Inspection visit

Fire Safety inspection

Waterview Lodge Llc, Rehabilitation & HealthcareCMS #22559828 citations on this visit
28 citations recorded

Citations

28 citations recorded*CMS

This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.

What do CMS severity letters mean?

Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.

General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.

Each letter combines severity with scope: how many residents the deficiency affected.

  • 0004GeneralS&S Fpotential for harm

    Develop and maintain an Emergency Preparedness Program (EP).

  • 0006GeneralS&S Fpotential for harm

    Conduct risk assessment and an All-Hazards approach.

  • 0015GeneralS&S Dpotential for harm

    Address subsistence needs for staff and patients.

  • 0024GeneralS&S Dpotential for harm

    Establish policies and procedures for volunteers.

  • 0029GeneralS&S Fpotential for harm

    Develop a communication plan.

  • 0031GeneralS&S Dpotential for harm

    Provide emergency officials' contact information.

  • 0033GeneralS&S Fpotential for harm

    Establish methods for sharing information.

  • 0036GeneralS&S Dpotential for harm

    Establish emergency prep training and testing.

  • 0037GeneralS&S Dpotential for harm

    Establish staff and initial training requirements.

  • 0039GeneralS&S Fpotential for harm

    Conduct testing and exercise requirements.

  • 0041GeneralS&S Fpotential for harm

    Implement emergency and standby power systems.

  • 0211GeneralS&S Dpotential for harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

  • 0222GeneralS&S Dpotential for harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

  • 0311GeneralS&S Dpotential for harm

    Have an enclosure around a vertical opening shaft.

  • 0321GeneralS&S Fpotential for harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

  • 0324GeneralS&S Epotential for harm

    Provide properly protected cooking facilities.

  • 0345GeneralS&S Epotential for harm

    Have approved installation, maintenance and testing program for fire alarm systems.

  • 0353GeneralS&S Fpotential for harm

    Inspect, test, and maintain automatic sprinkler systems.

  • 0355GeneralS&S Dpotential for harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

  • 0372GeneralS&S Epotential for harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

  • 0511GeneralS&S Dpotential for harm

    Have properly installed electrical wiring and gas equipment.

  • 0521GeneralS&S Fpotential for harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

  • 0531GeneralS&S Fpotential for harm

    Have elevators that firefighters can control in the event of a fire.

  • 0711GeneralS&S Epotential for harm

    Provide a written emergency evacuation plan.

  • 0712GeneralS&S Dpotential for harm

    Have simulated fire drills held at unexpected times.

  • 0761GeneralS&S Dpotential for harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

  • 0918GeneralS&S Fpotential for harm

    Have generator or other power source capable of supplying service within 10 seconds.

  • 0923GeneralS&S Epotential for harm

    Have proper medical gas storage and administration areas.

FAQ · About this visit

Common questions about this visit

What happened during the October 29, 2024 survey of Waterview Lodge Llc, Rehabilitation & Healthcare?

This was a inspection survey of Waterview Lodge Llc, Rehabilitation & Healthcare on October 29, 2024. The surveyor cited 28 deficiencies, recorded on the federal Form 2567 statement of deficiencies.

Were any deficiencies cited at Waterview Lodge Llc, Rehabilitation & Healthcare on October 29, 2024?

Yes, 28 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Develop and maintain an Emergency Preparedness Program (EP)."

What type of survey was this?

This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.