Inspection visit
Fire Safety inspection
Citations
18 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0004GeneralS&S Dpotential for harm
Develop and maintain an Emergency Preparedness Program (EP).
- 0200GeneralS&S Epotential for harm
Meet other general requirements.
- 0211GeneralS&S Epotential for harm
Keep aisles, corridors, and exits free of obstruction in case of emergency.
- 0223GeneralS&S Epotential for harm
Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
- 0271GeneralS&S Dpotential for harm
Have exits that are accessible at all times.
- 0321GeneralS&S Epotential for harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
- 0324GeneralS&S Dpotential for harm
Provide properly protected cooking facilities.
- 0342GeneralS&S Dpotential for harm
Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
- 0345GeneralS&S Fpotential for harm
Have approved installation, maintenance and testing program for fire alarm systems.
- 0353GeneralS&S Fpotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0362GeneralS&S Dpotential for harm
Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.
- 0363GeneralS&S Dpotential for harm
Install corridor and hallway doors that block smoke.
- 0525GeneralS&S Dpotential for harm
Enure that solid fuel-burning fireplaces are not in patient sleeping areas.
- 0531GeneralS&S Epotential for harm
Have elevators that firefighters can control in the event of a fire.
- 0761GeneralS&S Fpotential for harm
To conduct inspection, testing and maintenance of fire doors by qualified individuals.
- 0914GeneralS&S Fpotential for harm
Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
- 0918GeneralS&S Fpotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0920GeneralS&S Epotential for harm
Ensure proper usage of power strips and extension cords.
FAQ · About this visit
Common questions about this visit
What happened during the April 25, 2025 survey of ALTHEA WOODLAND NURSING HOME?
This was a inspection survey of ALTHEA WOODLAND NURSING HOME on April 25, 2025. The surveyor cited 18 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at ALTHEA WOODLAND NURSING HOME on April 25, 2025?
Yes, 18 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Develop and maintain an Emergency Preparedness Program (EP)."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.
SourceView on CMS Care Compare