Inspection visit
Fire Safety inspection
Citations
15 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0374GeneralS&S Epotential for harm
Install smoke barrier doors that can resist smoke for at least 20 minutes.
- 0222GeneralS&S Epotential for harm
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
- 0281GeneralS&S Dpotential for harm
Install proper backup exit lighting.
- 0321GeneralS&S Dpotential for harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
- 0324GeneralS&S Epotential for harm
Provide properly protected cooking facilities.
- 0345GeneralS&S Epotential for harm
Have approved installation, maintenance and testing program for fire alarm systems.
- 0351GeneralS&S Dpotential for harm
Install an approved automatic sprinkler system.
- 0363GeneralS&S Dpotential for harm
Install corridor and hallway doors that block smoke.
- 0372GeneralS&S Epotential for harm
Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
- 0521GeneralS&S Epotential for harm
Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
- 0761GeneralS&S Epotential for harm
To conduct inspection, testing and maintenance of fire doors by qualified individuals.
- 0918GeneralS&S Epotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0920GeneralS&S Dpotential for harm
Ensure proper usage of power strips and extension cords.
- 0921GeneralS&S Epotential for harm
Ensure that testing and maintenance of electrical equipment is performed.
- 0923GeneralS&S Dpotential for harm
Have proper medical gas storage and administration areas.
FAQ · About this visit
Common questions about this visit
What happened during the April 16, 2024 survey of GOLDEN HILL NURSING AND REHABILITATION CENTER?
This was a inspection survey of GOLDEN HILL NURSING AND REHABILITATION CENTER on April 16, 2024. The surveyor cited 15 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at GOLDEN HILL NURSING AND REHABILITATION CENTER on April 16, 2024?
Yes, 15 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Install smoke barrier doors that can resist smoke for at least 20 minutes."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.