Inspection visit
Fire Safety inspection
Citations
13 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0761GeneralS&S Dpotential for harm
To conduct inspection, testing and maintenance of fire doors by qualified individuals.
- 0916GeneralS&S Fpotential for harm
Have a battery powered remote alarm panel in a location accessible by operating personnel.
- 0291GeneralS&S Fpotential for harm
Install emergency lighting that can last at least 1 1/2 hours.
- 0343GeneralS&S Epotential for harm
Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.
- 0353GeneralS&S Fpotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0355GeneralS&S Epotential for harm
Properly select, install, inspect, or maintain portable fire extinguishes.
- 0522GeneralS&S Fpotential for harm
Have an externally vented heating system.
- 0700GeneralS&S Dpotential for harm
Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors.
- 0712GeneralS&S Fpotential for harm
Have simulated fire drills held at unexpected times.
- 0914GeneralS&S Fpotential for harm
Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
- 0918GeneralS&S Fpotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0920GeneralS&S Epotential for harm
Ensure proper usage of power strips and extension cords.
- 0351GeneralS&S Dpotential for harm
Install an approved automatic sprinkler system.
FAQ · About this visit
Common questions about this visit
What happened during the July 5, 2023 survey of JOHN KNOX VILLAGE CARE CENTER?
This was a inspection survey of JOHN KNOX VILLAGE CARE CENTER on July 5, 2023. The surveyor cited 13 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at JOHN KNOX VILLAGE CARE CENTER on July 5, 2023?
Yes, 13 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "To conduct inspection, testing and maintenance of fire doors by qualified individuals."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.
SourceView on CMS Care Compare