MARGATE HEALTH AND REHABILITATION CENTER 5951 COLONIAL DRIVE, MARGATE, Florida, 33063
K0000 | Bldg. 01 | INITIAL COMMENTS | K0000 | An unannounced Fire & Life Safety recertification survey was conducted at Margate Health and Rehabilitation Center, a nursing home in Margate, Florida. The Facility is not in compliance with 42 CFR 483.90(a), and National Fire Protection Association (NFPA) 101 (2012 Edition), NFPA 99 (2012 Edition) requirements for nursing homes. Initial Plan Review: 1985 Existing NFPA 220 Construction Type: II (000) Number of beds: 170 Number of rooms sampled: 96 of 99 The following is a description of the deficiencies found at the time of the visit. |
K0923 | SS = D | Bldg. 01 | Gas Equipment - Cylinder and Container Storag | CFR(s): NFPA 101 | Gas Equipment - Cylinder and Container Storage | Greater than or equal to 3,000 cubic Storage locations are designed, constructed, and in accordance with 5.1.3.2.2 and 5.1.3.3.3. >300 but <3,000 cubic Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited-combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 (5 if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum hr. fire | K0923 | Gas Equipment - Cylinder and Container Storage NFPA 101 | Immediate Corrective Action: On . all tanks in excess of the allowable amount of 10 for the soiled utility room space, were removed and relocated to appropriate .. Storage rooms on other resident units. .. tank on ground in soiled utility room was immediately placed into crate/holder. No resident was affected by this deficient practice; however, the facility will ensure that all residents are protected, by conducting weekly audits of the .. storage in soiled utility rooms for appropriate storage at allowable limit, and that no .. tank is left unsecured on ground. |
105505
MARGATE HEALTH AND REHABILITATION CENTER 5951 COLONIAL DRIVE, MARGATE, Florida, 33063
PREFIX TAG ID PREFIX TAG CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) COMPLETION DATE
K0923 SS = D Bldg. 01 Continued from page 1
K0923 Continued from page 1
Less than or equal to 300 cubic protection rating. In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2. A precautionary sign readable from 5 is on each door or gate of a cylinder storage area, where the sign includes the wording as a minimum; "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING." Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge a threshold pressure considered empty is established. Empty cylinders are marked to avoid protected from weather. 11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99) This STANDARD is NOT met as evidenced by:
Based on observations and staff interview, the facility failed to maintain storage of cylinders, in accordance with NFPA 101. The findings included: During the Life Safety Survey tour of the facility on from 2:40 PM - 3:30 PM, with the Maintenance Staff, it was observed that the South Wing Soiled Utility Room was observed where there were 30 cylinders stored with other combustibles. Also, it was observed at the North Wing Soiled Utility Room that there were 1 of 3 cylinders unsecured on the ground. During an Interview with the Maintenance Director on at 3:30 PM, the Maintenance Director acknowledged this finding. This finding was also discussed and acknowledged by the Administrator during the exit conference. NFPA 101 (2012 Edition) 19.3.2.4 NFPA 99 (2012 Edition) 11.3.2.3(2), 11.6.2.3
Systematic Changes: An in-serviced education was provided to Director of Environmental Services and Maintenance staff, by Administrator, on the importance of proper storage limit of tanks in soiled utility rooms. An in-service was provided to staff, by Assistant Director of Nursing, about securing into holder/crate in soiled utility rooms. Monitoring: Environment Services Director/Designee will complete weekly observations of tank storage and security, in soiled utility rooms. All
findings and compliance will be reported to QA committee quarterly for up to 1 year.
5951 COLONIAL DRIVE, MARGATE, Florida, 33063
PREFIX PREFIX CROSS-REFERENCED TO THE COMPLETION DATE
E0000 Initial Comments E0000
During the Fire & Life Safety recertification survey conducted on at Margate Health and Rehabilitation Center, a nursing home, Emergency Preparedness was reviewed.
Margate Health and Rehabilitation is in compliance with Emergency Preparedness per Code of Federal Regulations (CFR) 42, Part 483.73, Requirement for Long-Term Care Facilities.
