Inspection visit
Fire Safety inspection
Citations
14 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0131GeneralS&S Fpotential for harm
Meet requirements for sections of health care facilities separated by fire resistive construction.
- 0161GeneralS&S Dpotential for harm
Use approved construction type or materials.
- 0211GeneralS&S Epotential for harm
Keep aisles, corridors, and exits free of obstruction in case of emergency.
- 0321GeneralS&S Dpotential for harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
- 0324GeneralS&S Dpotential for harm
Provide properly protected cooking facilities.
- 0342GeneralS&S Epotential for harm
Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
- 0345GeneralS&S Fpotential for harm
Have approved installation, maintenance and testing program for fire alarm systems.
- 0353GeneralS&S Dpotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0363GeneralS&S Epotential for harm
Install corridor and hallway doors that block smoke.
- 0753GeneralS&S Fpotential for harm
Have restrictions on the use of highly flammable decorations.
- 0912GeneralS&S Dpotential for harm
Have power receptacles that are properly grounded.
- 0918GeneralS&S Fpotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0920GeneralS&S Dpotential for harm
Ensure proper usage of power strips and extension cords.
- 0923GeneralS&S Epotential for harm
Have proper medical gas storage and administration areas.
FAQ · About this visit
Common questions about this visit
What happened during the February 11, 2026 survey of VIA CHRISTI VILLAGE RIDGE?
This was a inspection survey of VIA CHRISTI VILLAGE RIDGE on February 11, 2026. The surveyor cited 14 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at VIA CHRISTI VILLAGE RIDGE on February 11, 2026?
Yes, 14 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Meet requirements for sections of health care facilities separated by fire resistive construction."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.
SourceView on CMS Care Compare
Next steps
Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.
Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.
Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.