LIST OF DEFICIENCIES
LIFE CARE CENTER OF PENSACOLA 3291 EAST OLIVE RD PENSACOLA, FL 32514
PREFIX TAG ID PREFIX TAG DEFICIENCY) COMPLETION DATE
E 000 Initial Comments E 000
During the recertification survey conducted on 03/27/2023 at Life Care Center of Pensacola, a nursing home, the Emergency Preparedness Program (EP) was reviewed. Life Care Center of Pensacola complies with the Emergency Preparedness rule per Code of Federal Regulations (CFR) 42, Part 483.73, and Requirement for Long-Term Care Facilities.
K 000 INITIAL COMMENTS K 000
An unannounced Fire & Life Safety recertification survey was conducted 03/27/2023 at Life Care Center of Pensacola, a nursing home in Pensacola, Florida. Life Care Center of Pensacola is not in compliance with 42 CFR 483 Subpart B, 42 CFR 488.307, and National Fire Protection Association (NFPA) 101 (2012 edition) requirements for nursing homes. Initial Plan Review: 2005 Existing NFPA 220 Construction Type: II (111) Number of beds: 120 Census: 98
K 324 Cooking Facilities SS=D CFR(s): NFPA 101
K 324 4/30/23
Cooking Facilities Cooking equipment is protected in accordance with NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, unless: * residential cooking equipment (i.e., small appliances such as microwaves, hot plates, toasters) are used for food warming or limited cooking in accordance with 18.3.2.5.2, 19.3.2.5.2
**LIFE CARE CENTER OF PENSACOLA**
**3291 EAST OLIVE RD** **PENSACOLA, FL 32514**
K 324 | Continued From page 1 * cooking facilities open to the corridor in smoke compartments with 30 or fewer patients comply with the conditions under 18.3.2.5.3, 19.3.2.5.3, or * cooking facilities in smoke compartments with 30 or fewer patients comply with conditions under 18.3.2.5.4, 19.3.2.5.4. Cooking facilities protected according to NFPA 96 per 9.2.3 are not required to be enclosed as hazardous areas, but shall not be open to the corridor. 18.3.2.5.1 through 18.3.2.5.4, 19.3.2.5.1 through 19.3.2.5.5, 9.2.3, TIA 12-2
This REQUIREMENT is not met as evidenced by:
Based on observation and interview with the Maintenance Director, it was determined that the facility failed to maintain the kitchen hood system which would allow grease-laden vapors to build up in the seams resulting in a potential fire above the hood suppression system which could endanger the building occupants.
The findings include:
During the Fire & Life Safety tour of the facility with the Maintenance Director on 03/27/2023, between 10:30 AM and 1:30 PM, it was observed that the facility failed to maintain the kitchen hood system, the dietary kitchen was observed to have caulked missing and falling out of the seams. The Maintenance Director verified these findings at the times observed. Per NFPA 96 (2011 edition) 5.1.4. per NFPA 101 (2012 Edition) 19.3.2.5, 9.2.3
K 324
K324
1. The caulk missing and falling out of the seams in the kitchen hood system was replaced. 2. The Director of Plant Operations conducted an inspection of the kitchen hood system to assure no other areas were affected with caulk that was missing or falling out. No other areas were
106073 03/27/2023
LIFE CARE CENTER OF PENSACOLA 3291 EAST OLIVE RD PENSACOLA, FL 32514
ID PREFIX TAG PREFIX TAG DEFICIENCY) COMPLETION DATE
K 324 Continued From page 2
K 324 identified. 3. The Director of Plant Operations/designee will randomly audit the kitchen hood system to assure caulk is in place and not falling out or missing. 4. The results of the audits will be presented to the QAPI committee monthly for the next 3 months.
K 351 Sprinkler System - Installation SS=D CFR(s): NFPA 101
K 351 4/30/23
Sprinkler System - Installation 2012 EXISTING Nursing homes, and hospitals where required by construction type, are protected throughout by an approved automatic sprinkler system in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems. In Type I and II construction, alternative protection measures are permitted to be substituted for sprinkler protection in specific areas where state or local regulations prohibit sprinklers. In hospitals, sprinklers are not required in clothes closets of patient sleeping rooms where the area of the closet does not exceed 6 square feet and sprinkler coverage covers the closet floor as required by NFPA 13, Standard for Installation of Sprinkler Systems. 19.3.5.1, 19.3.5.2, 19.3.5.3, 19.3.5.4, 19.3.5.5, 19.4.2, 19.3.5.10, 9.7, 9.7.1.1(1) This REQUIREMENT is not met as evidenced by:
Based on observation and interview with the Maintenance Director during tour of the facility, the automatic sprinkler system was not installed in accordance with NFPA 13. This in the event of fire could delay or deny extinguishment of a fire.
