Skip to main content

Inspection visit

Fire Safety inspection

PARKSIDE NURSING AND REHABILITATION CENTERCMS #36536316 citations on this visit
16 citations recorded

Citations

16 citations recorded*CMS

This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.

What do CMS severity letters mean?

Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.

General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.

Each letter combines severity with scope: how many residents the deficiency affected.

  • 0291GeneralS&S Fpotential for harm

    Install emergency lighting that can last at least 1 1/2 hours.

  • 0223GeneralS&S Fpotential for harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

  • 0324GeneralS&S Fpotential for harm

    Provide properly protected cooking facilities.

  • 0344GeneralS&S Fpotential for harm

    Have an alternate power supply for its alarm system.

  • 0345GeneralS&S Fpotential for harm

    Have approved installation, maintenance and testing program for fire alarm systems.

  • 0351GeneralS&S Fpotential for harm

    Install an approved automatic sprinkler system.

  • 0353GeneralS&S Fpotential for harm

    Inspect, test, and maintain automatic sprinkler systems.

  • 0372GeneralS&S Epotential for harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

  • 0511GeneralS&S Fpotential for harm

    Have properly installed electrical wiring and gas equipment.

  • 0521GeneralS&S Fpotential for harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

  • 0711GeneralS&S Fpotential for harm

    Provide a written emergency evacuation plan.

  • 0914GeneralS&S Epotential for harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

  • 0918GeneralS&S Fpotential for harm

    Have generator or other power source capable of supplying service within 10 seconds.

  • 0920GeneralS&S Epotential for harm

    Ensure proper usage of power strips and extension cords.

  • 0741GeneralS&S Fpotential for harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

  • 0761GeneralS&S Fpotential for harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

FAQ · About this visit

Common questions about this visit

What happened during the June 27, 2022 survey of PARKSIDE NURSING AND REHABILITATION CENTER?

This was a inspection survey of PARKSIDE NURSING AND REHABILITATION CENTER on June 27, 2022. The surveyor cited 16 deficiencies, recorded on the federal Form 2567 statement of deficiencies.

Were any deficiencies cited at PARKSIDE NURSING AND REHABILITATION CENTER on June 27, 2022?

Yes, 16 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Install emergency lighting that can last at least 1 1/2 hours."

What type of survey was this?

This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.

Share this reportEmail

Next steps

Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.

Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.

Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.