K 000 INITIAL COMMENTS K 000
An unannounced Fire & Life Safety re-licensure survey was conducted on 11/20/2024 at Arabella Health and Wellness of Carrabelle, a nursing home in Carrabelle, Florida, in accordance with the standards of National Fire Protection Association (NFPA) 1 and 101 (2021 edition) and all applicable requirements of the Florida State Fire Marshal's Rules and Regulations, Florida Administrative Code (F.A.C.) 69A-3, F.A.C. 69A-53, F.A.C. 59A-4, and Florida Statutes (F.S.) 400 Part II, and F.S. 633.0215, adopting National Fire Protection Association (NFPA) 1 and 101 (2021 edition) standards, collectively known as the Florida Fire Prevention Code, and all NFPA referenced standards and requirements adopted per NFPA 101, Chapter 2.
There were deficiencies found at the time of the visit
K 291 NFPA 101 Emergency Lighting K 291 12/13/24
Emergency Lighting
Emergency lighting of at least 1-1/2-hour duration is provided automatically in accordance with 7.9.18.2.9.1, 19.2.9.1.
This Statute or Rule is not met as evidenced by:
Based on record review and interview with the Maintenance Director, the facility failed to provide and maintain reliable emergency lighting. Testing is required to insure the durability of the batteries for the required period of time. This condition could jeopardize the safety of patients and staff in an emergency situation.
The findings include:
During the Fire & Life Safety document review of the facility with the Director of Maintenance on
#1 Corrective Action for affected residents. Monthly and Annual 90 minute testing of the Emergency Lighting System as specified in NFPA 101 (2012 edition) will be completed and documents maintained in Life Safety Binder by Maintenance Director. Battery Packs are on order for the lights that need them.
#2 How will the facility identify other like residents?
AHCA Form 3020-0001
LABORATORY DIRECTOR'S OR PROVIDER/SUPPLIER REPRESENTATIVE'S SIGNATURE TITLE (X6) DATE
Electronically Signed 12/02/24
STATE FORM 8899 P3CC21 If continuation sheet 1 of 11
Agency for Health Care Administration
PRINTED: 01/14/2025
FORM APPROVED
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION
(X1) PROVIDER/SUPPLIER/CLIA
IDENTIFICATION NUMBER:
35961023
(X2) MULTIPLE CONSTRUCTION
A. BUILDING: 01, 05
B. WING ______
(X3) DATE SURVEY
COMPLETED
11/20/2024
NAME OF PROVIDER OR SUPPLIER
ARABELLA HEALTH & WELLNESS OF CARRABELLE
STREET ADDRESS, CITY, STATE, ZIP CODE
239 CROOKED RIVER ROAD
CARRABELLE, FL 32322
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
ID
PREFIX
TAG
PROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
CROSS-REFERENCED TO THE APPROPRIATE
DEFICIENCY)
(X5)
COMPLETE
DATE
K 291
Continued From page 1
11/20/2024, no records were provided to verify
the emergency backup lighting received 90
minute testing.
The Maintenance Director verified these findings
at the times observed.
Monthly testing of emergency lights is required to
insure reliable operation in the event of a power
failure. Annual testing is required to insure the
durability of the batteries for the required period
of time as specified in NFPA 101 (2021 edition).
Class III
K 291
The Administrator and Maintenance
Director will ensure the Emergency
Lighting system is audited monthly and
annually per Life Safety Code to ensure no
further residents and staff will be
potentially affected in an emergency
situation by leaving areas dark.
#3 What will you do to prevent
recurrence?
To prevent this deficient practice from
recurring, the Maintenance Director has
been educated on the importance of
completing the required inspection of the
Emergency Lighting System per Life
Safety guidelines found in NFPA 101
(2012) and maintaining proper
documentation.
#4 How will you monitor and maintain
ongoing compliance?
To monitor and maintain ongoing
compliance the maintenance director will
document the inspection of the
Emergency Lighting System and report
findings to the Administrator monthly x 3
months.
The Administrator will source any needed
repair/replacement parts for the Lighting
System.
#4 QAPI
The Administrator will report the results of
the monitoring to the QAPI committee for
review and recommendations for the time
framed of the monitoring period or as it
is amended by the committee.
This plan has been reviewed at an ad hoc
Quality Assurance committee meeting
held on 12/13/2024.
AHCA Form 3020-0001
STATE FORM
696
P3CC21
If continuation sheet, 2 of 11
PRINTED: 01/14/2025
FORM APPROVED
Agency for Health Care Administration
| STATEMENT OF DEFICIENCIES AND PLAN OF CORRECTION | (X1) PROVIDER/SUPPLIER/CLIA IDENTIFICATION NUMBER: 35961023 | (X2) MULTIPLE CONSTRUCTION A. BUILDING: 01, 05 B. WING | (X3) DATE SURVEY COMPLETED 11/20/2024 |
|---|---|---|---|
NAME OF PROVIDER OR SUPPLIER
ARABELLA HEALTH & WELLNESS OF CARRABELLE
STREET ADDRESS, CITY, STATE, ZIP CODE
239 CROOKED RIVER ROAD
CARRABELLE, FL 32322
| (X4) ID PREFIX TAG | SUMMARY STATEMENT OF DEFICIENCIES (EACH DEFICIENCY MUST BE PRECEDED BY FULL REGULATORY OR LSC IDENTIFYING INFORMATION) | ID PREFIX TAG | PROVIDER'S PLAN OF CORRECTION (EACH CORRECTIVE ACTION SHOULD BE CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) | (X5) COMPLETE DATE |
|---|---|---|---|---|
| K 345 | Continued From page 2 | K 345 | | |
| K 345 SS=D | NFPA 101 Fire Alarm System - Testing and Maintenance | K 345 | | 12/13/24 |
Fire Alarm System - Testing and Maintenance
A fire alarm system is tested and maintained in accordance with an approved program complying with the requirements of NFPA 70, National Electric Code, and NFPA 72, National Fire Alarm and Signaling Code. Records of system acceptance, maintenance and testing are readily available.
