Inspection visit
Fire Safety inspection
Citations
13 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0041GeneralS&S Fpotential for harm
Implement emergency and standby power systems.
- 0222GeneralS&S Epotential for harm
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
- 0293GeneralS&S Epotential for harm
Have properly located and lighted "Exit" signs.
- 0324GeneralS&S Epotential for harm
Provide properly protected cooking facilities.
- 0345GeneralS&S Fpotential for harm
Have approved installation, maintenance and testing program for fire alarm systems.
- 0353GeneralS&S Fpotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0374GeneralS&S Epotential for harm
Install smoke barrier doors that can resist smoke for at least 20 minutes.
- 0511GeneralS&S Epotential for harm
Have properly installed electrical wiring and gas equipment.
- 0531GeneralS&S Fpotential for harm
Have elevators that firefighters can control in the event of a fire.
- 0712GeneralS&S Fpotential for harm
Have simulated fire drills held at unexpected times.
- 0741GeneralS&S Epotential for harm
Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
- 0914GeneralS&S Fpotential for harm
Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
- 0918GeneralS&S Fpotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
FAQ · About this visit
Common questions about this visit
What happened during the April 11, 2022 survey of LANSDOWNE VILLAGE?
This was a inspection survey of LANSDOWNE VILLAGE on April 11, 2022. The surveyor cited 13 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at LANSDOWNE VILLAGE on April 11, 2022?
Yes, 13 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Implement emergency and standby power systems."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.
SourceView on CMS Care Compare
Next steps
Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.
Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.
Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.