Inspector’s narrative

What the inspector wrote

COMPLETED 03/28/2024 WINTER HAVEN, FL 33884 PREFIX PREFIX COMPLETE DATE
K 000 K 000 INITIAL COMMENTS An unannounced Fire & Life Safety re-licensure survey was conducted on 03/28/2024 at Astoria Health and Rehabilitation Center, a nursing home in Winter Haven, Florida in accordance with National Fire Protection Association (NFPA) 1 and 101 (2021 Edition) and applicable requirements of Florida State Fire Marshal's Rules and Regulations, Florida Administrative Code (F.A.C.) 69A-3, F.A.C. 69A-53, F.A.C. 59A-4, and Florida Statutes (F.S.) 400 Part II, and F.S. 633.0215, adopting National Fire Protection Association (NFPA) 1 and 101 (2021 Edition) known as the Florida Fire Prevention Code and all NFPA referenced standards and requirements adopted per NFPA 101, Chapter 2. The following is description of the deficiencies found at the time of the survey.
K 372 NFPA 101 Subdivision of Building Spaces - Smoke Barrier SS=D K 372 4/28/24 Subdivision of Building Spaces - Smoke Barrier Construction 2015 EXISTING Smoke barriers shall be constructed to a 1/2-hour fire resistance rating per 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations in fully ducted HVAC systems where an approved sprinkler system is installed for smoke compartments adjacent to the smoke barrier. 19.3.7.3, 8.6.7.1(1) Describe any mechanical smoke control system in REMARKS. DEPARTMENT OF DEFICIENCIES 35961019 03/28/2024 ASTORIA HEALTH AND REHABILITATION CENTER 701 OVERLOOK DR SE WINTER HAVEN, FL 33884 PREFIX TAG ID PREFIX TAG DEFICIENCY) COMPLETE DATE
K 372 Continued From page 1
K 372 2015 NEW Smoke barriers shall be constructed to provide at least a one hour fire resistance rating and constructed in accordance with 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations of fully ducted HVAC systems. 18.3.7.3, 18.3.7.4, 18.3.7.5, 8.3 Describe any mechanical smoke control system in REMARKS. This Statute or Rule is not met as evidenced by: Based on observation and interview, the facility failed to maintain smoke barrier continuity in accordance with NFPA 101. Findings included: On 3/28/2024 between the hours of 1:30 p.m. and 4:00 p.m. during the facility tour, it was observed that the Smoke partition wall had an unsealed penetration above ceiling across from room 418. (Photographic evidence obtained) The Maintenance Director was interviewed, and he stated that the partition had been penetrated unbeknownst to him. per NFPA 101 (2021 Edition) 19.3.7.3, 8.5, 8.5.2.2 Class III The facility requests paper compliance for citation. Preparation and/or execution of this plan do not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents, or other individuals who draft or may be discussed in this of correction is submitted as the facility's credible allegation of compliance. 1.Immediate action(s) taken for the resident(s) found to have been affected include: No residents were affected by the alleged deficient practice. 2.Identification of other residents having the potential to be affected was accomplished by: All residents have the potential to be affected. The smoke barrier walls have STATE FORM 6895 VF3H21 35961019 03/28/2024 ASTORIA HEALTH AND REHABILITATION CENTER 701 OVERLOOK DR SE WINTER HAVEN, FL 33884 PREFIX TAG ID PREFIX TAG DEFICIENCY) COMPLETE DATE
K 372 Continued From page 2
K 372 been repaired and free of any openings. All the walls above the ceiling have been inspected and no other areas were found to be affected. 3. Actions taken/systems put into place to reduce the risk of future occurrence include: The Director of Plant Operations or designee will complete an inspection any time any work is completed above the ceiling to ensure no holes have been created in the smoke barrier walls. 4. How the corrective action(s) will be monitored to ensure the practice will not recur: The Director of Plant Operations or designee will audit Random Facility Smoke Partition Walls within the facility to ensure ALL Facility Smoke Partition Walls are fully Sealed the following: 1x Monthly for 3x Months, Quarterly, Annually. The results of the audit will be forwarded to the Quality Assurance Committee for review monthly for at least three months with a goal of 100% compliance. Upon completion and 100% compliance for at least three months is achieved, frequency of further review and ongoing need for review will be determined by the QAPI committee STATE FORM DEPARTMENT OF DEFICIENCIES 35961019 03/28/2024 ASTORIA HEALTH AND REHABILITATION CENTER 701 OVERLOOK DR SE WINTER HAVEN, FL 33884 PREFIX COMPLETE DATE
