Inspection visit

Fire Safety inspection

COMPLETE CARE AT INGLEMOOR, LLCCMS #31534914 citations on this visit
14 citations recorded

Citations

14 citations recorded*CMS

This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.

What do CMS severity letters mean?

Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.

General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.

Each letter combines severity with scope: how many residents the deficiency affected.

  • 0541GeneralS&S Fpotential for harm

    Install properly constructed and protected linen or trash chutes.

  • 0041GeneralS&S Fpotential for harm

    Implement emergency and standby power systems.

  • 0223GeneralS&S Fpotential for harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

  • 0225GeneralS&S Fpotential for harm

    Have stairways and smokeproof enclosures used as exits that meet safety requirements.

  • 0321GeneralS&S Fpotential for harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

  • 0324GeneralS&S Fpotential for harm

    Provide properly protected cooking facilities.

  • 0353GeneralS&S Fpotential for harm

    Inspect, test, and maintain automatic sprinkler systems.

  • 0362GeneralS&S Fpotential for harm

    Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

  • 0521GeneralS&S Fpotential for harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

  • 0531GeneralS&S Fpotential for harm

    Have elevators that firefighters can control in the event of a fire.

  • 0914GeneralS&S Fpotential for harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

  • 0918GeneralS&S Fpotential for harm

    Have generator or other power source capable of supplying service within 10 seconds.

  • 0921GeneralS&S Fpotential for harm

    Ensure that testing and maintenance of electrical equipment is performed.

  • 0923GeneralS&S Fpotential for harm

    Have proper medical gas storage and administration areas.

FAQ · About this visit

Common questions about this visit

What happened during the March 13, 2025 survey of COMPLETE CARE AT INGLEMOOR, LLC?

This was a inspection survey of COMPLETE CARE AT INGLEMOOR, LLC on March 13, 2025. The surveyor cited 14 deficiencies, recorded on the federal Form 2567 statement of deficiencies.

Were any deficiencies cited at COMPLETE CARE AT INGLEMOOR, LLC on March 13, 2025?

Yes, 14 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Install properly constructed and protected linen or trash chutes."

What type of survey was this?

This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.