Inspection visit
Fire Safety inspection
Citations
16 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0030GeneralS&S Fpotential for harm
List the names and contact information of those in the facility.
- 0161GeneralS&S Dpotential for harm
Use approved construction type or materials.
- 0291GeneralS&S Epotential for harm
Install emergency lighting that can last at least 1 1/2 hours.
- 0293GeneralS&S Dpotential for harm
Have properly located and lighted "Exit" signs.
- 0321GeneralS&S Epotential for harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
- 0324GeneralS&S Fpotential for harm
Provide properly protected cooking facilities.
- 0345GeneralS&S Fpotential for harm
Have approved installation, maintenance and testing program for fire alarm systems.
- 0346GeneralS&S Fpotential for harm
Follow proper procedures when the fire alarm was out of service for more than 4 hours.
- 0353GeneralS&S Fpotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0355GeneralS&S Dpotential for harm
Properly select, install, inspect, or maintain portable fire extinguishes.
- 0362GeneralS&S Epotential for harm
Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.
- 0363GeneralS&S Dpotential for harm
Install corridor and hallway doors that block smoke.
- 0511GeneralS&S Dpotential for harm
Have properly installed electrical wiring and gas equipment.
- 0741GeneralS&S Dpotential for harm
Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
- 0914GeneralS&S Fpotential for harm
Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
- 0918GeneralS&S Fpotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
FAQ · About this visit
Common questions about this visit
What happened during the July 9, 2022 survey of Centerville Specialty Care?
This was a inspection survey of Centerville Specialty Care on July 9, 2022. The surveyor cited 16 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at Centerville Specialty Care on July 9, 2022?
Yes, 16 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "List the names and contact information of those in the facility."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.
SourceView on CMS Care Compare
Next steps
Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.
Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.
Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.