Skip to main content

Inspection visit

Fire Safety inspection

HALSTEAD HEALTH AND REHABILITATION CENTERCMS #17544614 citations on this visit
14 citations recorded

Citations

14 citations recorded*CMS

This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.

What do CMS severity letters mean?

Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.

General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.

Each letter combines severity with scope: how many residents the deficiency affected.

  • 0291GeneralS&S Fpotential for harm

    Install emergency lighting that can last at least 1 1/2 hours.

  • 0321GeneralS&S Fpotential for harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

  • 0345GeneralS&S Epotential for harm

    Have approved installation, maintenance and testing program for fire alarm systems.

  • 0353GeneralS&S Fpotential for harm

    Inspect, test, and maintain automatic sprinkler systems.

  • 0363GeneralS&S Epotential for harm

    Install corridor and hallway doors that block smoke.

  • 0511GeneralS&S Fpotential for harm

    Have properly installed electrical wiring and gas equipment.

  • 0522GeneralS&S Epotential for harm

    Have an externally vented heating system.

  • 0712GeneralS&S Fpotential for harm

    Have simulated fire drills held at unexpected times.

  • 0761GeneralS&S Fpotential for harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

  • 0918GeneralS&S Fpotential for harm

    Have generator or other power source capable of supplying service within 10 seconds.

  • 0923GeneralS&S Dpotential for harm

    Have proper medical gas storage and administration areas.

  • 0041GeneralS&S Fpotential for harm

    Implement emergency and standby power systems.

  • 0222GeneralS&S Fpotential for harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

  • 0324GeneralS&S Fpotential for harm

    Provide properly protected cooking facilities.

FAQ · About this visit

Common questions about this visit

What happened during the May 20, 2024 survey of HALSTEAD HEALTH AND REHABILITATION CENTER?

This was a inspection survey of HALSTEAD HEALTH AND REHABILITATION CENTER on May 20, 2024. The surveyor cited 14 deficiencies, recorded on the federal Form 2567 statement of deficiencies.

Were any deficiencies cited at HALSTEAD HEALTH AND REHABILITATION CENTER on May 20, 2024?

Yes, 14 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Install emergency lighting that can last at least 1 1/2 hours."

What type of survey was this?

This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.

Share this reportEmail

Next steps

Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.

Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.

Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.