Inspection visit

Fire Safety inspection

SNU ARMSTRONG CO MEMORIAL HOSPCMS #39589013 citations on this visit
13 citations recorded

Citations

13 citations recorded*CMS

This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.

What do CMS severity letters mean?

Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.

General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.

Each letter combines severity with scope: how many residents the deficiency affected.

  • 0111GeneralS&S Epotential for harm

    Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy.

  • 0291GeneralS&S Dpotential for harm

    Install emergency lighting that can last at least 1 1/2 hours.

  • 0324GeneralS&S Cno actual harm

    Provide properly protected cooking facilities.

  • 0353GeneralS&S Fpotential for harm

    Inspect, test, and maintain automatic sprinkler systems.

  • 0355GeneralS&S Dpotential for harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

  • 0372GeneralS&S Fpotential for harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

  • 0374GeneralS&S Dpotential for harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

  • 0761GeneralS&S Dpotential for harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

  • 0908GeneralS&S Cno actual harm

    Ensure gas and vacuum systems are inspected and tested as part of a maintenance program.

  • 0911GeneralS&S Epotential for harm

    Meet requirements for the installation and maintenance of electrical systems.

  • 0912GeneralS&S Bno actual harm

    Have power receptacles that are properly grounded.

  • 0916GeneralS&S Fpotential for harm

    Have a battery powered remote alarm panel in a location accessible by operating personnel.

  • 0918GeneralS&S Fpotential for harm

    Have generator or other power source capable of supplying service within 10 seconds.

FAQ · About this visit

Common questions about this visit

What happened during the September 19, 2024 survey of SNU ARMSTRONG CO MEMORIAL HOSP?

This was a inspection survey of SNU ARMSTRONG CO MEMORIAL HOSP on September 19, 2024. The surveyor cited 13 deficiencies, recorded on the federal Form 2567 statement of deficiencies.

Were any deficiencies cited at SNU ARMSTRONG CO MEMORIAL HOSP on September 19, 2024?

Yes, 13 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy."

What type of survey was this?

This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.