Inspection visit

Fire Safety inspection

WILLOWBROOKE CT SKILLED CARE CTR AT BAYLEIGH CHASECMS #21513713 citations on this visit
13 citations recorded

Citations

13 citations recorded*CMS

This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.

What do CMS severity letters mean?

Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.

General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.

Each letter combines severity with scope: how many residents the deficiency affected.

  • 0211GeneralS&S Dpotential for harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

  • 0223GeneralS&S Dpotential for harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

  • 0324GeneralS&S Fpotential for harm

    Provide properly protected cooking facilities.

  • 0345GeneralS&S Epotential for harm

    Have approved installation, maintenance and testing program for fire alarm systems.

  • 0351GeneralS&S Epotential for harm

    Install an approved automatic sprinkler system.

  • 0353GeneralS&S Dpotential for harm

    Inspect, test, and maintain automatic sprinkler systems.

  • 0363GeneralS&S Epotential for harm

    Install corridor and hallway doors that block smoke.

  • 0500GeneralS&S Fpotential for harm

    Meet other general requirements that are deficient.

  • 0521GeneralS&S Dpotential for harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

  • 0761GeneralS&S Fpotential for harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

  • 0916GeneralS&S Fpotential for harm

    Have a battery powered remote alarm panel in a location accessible by operating personnel.

  • 0918GeneralS&S Fpotential for harm

    Have generator or other power source capable of supplying service within 10 seconds.

  • 0511GeneralS&S Dpotential for harm

    Have properly installed electrical wiring and gas equipment.

FAQ · About this visit

Common questions about this visit

What happened during the July 12, 2019 survey of WILLOWBROOKE CT SKILLED CARE CTR AT BAYLEIGH CHASE?

This was a inspection survey of WILLOWBROOKE CT SKILLED CARE CTR AT BAYLEIGH CHASE on July 12, 2019. The surveyor cited 13 deficiencies, recorded on the federal Form 2567 statement of deficiencies.

Were any deficiencies cited at WILLOWBROOKE CT SKILLED CARE CTR AT BAYLEIGH CHASE on July 12, 2019?

Yes, 13 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Keep aisles, corridors, and exits free of obstruction in case of emergency."

What type of survey was this?

This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.