9.6.5, 9.6.7, 9.6.8, and NFPA 70, NFPA 72
This Statute or Rule is not met as evidenced by:
Based on document review and interview, the facility failed to maintain the Fire Alarm System. Maintaining the Fire Alarm System ensures proper operation and lessens the chance of a delayed alarm activation under hazardous conditions.
The findings include:
During the document review with the Maintenance Director on 11/20/2024, the facility failed to provide evidence of the annual duct detector differential testing and biennial sensitivity inspection.
An interview was conducted with the Maintenance Director confirmed the findings.
Please refer to:
NFPA 101(2021 Edition) sections 19.3.4.1, 19.3.4.4, 9.6, and 9.6.1.5
NFPA 72 (2010 Edition) sections 14.4.2.2, 14.4.2.2(14)(g)(6), and 14.4.5.3
Class III
#1 Corrective Action for affected residents.
Fire System vendor completed the annual Duct Detector Differential and sensitivity test on 11/26/24. This was completed per the guidelines of NFPA 70 National Electric Code, and NFPA 72.
#2 How will the facility identify other like residents?
An audit by Maintenance Director of documentation required by Life Safety was completed 11/21/24 and annual duct detector testing and sensitivity of the Fire Alarm System.
#3 What will you do to prevent recurrence?
To prevent this from recurring the Maintenance Director has been educated on importance of completing audits and to follow the AHCA Life Safety guidelines for annual testing of the Fire Alarm System per requirements.
#4 How will you monitor and maintain ongoing compliance?
AHCA Form 3020-0001
STATE FORM
6956 P3CC21 If continuation sheet 3 of 11
PRINTED: 01/14/2025 FORM APPROVED
Agency for Health Care Administration
STATEMENT OF DEFICIENCIES AND PLAN OF CORRECTION
(X1) PROVIDER/SUPPLIER/CLIA IDENTIFICATION NUMBER: 35961023
(X2) MULTIPLE CONSTRUCTION A. BUILDING: 01, 05 B. WING ____
(X3) DATE SURVEY COMPLETED 11/20/2024
NAME OF PROVIDER OR SUPPLIER ARABELLA HEALTH & WELLNESS OF CARRABELLE
STREET ADDRESS, CITY, STATE, ZIP CODE 239 CROOKED RIVER ROAD CARRABELLE, FL 32322
(X4) ID PREFIX TAG | SUMMARY STATEMENT OF DEFICIENCIES (EACH DEFICIENCY MUST BE PRECEDED BY FULL REGULATORY OR LSC IDENTIFYING INFORMATION) | ID PREFIX TAG | PROVIDER'S PLAN OF CORRECTION (EACH CORRECTIVE ACTION SHOULD BE CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) | (X5) COMPLETE DATE
---|---|---|---|---
K 345 | Continued From page 3 | K 345 | To monitor and maintain ongoing compliance the Maintenance Director and/or Designee will document audit of fire alarm system monthly x 4 months. #4 QAPI This plan has been reviewed at an ad hoc Quality Assurance committee meeting held on 12/13/24 The Administrator will report the results of the monitoring to the QAPI committee for review and recommendations for the time frame of the monitoring period or as it is amended by the committee. |
K 363 | NFPA 101 Corridor - Doors SS=D Corridor - Doors 2015 EXISTING Doors protecting corridor openings in other than required enclosures of vertical openings, exts, or hazardous areas shall be substantial doors, such as those constructed of 1-3/4 inch solid-bonded core wood, or capable of resisting fire for at least 20 minutes. Doors in fully sprinklered smoke compartments are only required to resist the passage of smoke. Doors shall be provided with a means suitable for keeping the door closed. There is no impediment to the closing of the Doors. Clearance between bottom of door and floor covering is not exceeding 1 inch. Roller latches are prohibited by CMS regulations (only for Federal survey citation) only on corridor doors and rooms containing flammable or combustible materials. Powered doors complying with 7.2.1.9 are permissible. Hold open devices that release when the door is pushed or pulled are permitted. Nonrated protective plates of unlimited height are | K 363 | | 12/13/24
AHCA Form 3020-0001 STATE FORM esss P3CC21 If continuation sheet 4 of 11
Agency for Health Care Administration PRINTED: 01/14/2025
FORM APPROVED
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION (X1) PROVIDER/SUPPLIER/CLIA
IDENTIFICATION NUMBER: (X2) MULTIPLE CONSTRUCTION
A. BUILDING: 01, 05
B. WING __
(X3) DATE SURVEY COMPLETED
35961023 11/20/2024
NAME OF PROVIDER OR SUPPLIER STREET ADDRESS, CITY, STATE, ZIP CODE
ARABELLA HEALTH & WELLNESS OF CARRABELLE 239 CROOKED RIVER ROAD
CARRABELLE, FL 32322
(X4) ID
PREFIX
TAG SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL ID
REGULATORY OR LSC IDENTIFYING INFORMATION) PREFIX
TAG PROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
CROSS-REFERENCED TO THE APPROPRIATE
DEFICIENCY) (X5)
COMPLETE
DATE
K 363 Continued From page 4 K 363
permitted. Dutch doors meeting 19.3.6.3.6 are
permitted.
Door frames shall be labeled and made of steel
or other materials in compliance with 8.3, unless
the smoke compartment is sprinklered. Fixed fire
window assemblies are allowed per 8.3. In
sprinklered compartments there are no
restrictions in area or fire resistance of glass or
frames in window assemblies.
19.3.6.3, 42 CFR Parts 403, 418, 460, 482, 483,
and 485
Show in REMARKS details of doors such as fire
protection ratings, automatics closing devices,
etc.
2015 NEW
Doors protecting corridor openings shall be
constructed to resist the passage of smoke.
Clearance between bottom of door and floor
covering is not exceeding 1 inch. There is no
impediment to the closing of the doors. Hold open
devices that release when the door is pushed or
pulled are permitted.
