Inspection visit
Fire Safety inspection
Citations
16 citations recorded*CMS
This is a Fire Safety survey. CMS cites these findings under the Life Safety Code and Emergency Preparedness rules, a separate set from the health (F-tag) deficiencies. The codes and grading differ, so these do not link to the health violation pages.
What do CMS severity letters mean?
Serious (G-L). Actual harm to a resident, or immediate jeopardy. Codes G through I indicate actual harm; J through L indicate immediate jeopardy to resident health or safety.
General (A-F). No actual harm found, or harm that is minimal. The facility must still submit a Plan of Correction. Most CMS citations land here.
Each letter combines severity with scope: how many residents the deficiency affected.
- 0007GeneralS&S Fpotential for harm
Address patient/client population and determine types of services needed.
- 0013GeneralS&S Fpotential for harm
Develop Emergency Preparedness policies and procedures.
- 0132GeneralS&S Dpotential for harm
Meet requirements for outpatient facilities located next to inpatient facilities separated by fire resistive construction.
- 0222GeneralS&S Epotential for harm
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
- 0741GeneralS&S Dpotential for harm
Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
- 0781GeneralS&S Epotential for harm
Have restrictions on the use of portable space heaters.
- 0918GeneralS&S Fpotential for harm
Have generator or other power source capable of supplying service within 10 seconds.
- 0920GeneralS&S Dpotential for harm
Ensure proper usage of power strips and extension cords.
- 0293GeneralS&S Epotential for harm
Have properly located and lighted "Exit" signs.
- 0311GeneralS&S Dpotential for harm
Have an enclosure around a vertical opening shaft.
- 0346GeneralS&S Fpotential for harm
Follow proper procedures when the fire alarm was out of service for more than 4 hours.
- 0347GeneralS&S Epotential for harm
Properly provide smoke detection systems in areas open to corridors.
- 0353GeneralS&S Cno actual harm
Inspect, test, and maintain automatic sprinkler systems.
- 0354GeneralS&S Fpotential for harm
Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.
- 0511GeneralS&S Epotential for harm
Have properly installed electrical wiring and gas equipment.
- 0541GeneralS&S Dpotential for harm
Install properly constructed and protected linen or trash chutes.
FAQ · About this visit
Common questions about this visit
What happened during the May 1, 2025 survey of Maplewood Center?
This was a inspection survey of Maplewood Center on May 1, 2025. The surveyor cited 16 deficiencies, recorded on the federal Form 2567 statement of deficiencies.
Were any deficiencies cited at Maplewood Center on May 1, 2025?
Yes, 16 deficiencies were cited, each with a CMS Scope and Severity grade. The first was: "Address patient/client population and determine types of services needed."
What type of survey was this?
This was a inspection survey conducted by state surveyors under federal Centers for Medicare & Medicaid Services (CMS) oversight. Findings are published on CMS Care Compare.
SourceView on CMS Care Compare
Next steps
Concerned about a resident’s care?Find your local ombudsman through the Eldercare Locatoror file a complaint with your state survey agency.
Researching this visit professionally?Book a 15-minute calland we will walk through what we have on file.
Data from CMS Care Compare public records. Dataset last refreshed . If you believe any information is inaccurate, report it here.