Inspection visit
Fire Safety inspection
Citations
16 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0291GeneralS&S Fpotential for harm
Install emergency lighting that can last at least 1 1/2 hours.
- 0223GeneralS&S Fpotential for harm
Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
- 0324GeneralS&S Fpotential for harm
Provide properly protected cooking facilities.
- 0344GeneralS&S Fpotential for harm
Have an alternate power supply for its alarm system.
- 0345GeneralS&S Fpotential for harm
Have approved installation, maintenance and testing program for fire alarm systems.
- 0351GeneralS&S Fpotential for harm
Install an approved automatic sprinkler system.
- 0353GeneralS&S Fpotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0372GeneralS&S Epotential for harm
Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
- 0511GeneralS&S Fpotential for harm
Have properly installed electrical wiring and gas equipment.
- 0521GeneralS&S Fpotential for harm
Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
- 0711GeneralS&S Fpotential for harm
Provide a written emergency evacuation plan.
- 0914GeneralS&S Epotential for harm
Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
- 0918GeneralS&S Fpotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0920GeneralS&S Epotential for harm
Ensure proper usage of power strips and extension cords.
- 0741GeneralS&S Fpotential for harm
Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
- 0761GeneralS&S Fpotential for harm
To conduct inspection, testing and maintenance of fire doors by qualified individuals.
FAQ · About this visit
Common questions about this visit
What happened during the June 27, 2022 survey of PARKSIDE NURSING AND REHABILITATION CENTER?
This was a inspection survey of PARKSIDE NURSING AND REHABILITATION CENTER on June 27, 2022. The surveyor cited 16 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at PARKSIDE NURSING AND REHABILITATION CENTER on June 27, 2022?
Yes, 16 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Install emergency lighting that can last at least 1 1/2 hours."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.