Inspection visit
Fire Safety inspection
Citations
13 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0111GeneralS&S Epotential for harm
Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy.
- 0291GeneralS&S Dpotential for harm
Install emergency lighting that can last at least 1 1/2 hours.
- 0324GeneralS&S Cno actual harm
Provide properly protected cooking facilities.
- 0353GeneralS&S Fpotential for harm
Inspect, test, and maintain automatic sprinkler systems.
- 0355GeneralS&S Dpotential for harm
Properly select, install, inspect, or maintain portable fire extinguishes.
- 0372GeneralS&S Fpotential for harm
Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
- 0374GeneralS&S Dpotential for harm
Install smoke barrier doors that can resist smoke for at least 20 minutes.
- 0761GeneralS&S Dpotential for harm
To conduct inspection, testing and maintenance of fire doors by qualified individuals.
- 0908GeneralS&S Cno actual harm
Ensure gas and vacuum systems are inspected and tested as part of a maintenance program.
- 0911GeneralS&S Epotential for harm
Meet requirements for the installation and maintenance of electrical systems.
- 0912GeneralS&S Bno actual harm
Have power receptacles that are properly grounded.
- 0916GeneralS&S Fpotential for harm
Have a battery powered remote alarm panel in a location accessible by operating personnel.
- 0918GeneralS&S Fpotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
FAQ · About this visit
Common questions about this visit
What happened during the September 19, 2024 survey of SNU ARMSTRONG CO MEMORIAL HOSP?
This was a inspection survey of SNU ARMSTRONG CO MEMORIAL HOSP on September 19, 2024. The surveyor cited 13 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at SNU ARMSTRONG CO MEMORIAL HOSP on September 19, 2024?
Yes, 13 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.
SourceView on CMS Care Compare