Doors shall be provided with self-latching and
positive latching hardware. Annotated protective
plates of unlimited height are permitted. Dutch
doors meeting 18.3.6.3.6 are permitted. Roller
latches are prohibited by CMS regulations (only
for Federal survey citation) on corridor doors and
rooms containing flammable or combustible
materials.
18.3.6.3, 42 CFR Parts 403, 418, 460, 482, 483,
and 485
Show in REMARKS details of doors such as fire
protection ratings, automatic closing devices, etc.
This Statute or Rule is not met as evidenced by:
AHCA Form 3020-0001
STATE FORM
e899 P3CC21 If continuation sheet, 5 of 11
Agency for Health Care Administration
PRINTED: 01/14/2025
FORM APPROVED
STATEMENT OF DEFICIENCIES AND PLAN OF CORRECTION
(X1) PROVIDER/SUPPLIER/CLIA IDENTIFICATION NUMBER: 35961023
(X2) MULTIPLE CONSTRUCTION
A. BUILDING: 01, 05
B. WING __________
(X3) DATE SURVEY COMPLETED 11/20/2024
NAME OF PROVIDER OR SUPPLIER
ARABELLA HEALTH & WELLNESS OF CARRABELLE
STREET ADDRESS, CITY, STATE, ZIP CODE
239 CROOKED RIVER ROAD
CARRABELLE, FL 32322
(X4) ID PREFIX TAG | SUMMARY STATEMENT OF DEFICIENCIES (EACH DEFICIENCY MUST BE PRECEDED BY FULL REGULATORY OR LSC IDENTIFYING INFORMATION) | ID PREFIX TAG | PROVIDER'S PLAN OF CORRECTION (EACH CORRECTIVE ACTION SHOULD BE CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) | (X5) COMPLETE DATE
--- | --- | --- | --- | ---
K 363 | Continued From page 5
Based on observation and interview made during the Fire & Life Safety tour, the facility failed to maintain proper maintenance of the Fire/Smoke doors. This condition could result in smoke compartments becoming involved in a fire and/or smoke situation. This could allow fire, smoke and fire gasses to enter the compartment, which could impede or deny the exiting of occupants in an emergency.
The findings include:
During the Fire & Life Safety tour of the facility with the Maintenance staff on 11/20/2024 from 10:00 am to 1:00 pm, it was observed that the following fire and smoke doors had issues:
1. The nourishment room had holes in the door.
2. The soiled utility room had holes in the door.
3. The laundry room door was not latching.
4. The medical records room was not closing.
The Director of Maintenance was present during the observation, and confirmed the findings.
Per NFPA 101 (2021 edition) Chapter 19, section 19.3.6.3.5, "Doors shall be provided with a means for keeping the door closed that is acceptable to the authority having jurisdiction."
Class III | K 363 | #1 Corrective Action for affected residents.
The auto closing latches on the Medical Records Office door and the Laundry Room door have been adjusted to close properly on 11/21/2024.
The Smoke Doors leading into the Nourishment Room and the Soiled Utility Room that have holes in them are being repaired. Vendor contacted 12/2/2024 ( Life Safety Services )
#2 How will the facility identify other like residents?
An audit of all facility doors has been completed by the Maintenance director to identify any doors that do not close properly per NFPA 101 (2012 edition), Chapter 19, 19.3.6.3.5. Doors that are provided with a means for keeping the door closed that is acceptable to the authority having jurisdiction.
The audit was completed 11/21/24.
#3 What will you do to prevent recurrence?
To prevent this deficient practice from recurring, the Maintenance Director has been educated to round and visualize any doors in the facility that do not latch properly and to initiate repairs.
Staff has been re-educated at mandatory in-service meeting to not place any tape over a door latch or use a wedge to prop a door open or prevent proper closing and latching of any door per NFPA 101 guidelines.
#4 How will you monitor and maintain ongoing compliance?
To monitor and maintain ongoing compliance, the Maintenance Director will document the rounding and report findings | |
AHCA Form 3020-0001
STATE FORM
6989
P3CC21
If continuation sheet, 6 of 11
PRINTED: 01/14/2025
FORM APPROVED
Agency for Health Care Administration
| STATEMENT OF DEFICIENCIES AND PLAN OF CORRECTION | (X1) PROVIDER/SUPPLIER/CLIA IDENTIFICATION NUMBER: 35961023 | (X2) MULTIPLE CONSTRUCTION A. BUILDING: 01, 05 B. WING | (X3) DATE SURVEY COMPLETED 11/20/2024 |
NAME OF PROVIDER OR SUPPLIER
ARABELLA HEALTH & WELLNESS OF CARRABELLE
STREET ADDRESS, CITY, STATE, ZIP CODE
239 CROOKED RIVER ROAD
CARRABELLE, FL 32322
| (X4) ID PREFIX TAG | SUMMARY STATEMENT OF DEFICIENCIES (EACH DEFICIENCY MUST BE PRECEDED BY FULL REGULATORY OR LSC IDENTIFYING INFORMATION) | ID PREFIX TAG | PROVIDER'S PLAN OF CORRECTION (EACH CORRECTIVE ACTION SHOULD BE CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) | (X5) COMPLETE DATE |
K 363 | Continued From page 6 | K 363 | to the Administrator weekly x 12 weeks. The Administrator will source any needed repair or replacement parts as needed. #4 QAPI This plan has been reviewed at an ad hoc Quality Assurance committee meeting held on 12/13/24. The Administrator will report the results of the monitoring to the QAPI committee for review and recommendations for the time frame of the monitoring period or as it is amended by the committee. |
K 914
SS=D | NFPA 99 Electrical Systems - Maintenance and Testing
Electrical Systems - Maintenance and Testing Hospital-grade receptacles at patient bed locations and where deep sedation or general anesthesia is administered, are tested after initial installation, replacement or servicing. Additional testing is performed at intervals defined by documented performance data. Receptacles not listed as hospital-grade at these locations are tested at intervals not exceeding 12 months. Line isolation monitors (LIM), if installed, are tested at intervals of less than or equal to 1 month by actuating the LIM test switch per 6.3.2.6.3.6, which activates both visual and audible alarm. For LIM circuits with automated self-testing, this manual test is performed at intervals less than or equal to 12 months. LIM circuits are tested per 6.3.3.3.2 after any repair or renovation to the electric distribution system. Records are maintained of required tests and associated repairs or modifications, containing date, room or area tested, and results.
