Inspection visit
Fire Safety inspection
Citations
11 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0004GeneralS&S Cno actual harm
Develop and maintain an Emergency Preparedness Program (EP).
- 0006GeneralS&S Cno actual harm
Conduct risk assessment and an All-Hazards approach.
- 0291GeneralS&S Dpotential for harm
Install emergency lighting that can last at least 1 1/2 hours.
- 0321GeneralS&S Epotential for harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
- 0353GeneralS&S Dpotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0372GeneralS&S Dpotential for harm
Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
- 0511GeneralS&S Epotential for harm
Have properly installed electrical wiring and gas equipment.
- 0923GeneralS&S Epotential for harm
Have proper medical gas storage and administration areas.
- 0041GeneralS&S Cno actual harm
Implement emergency and standby power systems.
- 0271GeneralS&S Epotential for harm
Have exits that are accessible at all times.
- 0030GeneralS&S Cno actual harm
List the names and contact information of those in the facility.
FAQ · About this visit
Common questions about this visit
What happened during the November 12, 2020 survey of KING STREET HOME INC?
This was a inspection survey of KING STREET HOME INC on November 12, 2020. The surveyor cited 11 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at KING STREET HOME INC on November 12, 2020?
Yes, 11 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Develop and maintain an Emergency Preparedness Program (EP)."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.
SourceView on CMS Care Compare
Next steps
Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.
Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.
Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.