Inspection visit

Fire Safety inspection

TOLSTOY FOUNDATION REHABILITATION AND NRSG CENTERCMS #33531113 citations on this visit
13 citations recorded

Citations

13 citations recorded*CMS

This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.

What do CMS severity letters mean?

Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.

General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.

Each letter combines severity with scope: how many residents the deficiency affected.

  • 0007GeneralS&S Cno actual harm

    Address patient/client population and determine types of services needed.

  • 0026GeneralS&S Cno actual harm

    Establish roles under a Waiver declared by secretary.

  • 0252GeneralS&S Epotential for harm

    Provide at least two remote exits on each floor or fire section of the building.

  • 0293GeneralS&S Dpotential for harm

    Have properly located and lighted "Exit" signs.

  • 0321GeneralS&S Epotential for harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

  • 0345GeneralS&S Epotential for harm

    Have approved installation, maintenance and testing program for fire alarm systems.

  • 0353GeneralS&S Dpotential for harm

    Inspect, test, and maintain automatic sprinkler systems.

  • 0355GeneralS&S Dpotential for harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

  • 0761GeneralS&S Epotential for harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

  • 0901GeneralS&S Epotential for harm

    Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.

  • 0921GeneralS&S Epotential for harm

    Ensure that testing and maintenance of electrical equipment is performed.

  • 0923GeneralS&S Dpotential for harm

    Have proper medical gas storage and administration areas.

  • 0363GeneralS&S Epotential for harm

    Install corridor and hallway doors that block smoke.

FAQ · About this visit

Common questions about this visit

What happened during the June 4, 2024 survey of TOLSTOY FOUNDATION REHABILITATION AND NRSG CENTER?

This was a inspection survey of TOLSTOY FOUNDATION REHABILITATION AND NRSG CENTER on June 4, 2024. The surveyor cited 13 deficiencies, recorded on the federal Form 2567 statement of deficiencies.

Were any deficiencies cited at TOLSTOY FOUNDATION REHABILITATION AND NRSG CENTER on June 4, 2024?

Yes, 13 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Address patient/client population and determine types of services needed."

What type of survey was this?

This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.