Skip to main content

Inspection visit

Fire Safety inspection

WILLOWS HEALTH AND REHAB CTRCMS #36567014 citations on this visit
14 citations recorded

Citations

14 citations recorded*CMS

This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.

What do CMS severity letters mean?

Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.

General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.

Each letter combines severity with scope: how many residents the deficiency affected.

  • 0372GeneralS&S Fpotential for harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

  • 0161GeneralS&S Epotential for harm

    Use approved construction type or materials.

  • 0222GeneralS&S Epotential for harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

  • 0223GeneralS&S Epotential for harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

  • 0271GeneralS&S Epotential for harm

    Have exits that are accessible at all times.

  • 0321GeneralS&S Fpotential for harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

  • 0345GeneralS&S Fpotential for harm

    Have approved installation, maintenance and testing program for fire alarm systems.

  • 0351GeneralS&S Epotential for harm

    Install an approved automatic sprinkler system.

  • 0353GeneralS&S Fpotential for harm

    Inspect, test, and maintain automatic sprinkler systems.

  • 0500GeneralS&S Epotential for harm

    Meet other general requirements that are deficient.

  • 0511GeneralS&S Epotential for harm

    Have properly installed electrical wiring and gas equipment.

  • 0521GeneralS&S Fpotential for harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

  • 0781GeneralS&S Epotential for harm

    Have restrictions on the use of portable space heaters.

  • 0916GeneralS&S Fpotential for harm

    Have a battery powered remote alarm panel in a location accessible by operating personnel.

FAQ · About this visit

Common questions about this visit

What happened during the May 9, 2022 survey of WILLOWS HEALTH AND REHAB CTR?

This was a inspection survey of WILLOWS HEALTH AND REHAB CTR on May 9, 2022. The surveyor cited 14 deficiencies, recorded on the federal Form 2567 statement of deficiencies.

Were any deficiencies cited at WILLOWS HEALTH AND REHAB CTR on May 9, 2022?

Yes, 14 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Ensure smoke barriers are constructed to a 1 hour fire resistance rating."

What type of survey was this?

This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.

Share this reportEmail

Next steps

Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.

Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.

Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.