Inspection visit
Fire Safety inspection
Citations
18 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0041GeneralS&S Fpotential for harm
Implement emergency and standby power systems.
- 0222GeneralS&S Epotential for harm
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
- 0232GeneralS&S Epotential for harm
Have corridors or aisles that are unobstructed and are at least 8 feet in width.
- 0291GeneralS&S Fpotential for harm
Install emergency lighting that can last at least 1 1/2 hours.
- 0321GeneralS&S Epotential for harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
- 0345GeneralS&S Fpotential for harm
Have approved installation, maintenance and testing program for fire alarm systems.
- 0353GeneralS&S Fpotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0354GeneralS&S Fpotential for harm
Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.
- 0500GeneralS&S Fpotential for harm
Meet other general requirements that are deficient.
- 0711GeneralS&S Fpotential for harm
Provide a written emergency evacuation plan.
- 0712GeneralS&S Fpotential for harm
Have simulated fire drills held at unexpected times.
- 0781GeneralS&S Epotential for harm
Have restrictions on the use of portable space heaters.
- 0912GeneralS&S Fpotential for harm
Have power receptacles that are properly grounded.
- 0914GeneralS&S Fpotential for harm
Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
- 0918GeneralS&S Fpotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0919GeneralS&S Epotential for harm
Meet requirements for the use of electrical equipment.
- 0920GeneralS&S Epotential for harm
Ensure proper usage of power strips and extension cords.
- 0922GeneralS&S Epotential for harm
Meet requirements for the use and maintenance of medical gas equipment.
FAQ · About this visit
Common questions about this visit
What happened during the July 13, 2023 survey of Gateway Vista?
This was a inspection survey of Gateway Vista on July 13, 2023. The surveyor cited 18 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at Gateway Vista on July 13, 2023?
Yes, 18 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Implement emergency and standby power systems."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.
SourceView on CMS Care Compare
Next steps
Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.
Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.
Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.