6.3.4 (NFPA 99) | K 914 | | 12/13/24 |
AHCA Form 3020-0001
STATE FORM
8899 P3CC21
If continuation sheet 7 of 11
Agency for Health Care Administration
PRINTED: 01/14/2025
FORM APPROVED
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION
(X1) PROVIDER/SUPPLIER/CLIA
IDENTIFICATION NUMBER:
35961023
(X2) MULTIPLE CONSTRUCTION
A. BUILDING: 01, 05
B. WING __
(X3) DATE SURVEY
COMPLETED
11/20/2024
NAME OF PROVIDER OR SUPPLIER
ARABELLA HEALTH & WELLNESS OF CARRABELLE
STREET ADDRESS, CITY, STATE, ZIP CODE
239 CROOKED RIVER ROAD
CARRABELLE, FL 32322
| (X4) ID PREFIX TAG | SUMMARY STATEMENT OF DEFICIENCIES (EACH DEFICIENCY MUST BE PRECEDED BY FULL REGULATORY OR LSC IDENTIFYING INFORMATION) | ID PREFIX TAG | PROVIDER'S PLAN OF CORRECTION (EACH CORRECTIVE ACTION SHOULD BE CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) | (X5) COMPLETE DATE |
|-------------------|----------------------------------------------------------------------------------------------------------------|--------------|---------------------------------------------------------------------------------------------------------------|-------------------|
| K 914 | Continued From page 7 | K 914 | | |
| | This Statute or Rule is not met as evidenced by: Based on record review and interview with the Maintenance Director, the facility failed to maintain documentation on the exercising of the main and feeder breakers. Failure to exercise these breakers as required by the manufacturer can lead to corrosion, among other issues, which can cause a delay or an inability to transfer power in a time of emergency. This could result in loss of power to the facility in the event of a simultaneous failure of the local utility and the emergency generator, potentially endangering the patients and occupants of the facility. | | | |
| | The findings include: | | | |
| | During the Fire & Life Safety document review of the facility with the Director of Maintenance on 11/20/2024, no documentation was provided to show that the Main & Feeder Circuit Breakers were inspected annually as required, including periodic exercise in accordance with the manufacturer's recommendations. | | | |
| | An interview with the Maintenance Director revealed and acknowledged that the facility did not have a system in place or a preventative maintenance program to ensure compliance with NFPA 110 (2021 Edition). | | | |
| | Please refer to NFPA 101 (2018 Edition) section 9.1.2 and NFPA 110 (2021 Edition) section 8.4.7. | | | |
| | Class III | | | |
| | | | #1 Corrective Action for affected residents. Maintenance Director is responsible and competent to complete an inhouse annual inspection of Main and Feeder Circuit Breaker test per NFPA 110 guidelines. Completed on 12/10/2024. | |
| | | | #2 How will the facility identify other like residents? Maintenance Director to complete the Main and Feeder Circuit Breaker testing to ensure no delay in transfer of power in the event of an emergency or loss of power per NFPA 101 9.1.2 and 110 8.4.7 (2012 edition). | |
| | | | #3 What will you do to prevent recurrence? To prevent this from recurring the Maintenance Director has been educated on the importance of completing necessary audits of the generator main and feeder circuits and maintaining documentation of audits and as part of our maintenance program to ensure compliance with NFPA 110 (2012 edition). | |
| | | | #4 How will you monitor and maintain ongoing compliance? Maintenance Director and/or designee to maintain documentation and scheduling of the annual Main and Feeder /Breaker test annually and/or as required by guidelines. | |
| | | | #4 QAPI This plan has been reviewed at an ad hoc Quality Assurance committee meeting held on 12/13/24 | |
AHCA Form 3020-0001
STATE FORM
696
P3CC21
If continuation sheet, 8 of 11
Agency for Health Care Administration
PRINTED: 01/14/2025
FORM APPROVED
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION
(X1) PROVIDER/SUPPLIER/CLIA
IDENTIFICATION NUMBER:
35961023
(X2) MULTIPLE CONSTRUCTION
A. BUILDING: 01, 05
B. WING ______
(X3) DATE SURVEY
COMPLETED
11/20/2024
NAME OF PROVIDER OR SUPPLIER
ARABELLA HEALTH & WELLNESS OF CARRABELLE
STREET ADDRESS, CITY, STATE, ZIP CODE
239 CROOKED RIVER ROAD
CARRABELLE, FL 32322
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
ID
PREFIX
TAG
PROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
CROSS-REFERENCED TO THE APPROPRIATE
DEFICIENCY)
(X5)
COMPLETE
DATE
K 914
Continued From page 8
K 914
The Administrator will report the results of
the monitoring to the QAPI committee for
review and recommendations for the time
frame of the monitoring period or as it is
amended by the committee.
12/13/24
K 918
NFPA 99 Electrical Systems - Essential Electric
SS=D Syste
K 918
Electrical Systems - Essential Electric System
Maintenance and Testing
The generator or other alternate power source
and associated equipment is capable of supplying
service within 10 seconds. If the 10-second
criterion is not met during the monthly test, a
process shall be provided to annually confirm this
capability for the life safety and critical branches.
Maintenance and testing of the generator and
transfer switches are performed in accordance
with NFPA 110.
Generator sets are inspected weekly, exercised
under load 30 minutes 12 times a year in 20-40
day intervals, and exercised once every 36
months for 4 continuous hours. Every test
under load conditions include a complete
simulated cold start and automatic or manual
transfer of all EES loads, and are conducted by
competent personnel. Maintenance and testing of
stored energy power sources (Type 3 EES) are in
accordance with NFPA 111. Main and feeder
circuit breakers are inspected annually, and a
program for periodically exercising the
components is established according to
manufacturer requirements. Written records of
maintenance and testing are maintained and
readily available. EES electrical panels and
circuits are marked and readily identifiable.
