Skip to main content

Inspection visit

Fire Safety inspection

Applewood Nursing Center, IncCMS #23537514 citations on this visit
14 citations recorded

Citations

14 citations recorded*CMS

This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.

What do CMS severity letters mean?

Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.

General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.

Each letter combines severity with scope: how many residents the deficiency affected.

  • 0211GeneralS&S Epotential for harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

  • 0324GeneralS&S Epotential for harm

    Provide properly protected cooking facilities.

  • 0331GeneralS&S Dpotential for harm

    Construct fire resistant interior walls.

  • 0342GeneralS&S Fpotential for harm

    Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.

  • 0351GeneralS&S Epotential for harm

    Install an approved automatic sprinkler system.

  • 0353GeneralS&S Fpotential for harm

    Inspect, test, and maintain automatic sprinkler systems.

  • 0362GeneralS&S Epotential for harm

    Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

  • 0363GeneralS&S Epotential for harm

    Install corridor and hallway doors that block smoke.

  • 0372GeneralS&S Epotential for harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

  • 0511GeneralS&S Dpotential for harm

    Have properly installed electrical wiring and gas equipment.

  • 0521GeneralS&S Fpotential for harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

  • 0918GeneralS&S Fpotential for harm

    Have generator or other power source capable of supplying service within 10 seconds.

  • 0923GeneralS&S Epotential for harm

    Have proper medical gas storage and administration areas.

  • 0321GeneralS&S Epotential for harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

FAQ · About this visit

Common questions about this visit

What happened during the May 3, 2024 survey of Applewood Nursing Center, Inc?

This was a inspection survey of Applewood Nursing Center, Inc on May 3, 2024. The surveyor cited 14 deficiencies, recorded on the federal Form 2567 statement of deficiencies.

Were any deficiencies cited at Applewood Nursing Center, Inc on May 3, 2024?

Yes, 14 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Keep aisles, corridors, and exits free of obstruction in case of emergency."

What type of survey was this?

This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.

Share this reportEmail

Next steps

Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.

Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.

Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.