K 511 Continued From page 3 K 511 4/28/24
K 511 NFPA 101 Utilities - Gas and Electric SS=D Utilities - Gas and Electric Equipment using gas or related gas piping complies with NFPA 54, National Fuel Gas Code, electrical wiring and equipment complies with NFPA 70, National Electric Code. Existing installations can continue in service provided no hazard to life. 18.5.1.1, 19.5.1.1, 9.1.1, 9.1.2 This Statute or Rule is not met as evidenced by: Based on observation and interview, the facility failed to maintain electrical equipment in accordance with NFPA 101. Findings included: On 3/28/2024 between the hours of 1:30 p.m. and 4:00 p.m. during the facility tour, it was observed that: 1) Critical branch electrical panel and electric room in 700 hall had mislabeled panel. 2) Electrical room by room 409 had mislabeled panel. 3) Electrical room in 400 hall had mislabeled panel. (Photographic Evidence Obtained) The Maintenance Director was interviewed, and he stated the panels and breakers in the on position that were labeled as spares. per NFPA 101 (2021 Edition) 19.5.1.1, 9.1, 9.1.2 per NFPA 70 (2020 Edition) 408.4 (A) Class III The facility requests paper compliance for citation. Preparation and/or execution of this plan do not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents, or other individuals who draft or may be discussed in this of correction is submitted as the facility's credible allegation of compliance. 1.Immediate action(s) taken for the resident(s) found to have been affected include: No residents were affected by the alleged deficient practice. 2.Identification of other residents having the potential to be affected was accomplished by: All residents have the potential to be affected. A full facility sweep was completed by the Director of 03/28/2024 ASTORIA HEALTH AND REHABILITATION CENTER 701 OVERLOOK DR SE WINTER HAVEN, FL 33884 PREFIX COMPLETE DATE
K 511 Continued From page 4 K 511 Plant Operations to ensure there were no other electrical panels mislabeled. 3. Actions taken/systems put into place to reduce the risk of future occurrence include: Director of Plant Operations checked Every Spare Breaker in the Electrical Panel within the facility to ensure they are in the OFF position. 4. How the corrective action(s) will be monitored to ensure the practice will not recur: Director of Plant Operations or Designee will audit Every Spare Breaker in the Electrical Panel within the facility to ensure they are in the OFF position for the following: 3x weekly for 4 weeks, then 1x weekly for 4 weeks and then monthly on going. The results of the audit will be forwarded to the Quality Assurance Committee for review monthly for at least three months with a goal of 100% compliance. Upon completion and 100% compliance for at least three months is achieved, frequency of further review and ongoing need for review will be determined by the QAPI committee. 4/28/24
K 521 NFPA 101 HVAC K 521 SS=D HVAC Heating, ventilation, and air conditioning shall comply with 9.2 and shall be installed in accordance with the manufacturer's specifications. DEPARTMENT OF DEFICIENCIES 35961019 03/28/2024 ASTORIA HEALTH AND REHABILITATION CENTER 701 OVERLOOK DR SE WINTER HAVEN, FL 33884 PREFIX TAG ID PREFIX TAG DEFICIENCY) COMPLETE DATE
K 521 Continued From page 5 18.5.2.1, 19.5.2.1, 9.2
K 521 This Statute or Rule is not met as evidenced by: Based on observation and interview, the facility failed to maintain the heating, ventilation, and air conditioning (HVAC) in accordance with NFPA 99. Findings included: On 3/28/2024 between the hours of 1:30 p.m. and 4:00 p.m. during the facility tour, it was observed that: 1) Room 444's bathroom ventilation fan failed the tissue test 2) Room 445 failed the tissue test in bathroom 3) Room 724's bathroom failed the tissue test 4) Soiled utility across from room 502 failed the tissue test 5) Soiled utility in the 800 hall failed the tissue test 6) Soiled side of the laundry ventilation fan failed