Inspection visit

Fire Safety inspection

HAMMONTON CENTER FOR REHABILITATION AND HEALTHCARECMS #31520911 citations on this visit
11 citations recorded

Citations

11 citations recorded*CMS

This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.

What do CMS severity letters mean?

Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.

General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.

Each letter combines severity with scope: how many residents the deficiency affected.

  • 0222GeneralS&S Epotential for harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

  • 0311GeneralS&S Dpotential for harm

    Have an enclosure around a vertical opening shaft.

  • 0321GeneralS&S Epotential for harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

  • 0341GeneralS&S Epotential for harm

    Install a fire alarm system that can be heard throughout the facility.

  • 0351GeneralS&S Epotential for harm

    Install an approved automatic sprinkler system.

  • 0355GeneralS&S Epotential for harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

  • 0364GeneralS&S Epotential for harm

    Install properly constructed windows in hallway walls or doors.

  • 0372GeneralS&S Epotential for harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

  • 0374GeneralS&S Fpotential for harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

  • 0521GeneralS&S Epotential for harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

  • 0918GeneralS&S Epotential for harm

    Have generator or other power source capable of supplying service within 10 seconds.

FAQ · About this visit

Common questions about this visit

What happened during the June 5, 2023 survey of HAMMONTON CENTER FOR REHABILITATION AND HEALTHCARE?

This was a inspection survey of HAMMONTON CENTER FOR REHABILITATION AND HEALTHCARE on June 5, 2023. The surveyor cited 11 deficiencies, recorded on the federal Form 2567 statement of deficiencies.

Were any deficiencies cited at HAMMONTON CENTER FOR REHABILITATION AND HEALTHCARE on June 5, 2023?

Yes, 11 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arra..."

What type of survey was this?

This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.

Share this reportEmail

Next steps

Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.

Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.

Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.