Inspection visit
Fire Safety inspection
Citations
15 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0035GeneralS&S Epotential for harm
Provide family notifications of emergency plan.
- 0211GeneralS&S Epotential for harm
Keep aisles, corridors, and exits free of obstruction in case of emergency.
- 0222GeneralS&S Epotential for harm
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
- 0321GeneralS&S Epotential for harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
- 0325GeneralS&S Epotential for harm
Have properly installed hallway dispensers for alcohol-based hand rub.
- 0345GeneralS&S Fpotential for harm
Have approved installation, maintenance and testing program for fire alarm systems.
- 0353GeneralS&S Epotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0355GeneralS&S Epotential for harm
Properly select, install, inspect, or maintain portable fire extinguishes.
- 0363GeneralS&S Dpotential for harm
Install corridor and hallway doors that block smoke.
- 0371GeneralS&S Dpotential for harm
Have properly sized and located compartments to protect residents from smoke.
- 0511GeneralS&S Epotential for harm
Have properly installed electrical wiring and gas equipment.
- 0741GeneralS&S Epotential for harm
Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
- 0761GeneralS&S Epotential for harm
To conduct inspection, testing and maintenance of fire doors by qualified individuals.
- 0918GeneralS&S Epotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0324GeneralS&S Epotential for harm
Provide properly protected cooking facilities.
FAQ · About this visit
Common questions about this visit
What happened during the September 27, 2024 survey of COLLEGE PARK REHABILITATION CENTER?
This was a inspection survey of COLLEGE PARK REHABILITATION CENTER on September 27, 2024. The surveyor cited 15 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at COLLEGE PARK REHABILITATION CENTER on September 27, 2024?
Yes, 15 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Provide family notifications of emergency plan."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.
SourceView on CMS Care Compare
Next steps
Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.
Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.
Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.