the tissue test 7) Soiled utility behind the nurses station in the 700 hall failed the tissue test. (Photographic Evidence Obtained) The Maintenance Director was interviewed, and he stated the ventilation fans were not performing as he expected them to. Per NFPA 101 (2021 Edition) 19.7.6, 4.6.12 NFPA 99 (2012 Edition) 9.3.6.5.2.5, 9.3.6.5.3.1 Class III The facility requests paper compliance for citation. Preparation and/or execution of this plan do not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents, or other individuals who draft or may be discussed in this of correction is submitted as the facility's credible allegation of compliance. 1.Immediate action(s) taken for the resident(s) found to have been affected include: No residents were affected by the alleged deficient practice. 2.Identification of other residents having the potential to be affected was accomplished by: All residents have the potential to be affected by the alleged deficient practice. Facility inspected all ventilation systems are operational. All ventilation systems have been inspected and brought up to
K521 compliance standards. 3.Actions taken/systems put into place to reduce the risk of future occurrence include: The ventilation fans have been inspected STATE FORM 6805 VF3H21 **ASTORIA HEALTH AND REHABILITATION CENTER** 701 OVERLOOK DR SE WINTER HAVEN, FL 33884 |---|---|---|---|---| | K 521 | Continued From page 6 | K 521 | (RM 444, 445, 724, Soiled Utility on 500, 700, 800, & laundry) and repaired on 4/2/2024 to bring the system up to K521compliance standards. Maintenance staff have been in-serviced on the ventilation standards. 4 How the corrective action(s) will be monitored to ensure the practice will not recur: A K521 HVAC audit tool will be completed by the Maintenance Director or designee 3 times weekly for 4 weeks, weekly for 4weeks, then monthly thereafter. The results of the audit will be forwarded to the Quality Assurance Committee for review monthly for at least three months with a goal of 100% compliance. Upon completion and 100% compliance for at least three months is achieved, frequency of further review and ongoing need for review will be determined by the QAPI committee. | | | K1150 SS=D | NFPA 99 (2015 Edition) Security Management This chapter shall apply to new and existing health care facilities. A health care facility shall have a security management plan. The scope, objectives, performance, and effectiveness of the security plan shall be tested at a frequency shown to be necessary by review of the security vulnerability assessment (SVA) in accordance with Section 13.3. NFPA 99 (2015 Edition) | K1150 | | 4/28/24 | STATE FORM COMPLETED 03/28/2024 701 OVERLOOK DR SE WINTER HAVEN, FL 33884 PREFIX PREFIX COMPLETE DATE
K1150 Continued From page 7 K1150 This Statute or Rule is not met as evidenced by: Based on observation and interview, the facility failed to maintain electrical equipment in accordance with NFPA 99. Findings included: On 02/01/2024 between the hours of 9:15 a.m. and 12:00 p.m. during the record review, it was found that No record was presented of the annual security vulnerability assessment (SVA). The maintenance director was interviewed, and he stated that he had no current SVA to present for review. per NFPA 101 (2021 Edition) 19.7.6, 4.6.12 per NFPA 99 (2021 Edition) 13.3.1 - 13.4.2 (1-9) Class III The facility requests paper compliance for citation. Preparation and/or execution of this plan do not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents, or other individuals who draft or may be discussed in this of correction is submitted as the facility's credible allegation of compliance. 1.Immediate action(s) taken for the resident(s) found to have been affected include: No residents were identified. 2.Identification of other residents having the potential to be affected was accomplished by: No residents were identified. 3.Actions taken/systems put into place to reduce the risk of future occurrence include: Security Vulnerability Assessments updated and reviewed on 4/15/2024 by Director of Plant Operations, Director of Clinical Services and Executive Director. The following implementations include: Prevention of, and response to infant or pediatric abduction, forensic patients, suspicious material or package, STATE FORM 6805 VF3H21 03/28/2024 ASTORIA HEALTH AND REHABILITATION CENTER 701 OVERLOOK DR SE WINTER HAVEN, FL 33884 COMPLETE DATE
