Inspection visit
Fire Safety inspection
Citations
14 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0223GeneralS&S Dpotential for harm
Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
- 0321GeneralS&S Dpotential for harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
- 0324GeneralS&S Fpotential for harm
Provide properly protected cooking facilities.
- 0353GeneralS&S Dpotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0355GeneralS&S Dpotential for harm
Properly select, install, inspect, or maintain portable fire extinguishes.
- 0525GeneralS&S Fpotential for harm
Enure that solid fuel-burning fireplaces are not in patient sleeping areas.
- 0712GeneralS&S Dpotential for harm
Have simulated fire drills held at unexpected times.
- 0761GeneralS&S Dpotential for harm
To conduct inspection, testing and maintenance of fire doors by qualified individuals.
- 0100GeneralS&S Epotential for harm
Meet other general requirements.
- 0211GeneralS&S Dpotential for harm
Keep aisles, corridors, and exits free of obstruction in case of emergency.
- 0914GeneralS&S Fpotential for harm
Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
- 0918GeneralS&S Fpotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0920GeneralS&S Dpotential for harm
Ensure proper usage of power strips and extension cords.
- 0923GeneralS&S Dpotential for harm
Have proper medical gas storage and administration areas.
FAQ · About this visit
Common questions about this visit
What happened during the August 4, 2023 survey of AUTUMN LAKE HEALTHCARE AT CHERRY LANE?
This was a inspection survey of AUTUMN LAKE HEALTHCARE AT CHERRY LANE on August 4, 2023. The surveyor cited 14 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at AUTUMN LAKE HEALTHCARE AT CHERRY LANE on August 4, 2023?
Yes, 14 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smok..."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.