Inspection visit
Fire Safety inspection
Citations
15 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0921GeneralS&S Fpotential for harm
Ensure that testing and maintenance of electrical equipment is performed.
- 0500GeneralS&S Epotential for harm
Meet other general requirements that are deficient.
- 0211GeneralS&S Epotential for harm
Keep aisles, corridors, and exits free of obstruction in case of emergency.
- 0222GeneralS&S Epotential for harm
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
- 0293GeneralS&S Fpotential for harm
Have properly located and lighted "Exit" signs.
- 0321GeneralS&S Epotential for harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
- 0324GeneralS&S Fpotential for harm
Provide properly protected cooking facilities.
- 0331GeneralS&S Epotential for harm
Construct fire resistant interior walls.
- 0345GeneralS&S Fpotential for harm
Have approved installation, maintenance and testing program for fire alarm systems.
- 0353GeneralS&S Epotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0363GeneralS&S Epotential for harm
Install corridor and hallway doors that block smoke.
- 0374GeneralS&S Fpotential for harm
Install smoke barrier doors that can resist smoke for at least 20 minutes.
- 0920GeneralS&S Epotential for harm
Ensure proper usage of power strips and extension cords.
- 0919GeneralS&S Epotential for harm
Meet requirements for the use of electrical equipment.
- 0923GeneralS&S Fpotential for harm
Have proper medical gas storage and administration areas.
FAQ · About this visit
Common questions about this visit
What happened during the April 9, 2025 survey of Beatrice Health and Rehabilitaion?
This was a inspection survey of Beatrice Health and Rehabilitaion on April 9, 2025. The surveyor cited 15 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at Beatrice Health and Rehabilitaion on April 9, 2025?
Yes, 15 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Ensure that testing and maintenance of electrical equipment is performed."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.
SourceView on CMS Care Compare
Next steps
Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.
Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.
Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.