Minimizing the possibility of damage of the
emergency power source is a design
AHCA Form 3020-0001
STATE FORM
899
P3CC21
If continuation sheet 9 of 11
PRINTED: 01/14/2025
FORM APPROVED
Agency for Health Care Administration
| STATEMENT OF DEFICIENCIES AND PLAN OF CORRECTION | (X1) PROVIDER/SUPPLIER/CLIA IDENTIFICATION NUMBER: 35961023 | (X2) MULTIPLE CONSTRUCTION A. BUILDING: 01, 05 B. WING _______________ | (X3) DATE SURVEY COMPLETED 11/20/2024 |
NAME OF PROVIDER OR SUPPLIER
ARABELLA HEALTH & WELLNESS OF CARRABELLE
STREET ADDRESS, CITY, STATE, ZIP CODE
239 CROOKED RIVER ROAD
CARRABELLE, FL 32322
| (X4) ID PREFIX TAG | SUMMARY STATEMENT OF DEFICIENCIES (EACH DEFICIENCY MUST BE PRECEDED BY FULL REGULATORY OR LSC IDENTIFYING INFORMATION) | ID PREFIX TAG | PROVIDER'S PLAN OF CORRECTION (EACH CORRECTIVE ACTION SHOULD BE CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) | (X5) COMPLETE DATE |
|---|---|---|---|
K 918 | Continued From page 9
consideration for new installations.
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70)
This Statute or Rule is not met as evidenced by:
Based on observations and interview with the Maintenance Director, the facility failed to maintain replacement parts for the emergency back-up generator in accordance with NFPA 99. This could result in a loss of power to the emergency generator, thereby endangering the patients and occupants of the facility.
The findings include:
During the Fire & Life Safety tour of the facility with the Director of Maintenance on 11/20/2024 between 10:00 am and 1:00 pm, it was revealed that the facility failed to maintain replacement parts for the emergency generator identified as having a high mortality, or as recommended by the manufacturer, in a secure location on the premises.
The Maintenance Director confirmed this at the time of the observation.
Please refer to:
NFPA 101 (2021 Edition) sections 19.7.6 and 4.6.12.1
NFPA 99 (2021 Edition) section 6.7.4.1.1.3
NFPA 110 (2019 Edition) sections 8.2.4 and 8.2.4.1
Class III | K 918 | #1 Corrective Action for affected residents. Maintenance Director requested quote and ordered mortality parts for the Kohler generator on 12/10/24 from Generator Maintenance Service Provider after a Preventative Maintenance Service performed on existing generator.
#2 How will the facility identify other like residents?
An audit of Mortality parts will be maintained by Maintenance Director and/or Designee. Administrator will replace any parts needed for repairs to the generator as needed.
#3 What will you do to prevent recurrence?
In order to prevent this from recurring, Maintenance director has been educated on the importance of Maintaining replacement parts for existing generator in accordance with NFPA 99 in a secured location on the premises.
#4 How will you monitor and maintain ongoing compliance?
To monitor and maintain ongoing compliance with this matter, the Maintenance Director and/or designee will audit replacements parts provided by Provider monthly x 3 months.
Administrator will replace any parts needed for repairs to existing generator. |
AHCA Form 3020-0001
STATE FORM
6956 P3CC21 If continuation sheet 10 of 11
Agency for Health Care Administration PRINTED: 01/14/2025
FORM APPROVED
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION (X1) PROVIDER/SUPPLIER/CLIA (X2) MULTIPLE CONSTRUCTION
IDENTIFICATION NUMBER: A. BUILDING: 01, 05
B. WING ____
35961023 11/20/2024
NAME OF PROVIDER OR SUPPLIER STREET ADDRESS, CITY, STATE, ZIP CODE
ARABELLA HEALTH & WELLNESS OF CARRABELLE 239 CROOKED RIVER ROAD
CARRABELLE, FL 32322
(X4) ID SUMMARY STATEMENT OF DEFICIENCIES ID PROVIDER'S PLAN OF CORRECTION
PREFIX (EACH DEFICIENCY MUST BE PRECEDED BY FULL PREFIX (EACH CORRECTIVE ACTION SHOULD BE
TAG REGULATORY OR LSC IDENTIFYING INFORMATION) TAG CROSS-REFERENCED TO THE APPROPRIATE
DEFICIENCY)
K 918 Continued From page 10 K 918 #4 QAPI
This plan has been reviewed at an ad hoc
Quality Assurance committee meeting
held on 12/13/24
The Administrator will report the results of
the monitoring to the QAPI committee for
review and recommendations for the time
frame of the monitoring period or as it is
amended by the committee.
(X5)
COMPLETE
DATE
AHCA Form 3020-0001
STATE FORM
6559 P3CC21
If continuation sheet 11 of 11
DEPARTMENT OF HEALTH AND HUMAN SERVICES
PRINTED: 01/14/2025
CENTERS FOR MEDICARE & MEDICAID SERVICES
FORM APPROVED
OMB NO. 0938-0391
SUMMARY OF DEFICIENCIES
(X1) PROVIDER/SUPPLIER/CLIA
(X2) MULTIPLE CONSTRUCTION
AND PLAN OF CORRECTION
IDENTIFICATION NUMBER:
A. BUILDING 01, 05
(X3) DATE SURVEY
COMPLETED
106081
B. WING
11/20/2024
NAME OF PROVIDER OR SUPPLIER
STREET ADDRESS, CITY, STATE, ZIP CODE
ARABELLA HEALTH & WELLNESS OF CARRABELLE
239 CROOKED RIVER ROAD
CARRABELLE, FL 32322
(X4) ID
SUMMARY STATEMENT OF DEFICIENCIES
ID
(X5)
PREFIX
TAG
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
PROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
CROSS-REFERENCED TO THE APPROPRIATE
DEFICIENCY)
COMPLETION
DATE
E 000 Initial Comments
E 000
During the recertification survey conducted on
11/20/2024 at Arabella Health and Wellness of
Carrabelle, a nursing home in Carrabelle, FL, the
Emergency Preparedness Program was
reviewed.
