105519 NSPIRE HEALTHCARE PLANTATION 6931 W SUNRISE BLVD , PLANTATION, Florida, 33313 PREFIX TAG ID PREFIX TAG CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) COMPLETION DATE
K0000 INITIAL COMMENTS
K0000 /2026 An unannounced Fire & Life Safety Recertification survey was conducted on Plantation, a nursing home in Plantation, Florida. Nspire Healthcare Plantation is not in compliance with 42 CFR 483 Subpart B, 42 CFR 488.307, and National Fire Protection Association (NFPA) 101 (2012 Edition), NFPA 99 (2012 Edition) requirements for nursing homes. Initial Plan Review: 1983 Existing NFPA 220 Construction Type: II (111) Number of beds: 120 Census: 107 The following is a description of the noncompliance.
K0345 SS = F Bldg.-01 Fire Alarm System - Testing and Maintenance CFR(s): NFPA 101 Fire Alarm System - Testing and Maintenance
K0345 All smoke duct detectors identified as not sensitivity tested will be addressed/tested. The facility will be coordinating with the licensed fire alarm vendor to: Complete sensitivity testing on the 18 duct smoke detectors that were not tested during the biennial testing dated A 100% review of fire alarm testing records was conducted to ensure all devices are included and properly documented. Maintenance Director will be re-educated on NFPA 72 sensitivity testing requirements and the importance of reconciling all fire alarm testing reports for consistency and completeness prior to acceptance. Annual testing will be verified by the Maintenance Director and reviewed by the Administrator during Life Safety reviews. /2026 NSPIRE HEALTHCARE PLANTATION 6931 W SUNRISE BLVD, PLANTATION, Florida, 33313
K0345 SS = F Bldg. 01 Continued from page 1 The findings included: On , at 10:50 AM, during record review with the Regional Maintenance Director, it was revealed that the biennial smoke detector sensitivity testing, dated , did not include the 18 of 18 duct smoke detectors. An interview was conducted with the Regional Maintenance Director concurrently with the record review and he acknowledged the findings. The findings were reviewed with the Administrator and the Regional Maintenance Director at the exit conference on at 2:00 PM. NFPA 101 (2012 Edition) 4.6.12, 9.6, 19.3.4.1 NFPA 72 (2010 Edition) 7.7.1.1, 14.4.3.2, 14.4.4.3.2, 14.6.2.1 Photographic evidence obtained. K0345 105519 NSPIRE HEALTHCARE PLANTATION 6931 W SUNRISE BLVD , PLANTATION, Florida, 33313 PREFIX PREFIX CROSS-REFERENCED TO THE COMPLETION DATE
E0000 | Initial Comments | E0000 | | /2026 During the Fire & Life Safety Recertification survey, conducted on at Nspire Healthcare Plantation, a nursing home, Emergency Preparedness was reviewed. Nspire Healthcare Plantation is in compliance with Emergency Preparedness per Code of Federal Regulations (CFR) 42, Part 483.73, Requirement for Long-Term Care Facilities. Florida Department of Health PRINTED: 04/07/2026 03/10/2026 NSPIRE HEALTHCARE PLANTATION 6931 W SUNRISE BLVD, PLANTATION, Florida, 33313 PREFIX PREFIX CROSS-REFERENCED TO THE COMPLETION DATE
K0000 INITIAL COMMENTS K0000 An unannounced Fire & Life Safety re-licensure survey was conducted on at Nspire Healthcare Plantation, a nursing home in Plantation, Florida in accordance with National Fire Protection Association (NFPA) 1 and 101 (2021 Edition) and applicable requirements of Florida State Fire Marshal's Rules and Regulations, Florida Administrative Code (F.A.C.) 69A-3, F.A.C. 69A-53, F.A.C. 58A-4, and Florida Statutes (F.S.) 400 Part II, and F.S. 633.0215, adopting National Fire Protection Association (NFPA) 1 and 101 (2021 Edition) known as the Florida Fire Prevention Code and all NFPA referenced standards and requirements adopted per NFPA 101, Chapter 2. The following is a description of the deficiencies found at the time of the visit.
K0345 SS = F Bldg. 05 Fire Alarm System - Testing and Maintenance CFR(s): NFPA 101 K0345 Fire Alarm System - Testing and Maintenance Detection systems, where required, shall be in accordance with Section 9.6. Fire alarm systems required by this Code shall be installed, tested, and maintained in accordance with the applicable requirements of NFPA70 and NFPA72 unless otherwise permitted by 9.6.1.4. 18.3.4.1, 19.3.4.1, 9.6, and NFPA 70, and NFPA 72 This LICENSURE REQUIREMENT is NOT MET as evidenced by: Based on record review and staff interview, the facility failed to maintain their fire alarm system in accordance with NFPA 101, for 1 of 1 fire alarm system. This deficiency affects all residents and staff in facility. The findings included: On , at 10:50 AM, during record review with /2026 All smoke duct detectors identified as not sensitivity tested will be addressed/tested. The facility will be coordinating with the licensed fire alarm vendor to: Complete sensitivity testing on the 18 duct detectors that were not tested during the biennial testing dated. A 100% review of fire alarm testing records was conducted to ensure all devices are included and properly documented. Maintenance Director will be re-educated on NFPA 72 sensitivity testing requirements and the importance of reconciling all fire alarm testing reports for consistency and completeness prior to acceptance. Annual testing will be verified by the Maintenance Director and reviewed by the Administrator during Life Safety reviews. Office of Primary Care and Health Systems Management Agency: State Department of Health NSPIRE HEALTHCARE PLANTATION 6931 W SUNRISE BLVD , PLANTATION, Florida, 33313 PREFIX TAG ID PREFIX TAG CROSS-REFERENCED TO THE APPROPRIATE DEFICIENCY) COMPLETION DATE
K0345 SS = F Bldg. 05 Continued from page 1 it was revealed that the Regional Maintenance Director, it was revealed that the biennial smoke detector sensitivity testing, dated detectors. , did not include the 18 of 18 duct smoke detectors. An interview was conducted with the Regional Maintenance Director concurrently with the record review and he acknowledged the findings. The findings were reviewed with the Administrator and the Regional Maintenance Director at the exit conference on at 2:00 PM. NFPA 101 (2021 Edition) 4.6.12, 9.6, 19.3.4.1 NFPA 72 (2019 Edition) 7.7.1.1, 14.4.3.2, 14.4.4.3.2, 14.6.2.1 Photographic evidence obtained. Class III
K0345 STATE FORM

Reading this as a family member? Your long-term care ombudsman is a free advocate for residents and families.

Back to top

Citations

No citations recorded on this visit

The surveyor cited no deficiencies during this survey.

FAQ · About this visit

Common questions about this visit

What happened during the March 10, 2026 survey of NSPIRE HEALTHCARE PLANTATION?

This was a inspection survey of NSPIRE HEALTHCARE PLANTATION on March 10, 2026. The surveyor cited no deficiencies.

Were any deficiencies cited at NSPIRE HEALTHCARE PLANTATION on March 10, 2026?

No deficiencies were cited during this survey.

What type of survey was this?

This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.

Share this reportEmail

Next steps

Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.

Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.

Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.