Inspection visit
Fire Safety inspection
Citations
30 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0711GeneralS&S Fpotential for harm
Provide a written emergency evacuation plan.
- 0004GeneralS&S Fpotential for harm
Develop and maintain an Emergency Preparedness Program (EP).
- 0015GeneralS&S Fpotential for harm
Address subsistence needs for staff and patients.
- 0039GeneralS&S Fpotential for harm
Conduct testing and exercise requirements.
- 0161GeneralS&S Epotential for harm
Use approved construction type or materials.
- 0211GeneralS&S Epotential for harm
Keep aisles, corridors, and exits free of obstruction in case of emergency.
- 0222GeneralS&S Epotential for harm
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
- 0223GeneralS&S Epotential for harm
Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
- 0291GeneralS&S Epotential for harm
Install emergency lighting that can last at least 1 1/2 hours.
- 0293GeneralS&S Epotential for harm
Have properly located and lighted "Exit" signs.
- 0321GeneralS&S Epotential for harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
- 0324GeneralS&S Epotential for harm
Provide properly protected cooking facilities.
- 0325GeneralS&S Epotential for harm
Have properly installed hallway dispensers for alcohol-based hand rub.
- 0345GeneralS&S Fpotential for harm
Have approved installation, maintenance and testing program for fire alarm systems.
- 0353GeneralS&S Fpotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0354GeneralS&S Fpotential for harm
Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.
- 0355GeneralS&S Fpotential for harm
Properly select, install, inspect, or maintain portable fire extinguishes.
- 0363GeneralS&S Epotential for harm
Install corridor and hallway doors that block smoke.
- 0364GeneralS&S Epotential for harm
Install properly constructed windows in hallway walls or doors.
- 0372GeneralS&S Fpotential for harm
Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
- 0374GeneralS&S Epotential for harm
Install smoke barrier doors that can resist smoke for at least 20 minutes.
- 0511GeneralS&S Fpotential for harm
Have properly installed electrical wiring and gas equipment.
- 0521GeneralS&S Fpotential for harm
Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
- 0712GeneralS&S Fpotential for harm
Have simulated fire drills held at unexpected times.
- 0741GeneralS&S Epotential for harm
Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
- 0901GeneralS&S Fpotential for harm
Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.
- 0914GeneralS&S Fpotential for harm
Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
- 0920GeneralS&S Fpotential for harm
Ensure proper usage of power strips and extension cords.
- 0921GeneralS&S Fpotential for harm
Ensure that testing and maintenance of electrical equipment is performed.
- 0030GeneralS&S Fpotential for harm
List the names and contact information of those in the facility.
FAQ · About this visit
Common questions about this visit
What happened during the January 27, 2023 survey of OAK PARK CARE CENTER?
This was a inspection survey of OAK PARK CARE CENTER on January 27, 2023. The surveyor cited 30 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at OAK PARK CARE CENTER on January 27, 2023?
Yes, 30 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Provide a written emergency evacuation plan."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.