Arabella Health and Wellness of Carrabelle
complies with the Emergency Preparedness rule
per Code of Federal Regulations (CFR) 42, Part
483.73, Requirement for Long-Term Care
Facilities.
K 000 INITIAL COMMENTS
K 000
An unannounced Fire & Life Safety recertification
survey was conducted on 11/20/2024 at Arabella
Health and Wellness of Carrabelle, a nursing
home in Carrabelle, Florida. The facility was not
in compliance with Code of Federal Regulations
(CFR) 42, Part 483.90, Requirement for Long
Term Care Facilities: Physical Environment and
National Fire Protection Association (NFPA) 101
(2012 edition) requirements for nursing homes.
Initial Plan Review: 1986
Existing
NFPA 220 Construction Type: V (111)
Number of beds: 90
Census: 74
K 291 Emergency Lighting
K 291
12/13/24
SS=D CFR(s): NFPA 101
Emergency Lighting
Emergency lighting of at least 1-1/2-hour duration
is provided automatically in accordance with 7.9.
18.2.9.1, 19.2.9.1
THIS REQUIREMENT is not met as evidenced
by:
Based on record review and interview with the
#1 Corrective Action for affected
LABORATORY DIRECTOR'S OR PROVIDER/SUPPLIER REPRESENTATIVE'S SIGNATURE
TITLE
(X6) DATE
Electronically Signed
12/02/2024
Any deficiency statement ending with an asterisk (*) denotes a deficiency which the institution may be excused from correcting providing it is determined that
other safeguards provide sufficient protection to the patients. (See Instructions.) Except for nursing homes, the findings stated above are disclosable 90 days
following the date of survey whether or not a plan of correction is provided. For nursing homes, the above findings and plans of correction are disclosable 14
days following the date these documents are made available to the facility. If deficiencies are cited, an approved plan of correction is requisite to continued
program participation.
FORM CMS-2567(02-99) Previous Versions Obsolete
Event ID:P3CC21
Facility ID: 35961023
If continuation sheet Page 1 of 7
DEPARTMENT OF HEALTH AND HUMAN SERVICES
PRINTED: 01/14/2025
CENTERS FOR MEDICARE & MEDICAID SERVICES
FORM APPROVED
OMB NO. 0938-0391
SUMMARY OF DEFICIENCIES
(X1) PROVIDER/SUPPLIER/CLIA
(X2) MULTIPLE CONSTRUCTION
AND PLAN OF CORRECTION
IDENTIFICATION NUMBER:
A. BUILDING 01, 05
(X3) DATE SURVEY
COMPLETED
106081
B. WING
11/20/2024
NAME OF PROVIDER OR SUPPLIER
STREET ADDRESS, CITY, STATE, ZIP CODE
ARABELLA HEALTH & WELLNESS OF CARRABELLE
239 CROOKED RIVER ROAD
CARRABELLE, FL 32322
(X4) ID
SUMMARY STATEMENT OF DEFICIENCIES
ID
(X5)
PREFIX
TAG
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
PREFIX
TAG
PROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
COMPLETION
REGULATORY OR LSC IDENTIFYING INFORMATION)
CROSS-REFERENCED TO THE APPROPRIATE
DATE
DEFICIENCY)
K 291 Continued From page 1
Maintenance Director, the facility failed to provide
and maintain reliable emergency lighting. Testing
is required to insure the durability of the batteries
for the required period of time. This condition
could jeopardize the safety of patients and staff in
an emergency situation.
The findings include:
During the Fire & Life Safety document review of
the facility with the Director of Maintenance on
11/20/2024, no records were provided to verify
the emergency backup lighting received 90
minute testing.
The Maintenance Director verified these findings
at the times observed.
Monthly testing of emergency lights is required to
insure reliable operation in the event of a power
failure. Annual testing is required to insure the
durability of the batteries for the required period
of time as specified in NFPA 101 (2012 edition).
K 291 residents.
Monthly and Annual 90 minute testing of
the Emergency Lighting System as
specified in NFPA 101 (2012 edition) will
be completed and documents maintained
in Life Safety Binder by Maintenance
Director.
Battery Packs are on order for the lights
that need them.
#2 How will the facility identify other like
residents?
The Administrator and Maintenance
Director will ensure the Emergency
Lighting system is audited monthly and
annually per Life Safety Code to ensure
no further residents and staff will be
potentially affected in an emergency
situation by leaving areas dark.
#3 What will you do to prevent
recurrence?
To prevent this deficient practice from
recurring, the Maintenance Director has
been educated on the importance of
completing the required inspection of the
Emergency Lighting System per Life
Safety guidelines found in NFPA 101
(2012) and maintaining proper
documentation.
#4 How will you monitor and maintain
ongoing compliance?
To monitor and maintain ongoing
compliance the maintenance director will
document the inspection of the
Emergency Lighting System and report
findings to the Administrator monthly x 3
months.
The Administrator will source any needed
FORM CMS-2567(02-99) Previous Versions Obsolete
Event ID:P3CC21
Facility ID: 35991023
If continuation sheet Page 2 of 7
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
PRINTED: 01/14/2025
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION
(X1) PROVIDER/SUPPLIER/CLIA
IDENTIFICATION NUMBER:
106081
(X2) MULTIPLE CONSTRUCTION
A. BUILDING 01, 05
B. WING
(X3) DATE SURVEY
COMPLETED
11/20/2024
NAME OF PROVIDER OR SUPPLIER
ARABELLA HEALTH & WELLNESS OF CARRABELLE
STREET ADDRESS, CITY, STATE, ZIP CODE
239 CROOKED RIVER ROAD
CARRABELLE, FL 32322
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
ID
PREFIX
TAG
PROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
CROSS-REFERENCED TO THE APPROPRIATE
DEFICIENCY)
(X5)
COMPLETION
DATE
K 291
Continued From page 2
K 291
repair/replacement parts for the Lighting
System.