K1150 Continued From page 8 K1150 suspicious powder or substance, and use of force. Maintenance staff have been in-serviced Security Vulnerability Assessments (SVA) standards. 4.How the corrective action(s) will be monitored to ensure the practice will not recur: An ongoing audit and review of all security vulnerability assessment requirements will be conducted by the Director of Plant Operations, designee. Audits will be conducted annually, and as necessary through a result of exercises, national, or local events. The results of the audit will be forwarded to the Quality Assurance Committee for review monthly for at least three months with a goal of 100% compliance. Upon completion and 100% compliance for at least three months is achieved, review and ongoing need for review will be determined by the QAPI committee. STATE FORM 6895 VF3H21 106086 03/28/2024 ASTORIA HEALTH AND REHABILITATION CENTER 701 OVERLOOK DR SE WINTER HAVEN, FL 33884 PREFIX TAG ID PREFIX TAG DEFICIENCY) COMPLETION DATE
E 000 Initial Comments
E 000 During the recertification survey conducted on 03/28/2024 at Astoria Health and Rehabilitation Center, a nursing home, Emergency Preparedness was reviewed. Astoria Health and Rehabilitation Center is in compliance with Emergency Preparedness per Code of Federal Regulations (CFR) 42, Part 483.73 Requirement for Long-Term Care Facilities. 04/19/2024 Event ID: VF3H21 Facility ID: 35961019 PLAN OF CORRECTION 701 OVERLOOK DR SE ASTORIA HEALTH AND REHABILITATION CENTER WINTER HAVEN, FL 33884 PREFIX TAG ID PREFIX TAG DEFICIENCY) COMPLETION DATE
K 000 INITIAL COMMENTS K 000 An unannounced Fire & Life Safety recertification survey was conducted 03/28/2024 at Astoria Health and Rehabilitation Center, a nursing home in Winter Haven, Florida. The Facility is not in compliance with 42 CFR 483.90(a), and National Fire Protection Association (NFPA) 101 (2012 Edition), NFPA 99 (2012 Edition) requirements for nursing homes. Initial Plan Review: 2010 New or Existing: Existing NFPA 220 Construction Type: II (111) Number of beds: 130 Census: 124 The following is a description of the deficiencies found at the time of the visit.
K 372 Subdivision of Building Spaces - Smoke Barrie SS=D CFR(s): NFPA 101 K 372 4/28/24 Subdivision of Building Spaces - Smoke Barrier Construction 2012 EXISTING Smoke barriers shall be constructed to a 1/2-hour fire resistance rating per 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations in fully ducted HVAC systems where an approved sprinkler system is installed for smoke compartments adjacent to the smoke barrier. 19.3.7.3, 8.6.7.1(1) Describe any mechanical smoke control system in REMARKS. This REQUIREMENT is not met as evidenced by: 106086 03/28/2024 ASTORIA HEALTH AND REHABILITATION CENTER 701 OVERLOOK DR SE WINTER HAVEN, FL 33884 DEFICIENCY)
K 372 Continued From page 1 K 372 Based on observation and interview, the facility The facility requests paper compliance for failed to maintain smoke barrier continuity in citation. accordance with NFPA 101. Findings included: On 3/28/2024 between the hours of 1:30 p.m. and Preparation and/or execution of this plan 4:00 p.m. during the facility tour, it was observed do not constitute admission or agreement that the Smoke partition wall had an unsealed by the provider that a deficiency exists. penetration above ceiling across from room 418. This response is also not to be construed (Photographic Evidence Obtained) as an admission of fault by the facility, its The Maintenance Director was interviewed, and he employees, agents, or other individuals stated the partition had been penetrated who draft or may be discussed in this per NFPA 101 (2012 Edition) 19.3.7.3, 8.5, 8.5.2.2 of correction is submitted as the facility's credible allegation of compliance. 1.Immediate action(s) taken for the resident(s) found to have been affected include: No residents were affected by the alleged deficient practice. 2.Identification of other residents having the potential to be affected was accomplished by: All residents have the potential to be affected. The smoke barrier walls have been repaired and free of any openings. All the walls above the ceiling have been inspected and no other areas were found to be affected. 3.Actions taken/systems put into place to reduce the risk of future occurrence include: The Director of Plant Operations or designee will complete an inspection any time any work is completed 106086 03/28/2024 ASTORIA HEALTH AND REHABILITATION CENTER 701 OVERLOOK DR SE WINTER HAVEN, FL 33884 PREFIX TAG ID PREFIX TAG DEFICIENCY) COMPLETION DATE