10510962 04/21/2026
5951 COLONIAL DRIVE, MARGATE, Florida, 33063
PREFIX PREFIX CROSS-REFERENCED TO THE COMPLETION DATE
K0000 Bldg. 05 INITIAL COMMENTS An unannounced Fire & Life Safety re-licensure survey was conducted on at Margate Health and Rehabilitation Center, a nursing home in Margate, Florida in accordance with National Fire Protection Association (NFPA) 1 and 101 (2021 Edition) and applicable requirements of 2021 Florida State Fire Marshal's Rules and Regulations, Florida Administrative Code (F.A.C.) 69A-3, F.A.C. 69A-53, F.A.C. 59A-4, and Florida Statutes (F.S.) 400 Part II, and F.S. 633.0215, adopting National Fire Protection Association (NFPA) 1 and 101 (2021 Edition) known as the Florida Fire Prevention Code and all NFPA referenced standards and requirements adopted per NFPA 101, Chapter 2. The following is a description of the deficiencies found at the time of the visit. K0000
K0923 SS = D Bldg. 05 Gas Equipment - Cylinder and Container Storag CFR(s): NFPA 99 Gas Equipment - Cylinder and Container Storage Greater than or equal to 3,000 cubic locations are designed, constructed, and in accordance with 5.1.3.3.2 and 5.1.3.3.3. >300 but Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited combustible construction, with door or gates (outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 (S - if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1hr. fire protection rating. Less than or equal to 300 cubic In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2. A precautionary sign readable from 5 is on each door or gate of K0923 K923: Gas Equipment - Cylinder and Container Storage NFPA 99 Immediate Corrective Action: On , all tanks in excess of the allowable amount of 10 for the soiled utility room space, were removed and relocated to appropriate Storage rooms on other resident units. tank on ground in soiled utility room was immediately placed into crate/holder. No resident was affected by this deficient practice; however, the facility will ensure that all residents are protected, by conducting weekly audits of the storage in soiled utility rooms for appropriate storage at allowable limit, and that no tank is left unsecured on ground. Systematic Changes: An in-serviced education was provided to Director of Environmental Services and Maintenance staff, by Administrator, on the importance of proper storage limit of , tanks in soiled utility rooms. An in-service was provided to staff, by Assistant
Office of Primary Care and Health Systems Management
10510962
04/21/2026
MARGATE HEALTH AND REHABILITATION CENTER
5951 COLONIAL DRIVE, MARGATE, Florida, 33063
PREFIX TAG ID PREFIX TAG CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) COMPLETION DATE
K0923 SS = D Bldg. 05 Continued from page 1 Continued from page 1 Director of Nursing, about securing tanks into holder/crate in soiled utility rooms.
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid . Cylinders stored in the open are protected from weather.
11.3, 11.3.5 through 11.3.12.5, 11.6.5 (NFPA 99)
This LICENSURE REQUIREMENT is NOT MET as evidenced by:
Based on observations and staff interview, the facility failed to maintain storage of cylinders, in accordance with NFPA 101¹.
The findings included:
During the Life Safety Survey tour of the facility from 2:40 PM - 3:30 PM, with the Maintenance Director, it was observed at the South Wing Soiled Utility Room that there were 30 cylinders stored with other combustibles. Also, it was observed at the North Wing Soiled Utility Room that there were 1 of 3 cylinders unsecured on the ground.
During an interview on at 3:30 PM, the Maintenance Director acknowledged this finding. This finding was also discussed and acknowledged by the Administrator during the exit conference.
NFPA 101 (2021 Edition) 19.3.2.4
NFPA 99 (2021 Edition) 11.3, 11.3.6, 11.3.6.3(2), 11.3.6.5, 11.6.2.3(11)
Class III
Monitoring:
Environment Services Director/Designee will complete weekly observations of tank storage and security, in soiled utility rooms and address findings immediately. All findings and compliance will be reported to QA committee quarterly for up to 1 year.