#4 QAPI
The Administrator will report the results of
the monitoring to the QAPI committee for
review and recommendations for the time
frame of the monitoring period or as it is
amended by the committee.
This plan has been reviewed at an ad hoc
Quality Assurance committee meeting
held on 12/13/2024.
K 363
SS=D
Corridor - Doors
CFR(s): NFPA 101
Corridor - Doors
Doors protecting corridor openings in other than
required enclosures of vertical openings, exits, or
hazardous areas resist the passage of smoke
and are made of 1 3/4 inch solid-bonded core
wood or other material capable of resisting fire for
at least 20 minutes. Doors in fully sprinklered
smoke compartments are only required to resist
the passage of smoke. Corridor doors and doors
to rooms containing flammable or combustible
materials have positive latching hardware. Roller
latches are prohibited by CMS regulation. These
requirements do not apply to auxiliary spaces that
do not contain flammable or combustible material.
Clearance between bottom of door and floor
covering is not exceeding 1 inch. Powered doors
complying with 7.2.1.9 are permissible if provided
with a device capable of keeping the door closed
when a force of 5 lbf is applied. There is no
impediment to the closing of the doors. Hold open
devices that release when the door is pushed or
pulled are permitted. Nonrated protective plates
of unlimited height are permitted. Dutch doors
K 363
12/13/24
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: P3CCZ1 Facility ID: 36961023 If continuation sheet Page 3 of 7
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
PRINTED: 01/14/2025
FORM APPROVED
OMB NO. 0938-0391
LIST OF DEFICIENCIES
AND PLAN OF CORRECTION
PROVIDER/SUPPLIER/CLIA
IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING 01, 05
(X3) DATE SURVEY
COMPLETED
106081
11/20/2024
NAME OF PROVIDER OR SUPPLIER
ARABELLA HEALTH & WELLNESS OF CARRABELLE
STREET ADDRESS, CITY, STATE, ZIP CODE
239 CROOKED RIVER ROAD
CARRABELLE, FL 32322
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
ID
PREFIX
TAG
PROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
CROSS-REFERENCED TO THE APPROPRIATE
DEFICIENCY)
(X5)
COMPLETION
DATE
K 363
Continued From page 3
K 363
meeting 19.3.6.3.6 are permitted. Door frames
shall be labeled and made of steel or other
materials in compliance with 8.3, unless the
smoke compartment is sprinklered. Fixed fire
window assemblies are allowed per 8.3. In
sprinklered compartments there are no
restrictions in area or fire resistance of glass or
frames in window assemblies.
19.3.6.3, 42 CFR Parts 403, 418, 460, 482, 483,
and 485
Show in REMARKS details of doors such as a fire
protection ratings, automatics closing devices,
etc.
This REQUIREMENT is not met as evidenced
by:
Based on observation and interview made during
the Fire & Life Safety Tour, the facility failed to
maintain proper maintenance of the Fire/Smoke
doors. This condition could result in smoke
compartments becoming involved in a fire and/or
smoke situation. This could allow fire, smoke and
fire gasses to enter the compartment, which
could impede or deny the exiting of occupants in
an emergency.
The findings include:
During the Fire & Life Safety tour of the facility
with the Maintenance Staff on 11/20/2024 from
10:00 am to 1:00 pm, it was observed that the
following fire and smoke doors had issues:
1. The nourishment room had holes in the door.
2. The soiled utility room had holes in the door.
3. The laundry room door was not latching.
4. The medical records room was not closing.
The Director of Maintenance was present during
the observation, and confirmed the findings.
#1 Corrective Action for affected
residents.
The auto closing latches on the Medical
Records Office door and the Laundry
Room door have been adjusted to close
properly on 11/21/2024.
The Smoke Doors leading into the
Nourishment Room and the Soiled Utility
Room that have holes are being
repaired. Vendor contacted 12/2/2024 (
Life Safety Services )
#2 How will the facility identify other like
residents?
An audit of all facility doors has been
completed by the Maintenance director to
identify any doors that do not close
properly per NFPA 101 (2012 edition),
Chapter 19, 19.3.6.3.5, Doors shall be
provided with a means for keeping the
door closed that is acceptable to the
authority having jurisdiction.
The audit was completed 11/21/24.
#3 What will you do to prevent
FORM CMS-2567(02-99) Previous Versions Obsolete
Event ID:P3CC21
Facility ID: 35991023
If continuation sheet Page 4 of 7
DEPARTMENT OF HEALTH AND HUMAN SERVICES
PRINTED: 01/14/2025
CENTERS FOR MEDICARE & MEDICAID SERVICES
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
(X1) PROVIDER/SUPPLIER/CLIA
(X2) MULTIPLE CONSTRUCTION
AND PLAN OF CORRECTION
IDENTIFICATION NUMBER:
A. BUILDING 01, 05
(X3) DATE SURVEY
COMPLETED
106081
B. WING
11/20/2024
NAME OF PROVIDER OR SUPPLIER
STREET ADDRESS, CITY, STATE, ZIP CODE
ARABELLA HEALTH & WELLNESS OF CARRABELLE
239 CROOKED RIVER ROAD
CARRABELLE, FL 32322
(X4) ID
SUMMARY STATEMENT OF DEFICIENCIES
ID
PROVIDER'S PLAN OF CORRECTION
PREFIX
TAG
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
(EACH CORRECTIVE ACTION SHOULD BE
CROSS-REFERENCED TO THE APPROPRIATE
DEFICIENCY)
(X5)
COMPLETION
DATE
K 363 Continued From page 4
K 363
Per NFPA 101 (2012 edition) Chapter 19, section
19.3.6.3.5, "Doors shall be provided with a means
for keeping the door closed that is acceptable to
the authority having jurisdiction."
recurrence?