K 372 Continued From page 2
K 372 above the ceiling to ensure no holes have been created to the smoke barrier walls. 4.How the corrective action(s) will be monitored to ensure the practice will not recur: The Director of Plant Operations or designee will audit Random Facility Smoke Partition Walls within the facility to ensure ALL Facility Smoke Partition Walls are fully Sealed the following: 1x Monthly for 3x Months, Quarterly, Annually. The results of the audit will be forwarded to the Quality Assurance Committee for review monthly for at least three months with a goal of 100% compliance. Upon completion and 100% compliance for at least three months is achieved, frequency of further review and ongoing need for review will be determined by the QAPI committee.
K 511 Utilities - Gas and Electric SS=D CFR(s): NFPA 101
K 511 4/28/24 Utilities - Gas and Electric Equipment using gas or related gas piping complies with NFPA 54, National Fuel Gas Code, electrical wiring and equipment complies with NFPA 70, National Electric Code. Existing installations can continue in service provided no hazard to life. 18.5.1.1, 19.5.1.1, 9.1.1, 9.1.1, 9.1.2 ``` ASTORIA HEALTH AND REHABILITATION CENTER 701 OVERLOOK DR SE WINTER HAVEN, FL 33884 DEFICIENCY)
K 511 Continued From page 3 K 511 This REQUIREMENT is not met as evidenced by: Based on observation and interview, the facility The facility requests paper compliance for failed to maintain electrical equipment in citation. accordance with NFPA 101. Preparation and/or execution of this plan Findings included: do not constitute admission or agreement by the provider that a deficiency exists. On 3/28/2024 between the hours of 1:30 p.m. and This response is also not to be construed 4:00 p.m. during the facility tour, it was observed as an admission of fault by the facility, its that: employees, agents, or other individuals who draft or may be discussed in this in the 700 hall had mislabeled panel. of correction is submitted as the facility's 2) Electrical room by room 409 had mislabeled credible allegation of compliance. panel. 3) Electrical room in 400 hall had mislabeled 1.Immediate action(s) taken for the panel. resident(s) found to have been affected include: (Photographic Evidence Obtained) No residents were affected by the alleged deficient practice. The Maintenance Director was interviewed, and he stated the panels indicated, had breakers in the on 2.Identification of other residents having the position that were labeled as spares. potential to be affected was accomplished by: per NFPA 101 (2012 Edition) 19.5.1.1, 9.1, 9.1.2 All residents have the potential to be per NFPA 70 (2011 Edition) 408.4 (A) affected. A full facility sweep was completed by the Director of Plant Operations to ensure there were no other electrical panels mislabeled. 3.Actions taken/systems put into place to reduce the risk of future occurrence include: Director of Plant Operations checked Every Spare Breaker in the Electrical Panel within the facility to ``` COMPLETED 03/28/2024 ASTORIA HEALTH AND REHABILITATION CENTER 701 OVERLOOK DR SE WINTER HAVEN, FL 33884 PREFIX TAG ID PREFIX TAG DEFICIENCY) (X7) COMPLETION DATE
K 511 Continued From page 4
K 511 ensure they are in the OFF position. 4.How the corrective action(s) will be monitored to ensure the practice will not recur: Director of Plant Operations or Designee will audit Every Spare Breaker in the Electrical Panel within the facility to ensure they are in the OFF position for the following: 3x weekly for 4 weeks, then 1x weekly for 4 weeks and then monthly on going. The results of the audit will be forwarded to the Quality Assurance Committee for review monthly for at least three months with a goal of 100% compliance. Upon completion and 100% compliance for at least three months is achieved, frequency of further review and ongoing need for review will be determined by the QAPI committee. 4/28/24