K351 1. The sprinkler located above the ceiling at the Garden Nurses station was scheduled to be moved. 2. The Director of Plant Operations
106073
03/27/2023
LIFE CARE CENTER OF PENSACOLA
3291 EAST OLIVE RD PENSACOLA, FL 32514
PREFIX TAG
ID PREFIX TAG
DEFICIENCY)
COMPLETION DATE
K 351
Continued From page 3 The findings include:
During the Fire & Life Safety tour of the facility with the Maintenance Director on 03/27/2023, between 10:30 AM and 1:30 PM, it was observed that the sprinkler located above the ceiling at the Garden Nurses station was blocked by the air conditioner duct work.
Maintenance Director verified these findings at the times observed.
According to NFPA 13 (2010 edition) 8.5.5.2.2; "Sprinklers shall be positioned in accordance with the minimum distances and special requirements of Section 8.6 through Section 8.12 so that they are located sufficiently away from obstructions such as truss webs and chords, pipes, columns, and fixtures."
K 351
conducted an inspection to determine if there were other areas where a sprinkler was blocked by the air condition duct work. No other area was identified.
3. The Director of Plant Operations/Designee will audit weekly to assure compliance.
4. Results of the audit will be presented to the QAPI committee monthly for the next 3 months.
K 363 SS=D
CFR(s): NFPA 101
Corridor - Doors Doors protecting corridor openings in other than required enclosures of vertical openings, exits, or hazardous areas resist the passage of smoke and are made of 1 3/4 inch solid-bonded core wood or other material capable of resisting fire for at least 20 minutes. Doors in fully sprinklered smoke compartments are only required to resist the passage of smoke. Corridor doors and doors to rooms containing flammable or combustible materials have positive latching hardware. Roller latches are prohibited by CMS regulation. These requirements do not apply to auxiliary spaces that do not contain flammable or combustible material. Clearance between bottom of door and floor covering is not exceeding 1 inch. Powered doors
K 363
4/30/23
LIST OF DEFICIENCIES 03/27/2023 LIFE CARE CENTER OF PENSACOLA 3291 EAST OLIVE RD PENSACOLA, FL 32514 PREFIX TAG ID PREFIX TAG DEFICIENCY) COMPLETION DATE
K 363 Continued From page 4 complying with 7.2.1.9 are permissible if provided with a device capable of keeping the door closed when a force of 5 lbf is applied. There is no impediment to the closing of the doors. Hold open devices that release when the door is pushed or pulled are permitted. Nonrated protective plates of unlimited height are permitted. Dutch doors meeting 19.3.6.3.6 are permitted. Door frames shall be labeled and made of steel or other materials in compliance with 8.3, unless the smoke compartment is sprinklered. Fixed fire window assemblies are allowed per 8.3. In sprinklered compartments there are no restrictions in area or fire resistance of glass or frames in window assemblies.
19.3.6.3, 42 CFR Parts 403, 418, 460, 482, 483, and 485
Show in REMARKS details of doors such as a fire protection ratings, automatics closing devices, etc.
This REQUIREMENT is not met as evidenced by:
Based on observation and interview with the Maintenance Director, the facility failed to maintain proper maintenance of the Fire/Smoke doors. This condition could result in (2) Smoke Compartments becoming involved in a Fire/Smoke situation. This could allow fire, smoke, and fire gases to enter the compartment, which would impede or deny the exiting of occupants in an emergency and result in harm to the occupants from the dangers of the emergency.
The findings include:
During the Fire & Life Safety tour of the facility with the Maintenance Director on 03/27/2023,
K 363
K363 1. The Seville Hall storage room located in the family room has a door closure installed.
The self-closing double doors next to room 226 had the latch fixed so that the door now latches.
The 1st floor Director of Nursing:’s office had the latch fixed on the storage room.
The 1st floor La Pav family room had the self-closing double doors latch fixed so that the door latches.
2. The director of Plant Operations
106073
03/27/2023
LIFE CARE CENTER OF PENSACOLA
3291 EAST OLIVE RD PENSACOLA, FL 32514
PREFIX TAG
ID PREFIX TAG
DEFICIENCY)
COMPLETION DATE
K 363 Continued From page 5 between 10:30 AM and 1:30 PM, it was observed that several Smoke doors were not closing properly. 1. Savel Hall, storage room located in the family room needs a door closure installed. 2. Self-closing double doors next to room 226, not latching. 3. Room 242, not latching. 4. On the 1st floor, the Director of Nursing's office has a storage room located inside the room, which needs a door closure placed on it. 5. On the 1st floor LaPav family room, self-closing double doors not latching.
The Maintenance Director verified these findings at the times observed.
NFPA 101, (2012 edition,) Chapter 19, 19.3.6.3.5, "Doors shall be provided with a means for keeping the door closed that is acceptable to the AHJ."
K 371 Subdivision of Building Spaces - Smoke Compar SS=D CFR(s): NFPA 101 Subdivision of Building Spaces - Smoke Compartments 2012 EXISTING Smoke barriers shall be provided to form at least two smoke compartments on every sleeping floor with a 30 or more patient bed capacity. Size of compartments cannot exceed 22,500 square feet or a 200-foot travel distance from any point in the compartment to a door in the smoke barrier. 19.3.7.1, 19.3.7.2 Detail in REMARKS zone dimensions including length of zones and dead-end corridors. This REQUIREMENT is not met as evidenced by:
K 363 conducted an inspection of other smoke doors to determine if they closed properly and addressed their needs.