To prevent this deficient practice from
recurring, the Maintenance Director has
been educated to round and visualize any
doors in the facility that do not latch
properly and to initiate repairs.
Staff has been re-educated at mandatory
in-service meeting to not place any tape
over a door latch or use a wedge to prop
a door open or prevent proper closing and
latching of any door per NFPA 101
guidelines.
#4 How will you monitor and maintain
ongoing compliance?
To monitor and maintain ongoing
compliance, the Maintenance Director will
document the rounding and report
findings to the Administrator weekly x 12
weeks.
The Administrator will source any needed
repair or replacement parts as needed.
#4 QAPI
This plan has been reviewed at an ad hoc
Quality Assurance committee meeting
held on 12/13/24.
The Administrator will report the results of
the monitoring to the QAPI committee for
review and recommendations for the time
frame of the monitoring period or as it is
amended by the committee.
K 914 Electrical Systems - Maintenance and Testing
K 914
SS=D CFR(s): NFPA 101
12/13/24
Electrical Systems - Maintenance and Testing
Hospital-grade receptacles at patient bed
locations and where deep sedation or general
FORM CMS-2567(02-99) Previous Versions Obsolete
Event ID:P3OC21
Facility ID: 35981023
If continuation sheet Page 5 of 7
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
PRINTED: 01/14/2025
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION
(X1) PROVIDER/SUPPLIER/CLIA
IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING 01, 05
(X3) DATE SURVEY
COMPLETED
106081
11/20/2024
NAME OF PROVIDER OR SUPPLIER
STREET ADDRESS, CITY, STATE, ZIP CODE
ARABELLA HEALTH & WELLNESS OF CARRABELLE
239 CROOKED RIVER ROAD
CARRABELLE, FL 32322
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
ID
PREFIX
TAG
PROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
CROSS-REFERENCED TO THE APPROPRIATE
DEFICIENCY)
(X5)
COMPLETION
DATE
K 914 Continued From page 5
anesthesia is administered, are tested after initial
installation, replacement or servicing. Additional
testing is performed at intervals defined by
documented performance data. Receptacles not
listed as hospital-grade at these locations are
tested at intervals not exceeding 12 months. Line
isolation monitors (LIM), if installed, are tested at
intervals of less than or equal to 1 month by
actuating the LIM test switch per 6.3.2.6.3.6, which
activates both visual and audible alarm. For
LIM circuits with automated self-testing, this
manual test is performed at intervals less than or
equal to 12 months. LIM circuits are tested per
6.3.3.3.2 after any repair or renovation to the
electric distribution system. Records are
maintained of required tests and associated
repairs or modifications, containing date, room or
area tested, and results.
6.3.4 (NFPA 99)
This REQUIREMENT is not met as evidenced
by:
Based on record review and interview with the
Maintenance Director, the facility failed to
maintain documentation for the exercising of the
main and feeder breakers. Failure to exercise
these breakers as required by the manufacturer
can lead to corrosion, among other issues, which
can cause a delay or an inability to transfer power
in a time of emergency. This could result in loss
of power to the facility in the event of a
simultaneous failure of the local utility and the
emergency generator, potentially endangering the
patients and occupants of the facility.
The findings include:
During the Fire & Life Safety document review of
the facility with the Director of Maintenance on
11/20/2024, no documentation was provided to
K 914
#1 Corrective Action for affected
residents.
Maintenance Director is responsible and
competent to complete an inhouse annual
inspection of Main and Feeder Circuit
Breaker test per NFPA 110 guidelines.
Completed on 12/10/2024.
#2 How will the facility identify other like
residents?
Maintenance Director to complete the
Main and Feeder Circuit Breaker testing
to ensure no delay in transfer or loss in
the event of emergency or power of
power per NFPA 101 9.1.2 and 110 8.4.7
(2012 edition).
#3 What will you do to prevent
FORM CMS-2567(02-99) Previous Versions Obsolete
Event ID:P3CC21
Facility ID: 35991023
If continuation sheet Page 6 of 7
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
PRINTED: 01/14/2025
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION
(X1) PROVIDER/SUPPLIER/CLIA
IDENTIFICATION NUMBER:
106081
(X2) MULTIPLE CONSTRUCTION
A. BUILDING 01, 05
B. WING
(X3) DATE SURVEY
COMPLETED
11/20/2024
NAME OF PROVIDER OR SUPPLIER
ARABELLA HEALTH & WELLNESS OF CARRABELLE
STREET ADDRESS, CITY, STATE, ZIP CODE
239 CROOKED RIVER ROAD
CARRABELLE, FL 32322
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
ID
PREFIX
TAG
PROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
CROSS-REFERENCED TO THE APPROPRIATE
DEFICIENCY)
(X5)
COMPLETION
DATE
K 914
Continued From page 6
show that the Main & Feeder Circuit Breakers were inspected annually as required, including periodic exercise in accordance with the manufacturer's recommendations.
An interview with the Maintenance Director revealed and acknowledged that the facility did not have a system in place or a preventative maintenance program to ensure compliance with NFPA 110 (2012 Edition).
Please refer to NFPA 101 (2012 Edition) section 9.1.2 and NFPA 110 (2012 Edition) section 8.4.7.
K 914
recurrence?
To prevent this from recurring the Maintenance Director has been educated on the importance of completing necessary audits of the generator main and feeder circuits and maintaining documentation of audits as part of our maintenance program to ensure compliance with NFPA 110 (2012 edition).
#4 How will you monitor and maintain ongoing compliance?
Maintenance Director and/or designee to maintain documentation and scheduling of the annual Main and Feeder /Breaker test annually and/or as required by guidelines.
#4 QAPI
This plan has been reviewed at an ad hoc Quality Assurance committee meeting held on 12/13/24
The Administrator will report the results of the monitoring to the QAPI committee for review and recommendations for the time frame of the monitoring period or as it is amended by the committee.
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: PSCCZ1 Facility ID: 36961023 If continuation sheet Page 7 of 7