Inspection visit
Fire Safety inspection
Citations
13 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0211GeneralS&S Dpotential for harm
Keep aisles, corridors, and exits free of obstruction in case of emergency.
- 0223GeneralS&S Dpotential for harm
Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
- 0324GeneralS&S Fpotential for harm
Provide properly protected cooking facilities.
- 0345GeneralS&S Epotential for harm
Have approved installation, maintenance and testing program for fire alarm systems.
- 0351GeneralS&S Epotential for harm
Install an approved automatic sprinkler system.
- 0353GeneralS&S Dpotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0363GeneralS&S Epotential for harm
Install corridor and hallway doors that block smoke.
- 0500GeneralS&S Fpotential for harm
Meet other general requirements that are deficient.
- 0521GeneralS&S Dpotential for harm
Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
- 0761GeneralS&S Fpotential for harm
To conduct inspection, testing and maintenance of fire doors by qualified individuals.
- 0916GeneralS&S Fpotential for harm
Have a battery powered remote alarm panel in a location accessible by operating personnel.
- 0918GeneralS&S Fpotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0511GeneralS&S Dpotential for harm
Have properly installed electrical wiring and gas equipment.
FAQ · About this visit
Common questions about this visit
What happened during the July 12, 2019 survey of WILLOWBROOKE CT SKILLED CARE CTR AT BAYLEIGH CHASE?
This was a inspection survey of WILLOWBROOKE CT SKILLED CARE CTR AT BAYLEIGH CHASE on July 12, 2019. The surveyor cited 13 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at WILLOWBROOKE CT SKILLED CARE CTR AT BAYLEIGH CHASE on July 12, 2019?
Yes, 13 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Keep aisles, corridors, and exits free of obstruction in case of emergency."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.
SourceView on CMS Care Compare
Next steps
Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.
Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.
Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.