficient.
- 0914GeneralS&S Fpotential for harm
Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
- 0041GeneralS&S Cno actual harm
Implement emergency and standby power systems.
- 0222GeneralS&S Epotential for harm
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
- 0281GeneralS&S Epotential for harm
Install proper backup exit lighting.
- 0346GeneralS&S Fpotential for harm
Follow proper procedures when the fire alarm was out of service for more than 4 hours.
- 0353GeneralS&S Epotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0354GeneralS&S Fpotential for harm
Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.
- 0374GeneralS&S Fpotential for harm
Install smoke barrier doors that can resist smoke for at least 20 minutes.
- 0711GeneralS&S Fpotential for harm
Provide a written emergency evacuation plan.
- 0754GeneralS&S Epotential for harm
Provide properly sized and located linen or trash receptacles.
- 0918GeneralS&S Cno actual harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0921GeneralS&S Fpotential for harm
Ensure that testing and maintenance of electrical equipment is performed.
- 0923GeneralS&S Epotential for harm
Have proper medical gas storage and administration areas.
FAQ · About this visit
Common questions about this visit
What happened during the May 8, 2025 survey of ROLLING HILLS HEALTHCARE CENTER?
This was a inspection survey of ROLLING HILLS HEALTHCARE CENTER on May 8, 2025. The surveyor cited 16 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at ROLLING HILLS HEALTHCARE CENTER on May 8, 2025?
Yes, 16 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Install emergency lighting that can last at least 1 1/2 hours."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.