Skip to main content

Inspection visit

Fire Safety inspection

Brookestone of PapillionCMS #28526815 citations on this visit
15 citations recorded

Citations

15 citations recorded*CMS

This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.

What do CMS severity letters mean?

Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.

General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.

Each letter combines severity with scope: how many residents the deficiency affected.

  • 0161GeneralS&S Fpotential for harm

    Use approved construction type or materials.

  • 0211GeneralS&S Epotential for harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

  • 0222GeneralS&S Fpotential for harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

  • 0293GeneralS&S Fpotential for harm

    Have properly located and lighted "Exit" signs.

  • 0321GeneralS&S Fpotential for harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

  • 0324GeneralS&S Fpotential for harm

    Provide properly protected cooking facilities.

  • 0345GeneralS&S Fpotential for harm

    Have approved installation, maintenance and testing program for fire alarm systems.

  • 0353GeneralS&S Fpotential for harm

    Inspect, test, and maintain automatic sprinkler systems.

  • 0355GeneralS&S Fpotential for harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

  • 0363GeneralS&S Fpotential for harm

    Install corridor and hallway doors that block smoke.

  • 0712GeneralS&S Fpotential for harm

    Have simulated fire drills held at unexpected times.

  • 0761GeneralS&S Fpotential for harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

  • 0919GeneralS&S Fpotential for harm

    Meet requirements for the use of electrical equipment.

  • 0920GeneralS&S Epotential for harm

    Ensure proper usage of power strips and extension cords.

  • 0922GeneralS&S Epotential for harm

    Meet requirements for the use and maintenance of medical gas equipment.

FAQ · About this visit

Common questions about this visit

What happened during the November 8, 2022 survey of Brookestone of Papillion?

This was a inspection survey of Brookestone of Papillion on November 8, 2022. The surveyor cited 15 deficiencies, recorded on the federal Form 2567 statement of deficiencies.

Were any deficiencies cited at Brookestone of Papillion on November 8, 2022?

Yes, 15 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Use approved construction type or materials."

What type of survey was this?

This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.

Share this reportEmail

Next steps

Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.

Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.

Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.