K 521 HVAC SS=D CFR(s): NFPA 101
K 521 HVAC Heating, ventilation, and air conditioning shall comply with 9.2 and shall be installed in accordance with the manufacturer's specifications. 18.5.2.1, 19.5.2.1, 9.2 This REQUIREMENT is not met as evidenced by: Based on observation and interview, the facility failed to maintain the heating, ventilation, and air The facility requests paper compliance for citation. 03/28/2024 ASTORIA HEALTH AND REHABILITATION CENTER 701 OVERLOOK DR SE WINTER HAVEN, FL 33884 COMPLETION DATE
K 521 Continued From page 5 conditioning (HVAC) in accordance with NFPA 99. K 521 Findings included: On 3/28/2024 between the hours of 1:30 p.m. and 4:00 p.m. during the facility tour, it was observed that: 1) Room 444's bathroom ventilation fan failed the tissue test 2) Room 445 failed the tissue test in the bathroom 3) Room 724's bathroom failed the tissue test 4) Soiled utility across from room 502 failed the tissue test 5) Soiled utility in 800 hall failed the tissue test 6) Soiled side of the laundry ventilation fan failed the tissue test 7) Soiled utility behind the nurses station in the 700 hall failed the tissue test. (Photographic Evidence Obtained) The Maintenance Director was interviewed, and he stated the ventilation fans were not performing as he expected them to. per NFPA 101 (2012 Edition) 19.7.6, 4.6.12 per NFPA 99 (2012 Edition) 9.3.7.5.2.5, 9.3.7.5.3.1 Preparation and/or execution of this plan do not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents, or other individuals who draft or may be discussed in this of correction is submitted as the facility's credible allegation of compliance. 1.Immediate action(s) taken for the resident(s) found to have been affected include: No residents were affected by the alleged deficient practice. 2.Identification of other residents having the potential to be affected was accomplished by: All residents have the potential to be affected by the alleged deficient practice. Facility inspected All ventilation systems are operational. All ventilation systems have been inspected and brought up to
K521 compliance standards. 3.Actions taken/systems put into place to reduce the risk of future occurrence include: The ventilation fans have been inspected (RM 444, 445, 724, Soiled Utility on 500, 700, 800, & laundry) and repaired on 4/2/2024 to bring the system up to K521 compliance standards. ID PLAN OF CORRECTION 106086 03/28/2024 ASTORIA HEALTH AND REHABILITATION CENTER 701 OVERLOOK DR SE WINTER HAVEN, FL 33884 PREFIX TAG ID PREFIX TAG DEFICIENCY) COMPLETION DATE
K 521 Continued From page 6
K 521 Maintenance staff have been in-serviced on the ventilation standards. 4.How the corrective action(s) will be monitored to ensure the practice will not recur: A K521 HVAC audit tool will be completed by the Maintenance Director or designee 3 times weekly for 4 weeks, weekly for 4weeks, then monthly thereafter. The results of the audit will be forwarded to the Quality Assurance Committee for review monthly for at least three months with a goal of 100% compliance. Upon completion and 100% compliance for at least three months is achieved, frequency of further review and ongoing need for review will be determined by the QAPI committee.

Reading this as a family member? Your long-term care ombudsman is a free advocate for residents and families.

Back to top

Citations

No citations recorded on this visit

The surveyor cited no deficiencies during this survey.

FAQ · About this visit

Common questions about this visit

What happened during the March 28, 2024 survey of ASTORIA HEALTH AND REHABILITATION CENTER?

This was a inspection survey of ASTORIA HEALTH AND REHABILITATION CENTER on March 28, 2024. The surveyor cited no deficiencies.

Were any deficiencies cited at ASTORIA HEALTH AND REHABILITATION CENTER on March 28, 2024?

No deficiencies were cited during this survey.

What type of survey was this?

This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.

Share this reportEmail

Next steps

Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.

Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.

Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.