Inspection visit
Fire Safety inspection
Citations
12 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0222GeneralS&S Dpotential for harm
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
- 0321GeneralS&S Dpotential for harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
- 0345GeneralS&S Fpotential for harm
Have approved installation, maintenance and testing program for fire alarm systems.
- 0353GeneralS&S Dpotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0363GeneralS&S Dpotential for harm
Install corridor and hallway doors that block smoke.
- 0372GeneralS&S Epotential for harm
Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
- 0374GeneralS&S Fpotential for harm
Install smoke barrier doors that can resist smoke for at least 20 minutes.
- 0914GeneralS&S Dpotential for harm
Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
- 0923GeneralS&S Dpotential for harm
Have proper medical gas storage and administration areas.
- 0511GeneralS&S Fpotential for harm
Have properly installed electrical wiring and gas equipment.
- 0521GeneralS&S Dpotential for harm
Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
- 0211GeneralS&S Fpotential for harm
Keep aisles, corridors, and exits free of obstruction in case of emergency.
FAQ · About this visit
Common questions about this visit
What happened during the November 17, 2023 survey of Sapphire Ridge Health and Rehabilitation?
This was a inspection survey of Sapphire Ridge Health and Rehabilitation on November 17, 2023. The surveyor cited 12 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at Sapphire Ridge Health and Rehabilitation on November 17, 2023?
Yes, 12 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arra..."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.
SourceView on CMS Care Compare
Next steps
Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.
Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.
Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.