Inspection visit
Fire Safety inspection
Citations
17 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0761GeneralS&S Epotential for harm
To conduct inspection, testing and maintenance of fire doors by qualified individuals.
- 0039GeneralS&S Dpotential for harm
Conduct testing and exercise requirements.
- 0100GeneralS&S Dpotential for harm
Meet other general requirements.
- 0211GeneralS&S Dpotential for harm
Keep aisles, corridors, and exits free of obstruction in case of emergency.
- 0223GeneralS&S Epotential for harm
Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
- 0321GeneralS&S Epotential for harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
- 0324GeneralS&S Dpotential for harm
Provide properly protected cooking facilities.
- 0342GeneralS&S Dpotential for harm
Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
- 0353GeneralS&S Epotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0362GeneralS&S Epotential for harm
Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.
- 0363GeneralS&S Dpotential for harm
Install corridor and hallway doors that block smoke.
- 0500GeneralS&S Dpotential for harm
Meet other general requirements that are deficient.
- 0712GeneralS&S Epotential for harm
Have simulated fire drills held at unexpected times.
- 0914GeneralS&S Dpotential for harm
Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
- 0918GeneralS&S Dpotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0920GeneralS&S Dpotential for harm
Ensure proper usage of power strips and extension cords.
- 0923GeneralS&S Dpotential for harm
Have proper medical gas storage and administration areas.
FAQ · About this visit
Common questions about this visit
What happened during the April 13, 2023 survey of FREDERICK VILLA HEALTHCARE?
This was a inspection survey of FREDERICK VILLA HEALTHCARE on April 13, 2023. The surveyor cited 17 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at FREDERICK VILLA HEALTHCARE on April 13, 2023?
Yes, 17 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "To conduct inspection, testing and maintenance of fire doors by qualified individuals."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.