Inspection visit
Fire Safety inspection
Citations
18 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0511GeneralS&S Dpotential for harm
Have properly installed electrical wiring and gas equipment.
- 0041GeneralS&S Epotential for harm
Implement emergency and standby power systems.
- 0291GeneralS&S Dpotential for harm
Install emergency lighting that can last at least 1 1/2 hours.
- 0324GeneralS&S Epotential for harm
Provide properly protected cooking facilities.
- 0341GeneralS&S Fpotential for harm
Install a fire alarm system that can be heard throughout the facility.
- 0345GeneralS&S Epotential for harm
Have approved installation, maintenance and testing program for fire alarm systems.
- 0353GeneralS&S Epotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0521GeneralS&S Epotential for harm
Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
- 0712GeneralS&S Dpotential for harm
Have simulated fire drills held at unexpected times.
- 0741GeneralS&S Fpotential for harm
Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
- 0918GeneralS&S Epotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0920GeneralS&S Dpotential for harm
Ensure proper usage of power strips and extension cords.
- 0923GeneralS&S Dpotential for harm
Have proper medical gas storage and administration areas.
- 0363GeneralS&S Epotential for harm
Install corridor and hallway doors that block smoke.
- 0015GeneralS&S Epotential for harm
Address subsistence needs for staff and patients.
- 0024GeneralS&S Dpotential for harm
Establish policies and procedures for volunteers.
- 0035GeneralS&S Dpotential for harm
Provide family notifications of emergency plan.
- 0037GeneralS&S Dpotential for harm
Establish staff and initial training requirements.
FAQ · About this visit
Common questions about this visit
What happened during the February 21, 2025 survey of CAREMERIDIAN LLC, DBA NEURORESTORATIVE?
This was a inspection survey of CAREMERIDIAN LLC, DBA NEURORESTORATIVE on February 21, 2025. The surveyor cited 18 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at CAREMERIDIAN LLC, DBA NEURORESTORATIVE on February 21, 2025?
Yes, 18 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Have properly installed electrical wiring and gas equipment."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.
SourceView on CMS Care Compare
Next steps
Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.
Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.
Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.