Inspection visit

Fire Safety inspection

FAIRFIELD NURSING & REHABILITATION CENTERCMS #21523631 citations on this visit
31 citations recorded

Citations

31 citations recorded*CMS

This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.

What do CMS severity letters mean?

Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.

General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.

Each letter combines severity with scope: how many residents the deficiency affected.

  • 0222GeneralS&S Epotential for harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

  • 0363GeneralS&S Epotential for harm

    Install corridor and hallway doors that block smoke.

  • 0004GeneralS&S Fpotential for harm

    Develop and maintain an Emergency Preparedness Program (EP).

  • 0100GeneralS&S Fpotential for harm

    Meet other general requirements.

  • 0200GeneralS&S Fpotential for harm

    Meet other general requirements.

  • 0211GeneralS&S Epotential for harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

  • 0223GeneralS&S Dpotential for harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

  • 0251GeneralS&S Dpotential for harm

    Conform to length requirements for dead end corridors.

  • 0261GeneralS&S Epotential for harm

    Have properly spaced exits within rooms.

  • 0281GeneralS&S Epotential for harm

    Install proper backup exit lighting.

  • 0293GeneralS&S Epotential for harm

    Have properly located and lighted "Exit" signs.

  • 0321GeneralS&S Dpotential for harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

  • 0324GeneralS&S Fpotential for harm

    Provide properly protected cooking facilities.

  • 0341GeneralS&S Fpotential for harm

    Install a fire alarm system that can be heard throughout the facility.

  • 0342GeneralS&S Fpotential for harm

    Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.

  • 0344GeneralS&S Epotential for harm

    Have an alternate power supply for its alarm system.

  • 0345GeneralS&S Fpotential for harm

    Have approved installation, maintenance and testing program for fire alarm systems.

  • 0347GeneralS&S Dpotential for harm

    Properly provide smoke detection systems in areas open to corridors.

  • 0353GeneralS&S Fpotential for harm

    Inspect, test, and maintain automatic sprinkler systems.

  • 0362GeneralS&S Dpotential for harm

    Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

  • 0500GeneralS&S Dpotential for harm

    Meet other general requirements that are deficient.

  • 0511GeneralS&S Epotential for harm

    Have properly installed electrical wiring and gas equipment.

  • 0521GeneralS&S Dpotential for harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

  • 0525GeneralS&S Dpotential for harm

    Enure that solid fuel-burning fireplaces are not in patient sleeping areas.

  • 0711GeneralS&S Fpotential for harm

    Provide a written emergency evacuation plan.

  • 0712GeneralS&S Fpotential for harm

    Have simulated fire drills held at unexpected times.

  • 0761GeneralS&S Fpotential for harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

  • 0914GeneralS&S Fpotential for harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

  • 0916GeneralS&S Fpotential for harm

    Have a battery powered remote alarm panel in a location accessible by operating personnel.

  • 0918GeneralS&S Fpotential for harm

    Have generator or other power source capable of supplying service within 10 seconds.

  • 0923GeneralS&S Epotential for harm

    Have proper medical gas storage and administration areas.

FAQ · About this visit

Common questions about this visit

What happened during the May 3, 2024 survey of FAIRFIELD NURSING & REHABILITATION CENTER?

This was a inspection survey of FAIRFIELD NURSING & REHABILITATION CENTER on May 3, 2024. The surveyor cited 31 deficiencies, recorded on the federal Form 2567 statement of deficiencies.

Were any deficiencies cited at FAIRFIELD NURSING & REHABILITATION CENTER on May 3, 2024?

Yes, 31 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arra..."

What type of survey was this?

This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.