Inspection visit

Fire Safety inspection

ODD FELLOWS HEALTH CARE CENTERCMS #20517032 citations on this visit
32 citations recorded

Citations

32 citations recorded*CMS

This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.

What do CMS severity letters mean?

Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.

General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.

Each letter combines severity with scope: how many residents the deficiency affected.

  • 0920GeneralS&S Dpotential for harm

    Ensure proper usage of power strips and extension cords.

  • 0007GeneralS&S Fpotential for harm

    Address patient/client population and determine types of services needed.

  • 0015GeneralS&S Fpotential for harm

    Address subsistence needs for staff and patients.

  • 0023GeneralS&S Fpotential for harm

    Establish policies and procedures for medical documentation.

  • 0025GeneralS&S Fpotential for harm

    Create arrangements with other facilities to receive patients.

  • 0029GeneralS&S Fpotential for harm

    Develop a communication plan.

  • 0030GeneralS&S Fpotential for harm

    List the names and contact information of those in the facility.

  • 0031GeneralS&S Fpotential for harm

    Provide emergency officials' contact information.

  • 0032GeneralS&S Fpotential for harm

    Provide primary/alternate means for communication.

  • 0033GeneralS&S Fpotential for harm

    Establish methods for sharing information.

  • 0034GeneralS&S Fpotential for harm

    Provide a means of sharing information on occupancy/needs.

  • 0036GeneralS&S Fpotential for harm

    Establish emergency prep training and testing.

  • 0039GeneralS&S Fpotential for harm

    Conduct testing and exercise requirements.

  • 0041GeneralS&S Fpotential for harm

    Implement emergency and standby power systems.

  • 0131GeneralS&S Fpotential for harm

    Meet requirements for sections of health care facilities separated by fire resistive construction.

  • 0133GeneralS&S Dpotential for harm

    Install a two-hour-resistant firewall separation.

  • 0211GeneralS&S Dpotential for harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

  • 0222GeneralS&S Dpotential for harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

  • 0291GeneralS&S Dpotential for harm

    Install emergency lighting that can last at least 1 1/2 hours.

  • 0321GeneralS&S Dpotential for harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

  • 0353GeneralS&S Dpotential for harm

    Inspect, test, and maintain automatic sprinkler systems.

  • 0355GeneralS&S Fpotential for harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

  • 0541GeneralS&S Fpotential for harm

    Install properly constructed and protected linen or trash chutes.

  • 0751GeneralS&S Dpotential for harm

    Have restrictions on the use of flammable curtains.

  • 0754GeneralS&S Dpotential for harm

    Provide properly sized and located linen or trash receptacles.

  • 0761GeneralS&S Dpotential for harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

  • 0911GeneralS&S Dpotential for harm

    Meet requirements for the installation and maintenance of electrical systems.

  • 0914GeneralS&S Dpotential for harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

  • 0918GeneralS&S Dpotential for harm

    Have generator or other power source capable of supplying service within 10 seconds.

  • 0923GeneralS&S Dpotential for harm

    Have proper medical gas storage and administration areas.

  • 0700GeneralS&S Dpotential for harm

    Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors.

  • 0712GeneralS&S Fpotential for harm

    Have simulated fire drills held at unexpected times.

FAQ · About this visit

Common questions about this visit

What happened during the March 20, 2025 survey of ODD FELLOWS HEALTH CARE CENTER?

This was a inspection survey of ODD FELLOWS HEALTH CARE CENTER on March 20, 2025. The surveyor cited 32 deficiencies, recorded on the federal Form 2567 statement of deficiencies.

Were any deficiencies cited at ODD FELLOWS HEALTH CARE CENTER on March 20, 2025?

Yes, 32 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Ensure proper usage of power strips and extension cords."

What type of survey was this?

This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.