3. The Director of Plant Operations/designee will conduct weekly audits to assure smoke doors close properly.
4. The results of the audits will be presented to the QAPI committee monthly for the next 3 months.
K 371 4/30/23
LIST OF DEFICIENCIES 106073 03/27/2023 LIFE CARE CENTER OF PENSACOLA 3291 EAST OLIVE RD PENSACOLA, FL 32514 ID PREFIX TAG PREFIX TAG DEFICIENCY) COMPLETION DATE
K 371 Continued From page 6
K 371
Based on observation and interview with the
K371 Maintenance Director, the facility failed to 1. The mechanical room next to room properly maintain the required Fire/Smoke barrier 208 had the two penetrations thru the wall penetrations, which have not been fire stopped or were properly fire stopped. smoke sealed. This condition could allow The 2nd floor service stairs had the Fire/Smoke to travel from one compartment to penetration thru the wall above the ceiling, other compartments, thus endangering occupants were properly fire stopped. of the facility. The self-closing double doors next to The findings include: room 227, south wall above the ceiling During the Fire & Life Safety tour of the facility was properly fire stopped. with the Maintenance Director on 03/27/2023, The 1st floor, La Pav, equipment room between 10:30 AM and 1:30 PM, it was found that spray foam was removed and properly fire penetrations through the wall have not been fire stopped. stopped or smoke sealed. The following locations The mechanical room on the 1st floor next were observed to have penetrations. to the staff lounge had the spray foam 1. Mechanical room to room 208, two removed and was properly fire stopped. penetrations through the wall 2. The Director of Plant Operations 2. 2nd floor, service stairs, penetration through conducted an inspection of other areas the wall above the ceiling tiles with the potential to need fire 3. Self-closing double doors next to room, 227, stopped/smoke sealed. south wall above the ceiling, penetration through 3. The Director of Plant Operations will wall randomly audit areas with fire caulk 4. On the 1st floor, LaPav, equipment room, installed to assure the areas noted are spray foam was used to seal a pipe in the floor, properly protected with required fire caulk. facility was unable to provide any fire rating on 4. The results of the random audits will foam. be presented to the QAPI committee 5. On the 1st floor, LaPav, electrical room, monthly for the next 3 months. spray foam was used to seal a pipe in the floor, facility was unable to provide any fire rating on the foam. 6. Mechanical room on 1st floor next to staff lounge, spray foam was used to seal a pipe in the floor, facility was unable to provide any fire rating on the foam.
All locations were not properly protected with the required fire caulk. The Maintenance Director
106073 03/27/2023 LIFE CARE CENTER OF PENSACOLA 3291 EAST OLIVE RD PENSACOLA, FL 32514 ID PREFIX TAG PREFIX TAG TAG DEFICIENCY) COMPLETION DATE
K 371 Continued From page 7
K 371 verified these findings at the times observed. According to NFPA 101(2012 edition) 8.4.4 & 8.4.4.1 and 19.3.7.6
K 923 Gas Equipment - Cylinder and Container Storag SS=D CFR(s): NFPA 101
K 923 4/30/23 Gas Equipment - Cylinder and Container Storage Greater than or equal to 3,000 cubic feet Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3. >300 but <3,000 cubic feet Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating. Less than or equal to 300 cubic feet In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2. A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING." Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure
| LIFE CARE CENTER OF PENSACOLA | 3291 EAST OLIVE RD PENSACOLA, FL 32514 |
|---|---|---|---|
K 923 Continued From page 8 considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather. 11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 [NFPA 99] This REQUIREMENT is not met as evidenced by:
Based on observation and interview with the Maintenance Director, the facility failed to properly store compressed medical gas cylinders in accordance with NFPA 99, Health Care Facilities Code. Improper storage of medical gas cylinders could result in the rupture of the cylinders and subsequent accelerated development of fire, smoke, and fire gases in a fire situation. The findings include:
During the Fire & Life Safety tour of the facility with the Maintenance Director on 03/27/2023, between 10:30 AM and 1:30 PM, the following were observed at the rear of the building: 1. 4 H-size oxygen cylinders were left free standing on the sidewalk unsecured 2. 49, E-size oxygen cylinders were left unsecured on the sidewalk 3. Resident room 206, an E-size oxygen cylinder was observed free standing in the room.
The Maintenance Director verified these findings at the times observed. Medical gas storage, handling of cylinders, and administration shall be in accordance with NFPA 99 (2018 edition) Chapters 5 and 11, and NFPA 101 (2018 edition) 19.3.2.4
K 923
K923 1. The 4 H sized oxygen cylinders that were left standing on the sidewalk were secured. The 49 E-size oxygen cylinders were secured. The E size cylinder in room 206 was secured.
2. Education provided to associates regarding proper securing and storage of oxygen tanks.
3. The Director of Plant Operations/designee will randomly audit the facility for appropriately stored and secured oxygen tanks. 4. The results of the audit will be presented to the QAPI committee for the next 3 months.